TEM

5025E

ISSUED JUL. 27’8

ENGINEERING MANUAL

ELECTRICAL & INSTRUMENTATIOB7 DRAFTING

.. -w.
PREPARATION OF

-— ELECTRICAL WORK DRAWING

.
, .
f
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
)
M ENOINEZRIX h. PREPARATION OF ELECTRICAL WORK DRAWING 5025E

ISSUED JUL.27’88 PAGE I CF 12

CONTENTS
PAGE
1. GENERAL

1.1 Purpose 2
1.2 Scope 2
1.3 Attentions Required in the Application 3
2. TITLE AND SYMSOLS TO BE USED IN DRAWINGS

2.1 Title of Drawing


2.2 Symbols to Be Used in Drawings
. ..-.
3. PREPARATION OF DRAWINGS

3.1 Common Requirements to Each Kind of Layout Dwg 4


3.2 Electrical Equipment Layout 5
3.3 Main Cable Route Plan 5
3.4 Wiring Layo~t 6
3.5 Grounding Layout 7
3.6 Lighting Layout 7
3.7 Communication System-Layout 8
3.8 Fire Alarm System Layout 9
3.9 Cable Rae!< (Duct) Layout 9
. 3.10 Cable Rack (Duct) Assembly 10
3.11 Typical Detail Drawing for Electrical 10
3.12 Connection Diagram 10
3.13 Cable Schedule for Electrical 11
3.14 Lighting Panelboard Circuit Schedule 12

At:ached Table 1. Sample Drawing List (Electrical)

.- .
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
/
b E.wxxE~xIx b. PREPARATION OF ELECTRICAL WOM. DRAWING 5025E
I I
ISSUED JUL.27’88 PAGZ 2 OF 12

1. GEhJERAL

1.1 PUTDOSE

This manual is intended to define the title, purpose of use, descripti~ns,


and the style of the drawings which are necesszry in the work of
installation of electrical equipment and wiring, and to show how to make
such drawings. .

1.2 Scope

(1) This manual applies to the drawings shown below.

serial Dwg -..-fi


Drawing Title Remarks
No. No.
I
1
I
Electrical Equipment Layout
I
I
52-54

2 Kain Cable Route Plan 80

3 Wiring Layout 55-57


I I
4 i Grounding Layout I 63-65 When Drawing Nos. of 63 to 65
74, 75 are not sufficient, use 74 and
75 for ‘gxounding for static-
electricity protection’ and
. ‘grounding for lightxing
—, protection’ , respectively.
5 I Lighting Layout 66-69

6 Comu=ication System Layout 76, 7-

7 Fire Alarm System Layout 78, 7!

8 Cable Rack (Duct) Layout 70, 71



9 Cable Rack (Duct) Assembly 72, 7:
10 Typical Detail Drawing for 5a, 5:
Electrical .. 7
11 Connection Diagram 60-62

~~ Cable Schedule for Electrical 8a


i3 Lighting Panelboarti CirCUit 89
Schedule

FORM A.G30.014
t
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
/
% EmINzxxIw b. PREPARATION OF ELECTRICAL WORK DRAWiNG 5025EI

& ISSUED JuL.27’8& PAGE 3 OF 12 I


(2) This manual does not apply to the drawings shown below.

Serial Drawing Title Dwg


Remarks
No. No.
1 Single Line Diagram 51

2 Hazardous Area Plan 96


.
3 Interlock Block Diagram 81, 82

4 Material List for Electrical 92

5 Cable Drum Schedule 93


.-s

1.3 Attentions Required in the App lication

(1) No standard is stipulated in regard to issuing of the drawings.


Therefore, confirm in each project with the assigned engineer about th~
kind of drawing to be prepared.

(2) In using this manual, refer also to the sample drawings pre?ared
separately.
Kinds of the sample drawings are as shown in the Attached Tabl= 1
“Sample Drawing List (Electrical)”.
.
(3) When any foreign country’s (non-Japanese) standards are to be applied
in the project there may be cases where the applicable symbols and alsc
design standards are quite different from those shown in this manual.
Therefore, discuss with the assigned engineers in regard to this
matter.

2. TITLE AND SYMBOLS TO BE USED IN DRAWINGS

2.1 Title of Drawing

(1) The titles of drawings shall be as those-shown in par. 1.2.


.. .
(2) The titles shall be in English, as a rule.

2.2 s @ols to Be Used in Drawinqs

The symtils in the drawings shall be in accordance with JiS C0301


“Graphic Symbols for Electrical Apparatus” and JIS C0303 “Graphical Symbols
of Indoor Wiring Diagram for Architectural Plansb for Project for Japan.

~ F-M A-G30.014
-?
.

TOKYO @ JAPAN
)
M EWINEERIK -,
ENGINEERING MANUALS
PREPARATION OF ELECTRICALWORK DRAWING
1- TEM

5025E

ISSUED JUL.27’88 PAGE 4 OF 12

3. PREPARATION OF DRAWINGS

The purpse of use and matters which at least shall be described are as
shown below for each kind of drawing. Examples of the drawings are shown in
the sample dzawings.

3.1 Common Requirements to Each Kind of Layout Drawinqs


.
(1) In case of some kinds of the layout drawings, many number of sheets
may be involved. In such cases, a drawing should be made which is to
be used exclusively as “explanation” made up of matters common to
such kind of drawing. In such “explanation”, the followings shall
be described.
.-L
(a) General notes

(b) Reference drawings

(c) symbols

(d) Explanation of cable mark

(e) Typical wiring illustration

(2) Descriptions required in each kind of drawings


.
(a) Indication of battery limit

(b) Drawing scale (scale with graduations)

(c) Key plan

(d) Indication of azimuth

(e) Routing of main cable (duct, rack, trench, etc.)

(f) Locations of major equipment (towers, tanks, rotating machinery,


, etc.), pipe racks, structures, buildings, etc.
.. .
(3) Attentions required

(a) Each of the layout drawings may be made by use of a base drawing,
which is a reproducible original of the plot plan dzawing made in
advance.

(b) Drawing scale shall be 1/100 as a standard. However, in cases


of “Main Cable Route Plan” and “Cable Rack Layout”, etc., other
scale may be chosen depending on the plant size, in order to
reduce the number of divided sheets involved.

(c) Any matters which are to be heeded in the construction work, but
cannot be depicted in drawing, should be indicated by “Notes”
described in blank spaces.
.
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
/
ti Ew~xz~x~x -. PREPARATION OF ELECTRICAL WORK DRAWING 5025E

ISSUED JUL.27’88 PAGE 5 OF 12


b

(d) Size of the drawing sheets shall be AO or Al, as a rule.

3.2 Electrical Equipment Lavout

(1) Purpose of use

(a) As information for civil design


.
(b) Installation of electrical equipment

(2) Matters to be described

(a) Outline sha?e, dimensions, location relationship, direction and


state of installation, and Identification No. of each equipment .--%
(switchboard; transformer, battery, etc.) to be installed.
-.
(b) Location of main cable route (duct, rack, trench, etc.)

(c) Section views and dimensions at parts properly selected.

(d) Distances between the equipment and buildinq,


- includinb. the
indication of the openings-of the building for carrying-in of the
equipment. -

Remarks: 1. To show the outline dimensions of equipment to be installed,


. use the finally tietermined dimensions on the manufacturer’s
drawings.
2. Depict the outline of equipment to be installed in such a way
that it represent the actual shape.
3. Size and shape of columns, thickness of walls, etc. shall be
depicted to scale, and the location of windows and doorways
should be indicated.
4. For columns, the column No. should be indicated, together with
dimensions of spacing between columns and length of center
line.
5. Dimensions of ducts, racks, trenches, etc. shall be indicated
when the drawing is made as information for civil design,
, whereas only the location of these should be shown by dotted
line when the drawing is mde to be issued “to the customer or
to the site.

3.3 Main Cable Route Plan

(1) Pur~se of use

(a) Detail design for construction and site work

(b) As information for civil design and process piping design

(2) Matters to be described

(a) Location, height, and scope of work relationship of the main


cable routes (dugts, racks, trenches, etc.)

F-M A-G30.014
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
k EW’INXEmM h. PREPARATION OF ELECTRICAL WORK DRAWING 5025E
I }
ISSUED JUL.27’88 PAGE 6 OF 12

(b) Dimensions of the main cable routes

(c) Location, height, and dimensions of the junction boxes, manholes,


etc.

Remark: This drawing should be made by use of a reproducible original


of the plot plan, which in made by piping design department.

3.4 Wirinq Lavout

(1) Pur~se of use

(a) Site work


---%
(b) Take-off of materials

(2) Matters to be described

Matters to be shown by Matters to be indicated


svmbols and lines supplementarily
(a) Motors Equipemnt No., rated output
(b) Generators Ditto , ditto
(c) Electric heaters Ditto rated capacity
(d! Capacitors Ditto ditto
(e) Transformers Ditto di~to
. (f) Battery chargers(Rectifiers) Ditto ditto
(g) Batteries Ditto ditto
(h) Inverters (UPS) Ditto ditto
(i) Switchboards Ditto
(j) Control boards Ditto
(k) Power sup?lyboxes for site work Ditto
(1) Lighting panelboards Ditto
(m) Junction boxes Serial No.
(n) Routing of cables Kind, No. of cores, size,
.— I size of conduit tube

Remarks: 1. Where the installation level of equipment is 2 m or more from


Ground Level or Floor Level, elevation shall be indicated.
2. When determining the key @an, pay enough considerations not
to have splits on short-distance cables from the main cable
route to the motor, etc.
3. 2 or more cables on the same route shall be shown by one line.
H o w e v e r , H.V. cables are to be shown as distinct from L.V.
cables.
4. Cable draw-in or dzaw-out point of each equipment shall be
shown in a manner that it represent the @sition of terminal
boxes.
5. In this drawing, the trunk line from the main switchboard in
the switch room to the lighting panelboard shall also be
indicated.
6. Where any conduit tube passes through from non-hazardous area
to hazardous area and requires sealing, such parts shall be
indicated by symbols.

FWM A-G30.014
J
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
)
- EMINE~RIW k. PREPARATION OF ELECTRICAL WORK DRAWING 5025E

ISSUED J~~.27’88 PAGE 7


L OF 12

3.5 Groundi>u Lavout

(1) Pur?ose of use

(a) Site WOK!<

(b) Take-off of materials

(2) Matters to be discribed

Matters to be shown by I Matters to be indicated


svmbols and lines I suDolementarily
(a) Electrical equipment requiring Equipment No.
grounding . ., . *
(b) Piping, tanks, etc. Line No. of piping,
requiring grounding ‘for static Equipment No. of the tank
electricity protection
(c) Towers, tanks, structures, etc. Equipment No. of the tower/tank
requiring qrounding for lightning Name of the structure
protection
(d) Routing of wires Kind, size, and size of conduit
tube
( e ) Groundinq electrodes Classification

Remarks: 1. AS for grounding electrdes, indicate also those necessary


. f~r instrument pznels in the control room, in ordez to ShOW
that they are within the scope of work.
2. In between the groun6ing main line and the groundicg
electrtie, terminals for measuring grounding resistance
should be provided.
3. Althouqh the design and work on grounding electrodes for
lightning protection of buildings are within the scope of
ci’?il department, indicate the location of such grounding
electrodes so that their relationship with other qrounding
electrodes be understood.

3.6 Liqhting Layout


.. .
(1) Purpose of use

(a) Site work-

(b) Take-off of materials

(2) Matters to be described

Matters to be shown by Matters to be in~icat=d


s ymbols and lines suDDlementarv
(a) Lighting fixtures Type, kind, capacity, panelboard
(incl, receptacles) No., te-rminal No. at panelboard
(b) Lighting panelboards Equipment No.
(c) Routing of cables and wires Circuit No. at panelboard,
.- Size, No. of run,
1 Size of conduit tube

~ FORM A-G20.014
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
)
Tm hxxzzww cm. PREPARATION OF ELECTRICAL WORK DR~wING 5025E

1 ISSUED ~~L.27’88 PAGE E OF 12

Remarks: 1. Depict sectional views of the related towers, tanks,


str~ct~res, etc., and indicate the location of the lighting
fixtures together with the direction of illumination.
2. Location of the panelboard, receptacles, lights, etc. shall
be determined in considerations of convenience in the
operation of the plant.
3. Pay attention to the location of columns, beams windows,
indoor ptpingt doorways, staircases, cables for running
cranes, etc. in the building and to the location of
piping/suggorts, staircases for structures and platforms,
gauges, safety valves, etc. of towersjtanks, in outside of
the building, in order to avoid any improper relationship.
4. Determine the location of the lightin~ fixtures, so that
cleaning and replacement of the lamps can be done easily. ---~
5. When depicting fixtur=s to be installed at above and below a
platform of tower and tank on the same plane of the drawing,
those above the platform should be in full line and those
below the platform in dotted line.
6. Vertically up-going wiring up to any platform of towers and
tanks shall be at the right side of the cat ladder and at the
outside of that cat ladder.

3.7 Communication System Layout

(1) Purpose of use

(a) Site work

(b) Take-off of materials

(2) Matters to be described

Matters to be shown by Matters to be indicated


sytiols and lines supplementarily
(a) Telephone sets Equipment No.
(b) Loudspeakers Ditto
(c) Amplifiers Ditto
(d) Handsets Ditto
(e) Routing of cables and-wires . Kind, No. of cores, size,
size of conduit tube
(f) Junction boxes Serial No.

Remarks: 1. System diagrams of each communication system shall


preferably be shown on this drawing or on ssparate sheets to
be attached.
2. This drawing shall be made in the same manner-as “Wiring
Layout” and “Lighting Layout”.

FORM A-G30,014
ENGINEERING MANUAiS TEM
T OK Y O @ JAPAN
W E;IXEZRXW -. PREPARATION OF ELECTRICAL” WORK DRAWING 5025E
J

IsSUED JUL.27’88 PAGE 9 OF 12

3.8 Fire Alarm Svstem Layout

(1) Purpose of use

(a) Site wor!<

(b) Take-off of materials

(2) Matters to be desczibed

Matters to be shown by Matters to be indicated


symbols and Lines suDulementzrily
(a) Detectors Equipment No.
(b) Transmitters ditto ..-=
(c) Receivers . ditto
(d) Routing of cables and wires Kind, No. of cores, size,
— size of canduit tube
(e) Junction boxes Serial No.

Remark: System diagram shall preferably be shown on this drawing or on


separate sheets to be attached.

3.9 Cable ~ac?< (Duct) I,ayou~

(1) Purpose of use

(a) Site work

(b) As infornst:on for civil design an~ process piping design

(c) Take-off of materials

(2) Matters to be d=scribed

(a) Location, height, and scope of work relationship of the racks


(ducts)
-
(b) Width and tyge of racks (ducts) and No. of stages of the rack
.- .
(c) Location of supports

(d) Method of sealing at wall-penetrations

(e) Section views and dimensions at parts properly selected.

Remark: Detailed fabrication drawing shall be shown on the “Cable


Rack (duct) Assembly”.

FWM A-G30.014
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
/
m EmIxzzRIw k. PREPARATION OF ELECTRICAL WORK DRAWING 5025E

ISSUED JUL.27’88 PAGE 10 OF 12

3.10 Cable Rack (Duct) Assembly

(1) Purpose of use

(a) Instruction on fabrication for manufacturer

(b) Site work

(c) Take-off of materials

(2) Matters to be described

(a) Necessary instructions on fabrication (Specifications such as


material, dimensions) . ..-=

(b) Quantity

Remark: The size of drawing shall be A3 as a rule. Describe titles


and drawing No. on the cover sheet, so that each assembly
drawing can be treated by Sheet No.

3.11 Typical Detail Drawinq for Electrical

(1) Purpose of use


. (a) Site work (installation, connection)

(b) Take-off of materials

(2) Matters to be described

(a) Methods of fabrication, installation and connection which are


general and not shown in any of the other electrical work
drawings.

(b) Detail work method for equipment which requires special


fabrication, installation, or connection.

. (c) Materials necessary--for the above (a) and (b) “

Remarks: 1. Methods of common type of work shall be shown by use of


standard drawings which has been prepared separately, not
by making drawings for each project.
2. The size of drawing shall be A3 as a rule. Describe
titles and drawing No. on the cover sheet, so that each
typical drawing can be treated by Sheet No.

3.12 Connection Diaqram

(1) Purpose of use

(a) Site work (connection)

F-M A-G30.014
?
ENGINEERING MANUALS TEM
TOKYO @ JAPAN
)
~” EMINEZRIX * PREPARATION OF ELECTRICAL” WORK DRAWING 5025E

ISSUED Ju~.27’88 PAGE 11 OF 12

(b) Maintenance, expansion

(c) Inspection on the site wor!c .

(2) Matters to be described

Matters to be shown by I Matters to be indicated


symbols and lines - I sup~lementarilv
(a) Switchboards and distribution Equipment No., Unit No.,
boards including terminal boards, Terminal No.
for each object equipment
(b) Object equi?ment including Equipment No., equipment name,
terminal boar6s terminal No., capacity
(c) Local control switch stations Equipment name, equipment No. . . . . .
including terminal boards
(d) Instrument panels including Equipment name, equipment’ No.,
— terminal boards terminal No.
(e) Equipment related in regard with Equipment name, terminal No.
sequence, including terminal
boards
(f) Cable interconnecting between Cable mark, color or No. for
each equipment identification of cores

Remarks: 1. Grounding wires shall not be entered.


2. This drawing shall be made in one sheet per each
. equipment. However, in some caszs, equipments belonging to
the same sequence may be shown on one sheet with a table of
them.
3. The size of drawing shall be A3 as a rule. Describe
titles and drawing No. on the cover sheet, so that each
connection diagram can be tr2ated by Sheet No.

3.13 Cable Schedule for Electrical

(1) PurWse of use


-.
(a) Laying of cable

(b) Maintenance, expans<on , .


.

(c) Inspection on site work

(d) ‘Take-off of materials

(2) Matters to be described

(a) Equipment No. or equipment name

(b) Cable mark

(c) Rated voltage, type, No. of cores, size, length, and drum No. of
the cable

FWM A-G30.014
10
TOKYO
I
/ JAPAN

- EMIN~ERIM -.
ENGINEERING MANUALS
PREPARATION OF Electrical WORK DRAWING
TEM

5025E

I ISSUED JUL.27’88 PAGE 12 OF 12

(d) Purpose and rated capacity of the object equipment — in the


column of “Remarks”.

This drawing shall be made by use of the designated A3


Remarks: 1.
sheets (Form B-BH 13.005 — 1/3 to 3/3), as a rule.
2. The cable marks shall be indicated in accordance with
TEM-5020 “How to Assign Cable Marks”. However, other
methods may be applied, if dictated by the nature of
project or by customer’s requirements.
3. The drum No. should be indicated in accordance with TEM-
5150 “How to Assign Drum No. for Cables and Wires”.
Eowever, other methods may be a?plied, if dictated by the
nature of project or by customer’s requirements.
. . ..L
3.14 Liqhtinq Panelboard Circuit Schedule

(1) ?urpose of use

(a) As information for manufacturers

(b) Site work

(c) Take-off of materials

(2) Matters to be described


.
(a) Branch circuit No.

(b) Dwg No. of “Lighting Layout Dwg” where the object lighting
fixtures are described.

(c) Kind, capacity, and quantity of the object lighting fixtures

(d) For each branch circuit — total capacity, current, and the size
of cable or wire to be connected.

(e) Internal connection drawing of the distribution boards

(f) Hub size of openning for wire ~aw-in/out of the distribution


bards

(g) Specification of internal switches of the distribution boards

Remarks: 1. Entry of the lighting fixtures shall be done for each of day-
and-night lights, night lights, and emergency lights,
separately.
2. The drawing shall be made on” one sheet per each distribution
bard.
3. The size of drawing shall be A3, as a rule.

F~M A-G30.014
TEM5025E

Attached Table 1-1/1

Attached Table 1. Sample Drawing List (Electrical)

1. Single Line Diagram D57-0000-51-O

2. Electrical Equipment Layout D57-0000-52-O

3. Wiring Layout D57-0000-55A,B

4. Cable Rack and Duct Layout D57-0000–70-O


..=
5. Typical Detail Drawing B57-0000-59-O
-.
6. Connection Diagram B57-0000-60-O

7. Grounding Layout D57-0000-63A,B

8. Lighting Layout D57-0000-66A,B

9. Interlack Block Diagram - D57-0000-81-O

10. Motor Schedule B57-0000–83-O

11. Cable Schedule B57-0000-88-O

12. Lighting Panelboard Circuit Schedule B57-0000-89-O

13. Hazardous Area Plan D57-0000-96-O

.- .