Professional Documents
Culture Documents
Loadestimation
Loadestimation
1.Load Estimation
In this chapter we will take new area and calculate the load estimation of each
part of this area so at the 1st we will show the figures of these parts to take off the
dimensions of each house or villa in each part and the dimension of each street and
garden.
-4-
Chapter 1 Load Estimation
Fig.1-2 This a picture for the full project which have 7 parts .
-5-
Chapter 1 Load Estimation
To take off the dimension we will take each part of the seven parts of the 3rd
place in the city of Al-Asher Men Ramadan alone to see if it has the same dimension of
each building or not and take off all dimension of these building as houses, Villas,
streets, and gardens. The following figures show each part of the city .
-6-
Chapter 1 Load Estimation
-7-
Chapter 1 Load Estimation
1.2 Distribution
Circuits and
Load Estimation
1.2.1 Maximum
Demand and
Diversity
-8-
Chapter 1 Load Estimation
If a ring circuit feeds fifteen 13 A sockets, the maximum demand clearly should
not be 15 x 13 = 195 A, if only because the circuit protection will not be rated at more
than 32 A. Some 13 A sockets may feed table lamps with 60 W lamps fitted, whilst
others may feed 3 kW washing machines; others again may not be loaded at all.
Lighting circuits pose a special problem when determining MD. Each lamp-
holder must be assumed to carry the current required by the connected load, subject to a
minimum loading of 100 W per lamp-holder (a demand of 0.42 A per lamp-holder at
240 V). Discharge lamps are particularly difficult to assess, and current cannot be
calculated simply by dividing lamp power by supply voltage. The reasons for this are:
3. - chokes and other control gear usually distort the waveform of the current so that it
contains harmonics which are additional to the fundamental supply current.
1.2.1.2 Diversity
-9-
Chapter 1 Load Estimation
In practice, the chances of all domestic ring sockets feeding loads taking 13 A
are small. Whilst there may be a 3 kW washing machine in the kitchen, a 3 kW heater in
the living room and another in the bedroom, the chance of all three being in use at the
same time is remote. If they are all connected at the same time, this could be seen as a
failure of the designer when assessing the installation requirements; the installation
should have two ring circuits to feed the parts of the house in question.
Most sockets, then, will feed smaller loads such as table lamps, vacuum cleaner,
television or audio machines and so on. The chances of all the sockets being used
simultaneously is remote in the extreme provided that the number of sockets (and ring
circuits) installed is large enough. The condition that only a few sockets will be in use at
the same time, and that the loads they feed will be small is called diversity.
Apart from indicating that diversity and maximum demand must be assessed, the
Regulations themselves give little help. Suggestions of values for the allowances
Distribution boards must not have diversity applied so that they can carry the total load
connected to them.
1.3 Calculation
In this project we will make design for Load Estimation for Houses and villas
and moles with Demand Factor 0.6
-10-
Chapter 1 Load Estimation
10 m
20 m
2) The 2nd areas show in Fig.1-11 of small villa consist of two floors each one
1200m2 have two villas. It mean Each villa have 600m2( 40% of the area for
the building "240m2" and 60% for the Garden of the villa "360 m2m2" ).
30 m
40 m
3) The 3rd areas show in Fig.1-12 of big villa consist of two floors each one
1200m2 have one ( 40% of the area for the building "480m2" and 60% for the
Garden of the villa "720m2" ).
-11-
Chapter 1 Load Estimation
30 m
40 m
4) The 4th areas show in Fig.1-13 of Big houses consist of three floors each one
300m2 have two flat. It mean Each flat have 150m2.
15 m
20 m
5) The 5th areas show in Fig.1-14 of houses consist of three floors each one
200m2 have two flat. It mean Each flat have 100m2. the 1st floor used as
moles.
10 m
20 m
Fig1-14 for houses with 3 floors (1st floor moles ,2nd,and 3rd floor flats ).
-12-
Chapter 1 Load Estimation
First method:-
By calculate each load in the flat by the watt unit and multiply it in DEMAND
FACTOR about 0.6 for all loads in the flat.
Second method:-
By measuring the load of lighting by the area. Then add the loads of the basics
Load using DEMAND FACTOR 100% And add the Total load of the electrical
appliances using DEMAND FACTOR 60%
Lighting: "DEMAND FACTOR 60% for houses and 65% for villas"
-13-
Chapter 1 Load Estimation
electrical appliances:
We will use the following table for calculate the load estimation
for the three types of area in the city.
Tables for calculate the load estimation of each place " houses and villas". :-
Table 1-1: types of loads
-14-
Chapter 1 Load Estimation
Schools 32.28
Banks 21.52
Hospitals 21.52
Hotels 21.52
Stores 32.28
Mosques 10.76
Parking 5.38
Restaurants 21.52
Offices 53.8
Stores 2.7
Theaters 10.76
-15-
Chapter 1 Load Estimation
-16-
Chapter 1 Load Estimation
a) Basic load:
Electric refrigerator + Washing Machine = 800+500 =1200W
b) Lighting:
100 m2 * 11VA = 1100VA * 0.6 = 660W
c) electrical appliances:
= Radio + Cassette + 4*Fan + TV + Receiver + Microwave oven
+ Vacuum cleaner + Blender + Heater + Boiler + An electric drill + PC +
Battery Charger + Toaster bread + A coffee preparation + telephone
= 150 + 150 + (4*200) + 350 + 200 + 700 + 600 + 150 + 2500 +
1500 + 1000 + 1000 + 240 + 1200 + 1200 + 240
= 11980 Watt
-17-
Chapter 1 Load Estimation
= (360/10)*100 = 3600Watt
All lighting = 9936 watt
c) electrical appliances:
= Radio + Cassette + 4*Fan + TV + Receiver +
Microwave oven + Vacuum cleaner + Blender + Heater + Boiler + An electric
drill + PC + Battery Charger + Toaster bread + A coffee preparation +
5*telephone + 3*Air-Conditioning + Furnace fan + Circular saw
= 150 + 150 + (4*200) + 350 + 200 + 700 + 600 + 150 +
2500 + 1500 + 1000 + 1500 + 240 + 1200 + 1200 +
(5*240) + (3*2250) + 600 + 2500
= 23290Watt
a) Basic load:
= 2*Deep freezer + 2*Electric refrigerator + 2*Washing Machine
= 2*[1200 + 1300 + 1500] = 8000 W
b) Lighting:
Building "480m2" * 33VA = 15840 VA * 0.8 = 12672W
Garden "720 m2" , " each 10m2 have lighting garden of 100 watt "
= (720/10)*100 = 7200Watt
All lighting = 12672W + 7200W = 19872 watt
c) electrical appliances:
-18-
Chapter 1 Load Estimation
-19-
Chapter 1 Load Estimation
5) Design of 5th area " houses with moles" using the two
methods:
Calculation of load - estimation in one flat
= Radio + Cassette + 4* Fan + TV + Receiver + Microwave oven + 12*
Lamp Florist + Vacuum cleaner + Blender +Heater + Boiler + An electric drill +
Electric refrigerator + Washing Machine + PC + Battery Charger + Toaster
bread + A coffee preparation + telephone
= 150 + 150 + (4*200) + 350 + 200 + 700 + (12*60) + 600 + 150 + 2500
+ 1500 + 1000 + 800 + 500 + 1000 + 240 + 1200 + 1200 + 240
= 14000Watt
1. Basic load:
= TV + Small Electric refrigerator + PC +2 Battery
= 350 + 300 + 1000 + (2*240)
= 2130 Watt
2. Lighting:
Building "100 m2" * 15VA = 1.5 KVA
Calculation of load - estimation in one mole = 2130+1500 =3.6
Calculation of load - estimation in one House mole
= (2*3.6) KVA + 40.8 KVA = 48 KVA
-20-
Chapter 1 Load Estimation
Table 1-4:
30m
30m
10m
20 20
20m
m m 40m
Load Estimation of the 3 areas by kilovolts equal about :
20m
4 flats20m
and 2 moles
78 KVA 48 KVA
-21-