A-01.

Smart Datalogger, including GPRS modem


Parameter Technical Specification
Datalogger type Ultra low power, smart and high-end datalogger
Memory, external Micro SD Card, 32GB
Analog input 5 channel, 12-bit ADC
Display LCD 3.5”-inch, TFT, 320x240 pix, LED-backlight, touchscreen,
On/Off switchable
Communication port 2 serial ports : RS-232/485 (ASCII, ModBus, NMEA-183), USB
Data format TCP, FTP, email
Input power DC 12/24V or AC 220V
GSM modem Built-In, 3G, GSM/GPRS/SMS communication, 900/1800MHz band,
open AT command, type-3 SIM card interface
Enclosure Including outdoor enclosure, non-corrosive, weather-proof
Solar power Including solar-panel, charger-controller and deep-cycle back-up
battery with adequate capacity.

A-02. Water Level Sensor


Parameter Technical
Transducer type Ultrasonic or Pressure
Measuring range 0 – 2m or 0 – 5m
Resolution 0.1% FS or 1 mm
Accuracy 0.5 %
Input voltage 12 VDC
Output Signal Analog 4 – 20 mA or serial data
Operating temperature 0 – 80 degC
Housing material Stainless Steel, IP-68, Nema-4X
Installation method Flange

A-03. Rainfall Sensor

Parameter Technical
Sensor type Tipping bucket with measuring bucket
Sampling area 200 cm2
Tick sensor Bounce-free reed contact
Resolution 0.5 mm
Accuracy ±2%
Supply voltage 12 VDC
Installation method Flange or clamp-on pipe

VIII-1
A-04.Visual Sensor

Parameter Technical
Lens 3.6 mm, high-performance color CMOS sensor
Minimum illumination 0.05 lux (w/o IR), 0 lux (with IR)
Connection USB (data and power)
Video format Standard compressed JPEG, 1920x1080
Adjustable parameter 14, including brightness, contrast, saturation, hue, color balace, gamma
API application Get camera, snapshot to file, capture video to file
Housing Outdoor, wheatear proof

A-05. Gate Position Sensor

Parameter Technical
Transducer type Synchro-transmitter / potentiometer / pulse / constant spring loaded
Measuring method Shaft-rotation or wire-messenger
Measuring range 0 – 400 cm
Resolution 1 mm
Accuracy 0.1% FS
Pulse signal 20 ms pulse for every 1 mm increment/decrement
Input voltage 12 VDC or 220 VAC
Output 4 – 20 mA or serial data (RS-485, ModBus)
Enclosure Outdoor, weather proof

A-07. Gate Control Interface / Local Control Unit (LCU)

Parameter Technical
Control interface Electric relay
Control command Open Gate, Close Gate, Stop
Status data Power On, Full Open, Full Close, Overload
Enclosure Outdoor, weather proof
Protection level IP-64, minimum

VIII-2
A-06. Automatic Wheater Station Sensors
Parameter Technical Specification
Transducer type Tipping bucket or Doppler Radar
Rainfall Measuring range 0 to 999.8 mm or 0 to 200 mm/hour
Resolution 0,2 mm
Accuracy ± 4%
Transducer type Capacitance type
Barometric
Pressure

Measuring range 410 to 820 mm Hg


Resolution 0,1 mm Hg
Accuracy ± 0,8 mm Hg
Transducer type PN junction silicon diode
Temperature

Measuring range 0 to +60 degC


Air

Resolution 1 degC
Accuracy ± 0,3 degC

Transducer type Capacitance type


Humidity
Relative

Measuring range 1 to 100% RH


Resolution 1%
Accuracy ± 2%
Transducer type Solid state magnetic or ultrasonic sensor
Wind
Speed

Measuring range 0 to 322 Km/h


Resolution 1 Km/h
Accuracy ± 5%
Transducer type Wind vane with potentiometer
Radiation

Direction

1 – 360o
Wind

Measuring range
Resolution 1o
Accuracy ± 3o
Transducer type Silicon photovoltaic detector or equivalent
Solar

Measuring range 0 to 1800 W/m2


Resolution 1 W/m2
Accuracy ± 5% full-scale
Power source Solar panel with back-up battery, 12/24 VDC
Output data Serial, RJ-11 connector
Enclosure Outdoor type, weather proof, IP-64 minimum
Installation method Flange or clamp-on pipe
A-08. Smart Actuator
Parameter Technical Specification
Actuator type Intelligent Electric Actuator, Modulation Multi-Turn
Capacity / Size Small Medium Large
From – To From – To From – To
Output speed (rpm) 18 72 18 72
Modulation torque (N.m) 70 42 180 72
Max torque (N.m) 133 89 343 142
Motor power (kW) 0.28 0.37 0.8 0.8
Max thrust (K.N) 31.6 21.1 87 34.9
Rated current (A) 3.4 3.9 2.4 9.6
Power Supply 220VAC 50Hz 1-phase
Data Interface RS-232/485, protocol : ModBus/ProfiBus/DeviceNet/FieldBus
Output data/status Gate position, opening, closing, stop, over-torque, over-heat,
fully- open, fully-closed

A-09. Reduction Gear for Actuator


Parameter Technical Specification
Function Actuator speed reduction to meet required modulation torque to
open/close sluice gate
Gate operation speed 5 to 10 cm per-minute
Material Heavy duty steel or brass
Enclosure Adequate outdoor gear-box shall be include for protection

4
A-11. Installation Material & Protection Accessories
Parameter Technical Specification
Equipment installation □ Every electronics equipment shall be installed in an
equipment enclosure
□ Enclosure material shall be metal sheet with powder coating
finishing or hard fiber
□ Equipment installation on a wall will be mounted with a proper
metal bracket
Cable and wire installation □ Every cable and wire installation shall be protected with
PVC conduit or ducting
□ Cable installation on wall will use proper cable clamp
□ Direct buried cable shall be protected with metal conduit
Cable termination □ Every cable termination shall be covered in a terminal box
□ Terminal box material shall be metal sheet with powder coating
finishing or hard fiber
□ Terminal strip shall be corrosion proof
□ Inlet of terminal box shall be covered with cable gland
Protection Accesories □ Installation material must be included lightning arrester device
either for antenna, signal or power input
□ Every electronic or electrical installation must be protected against
vandalism or stealing with appropriate enclosure or
cage/fence.
A-12. Installation, Testing & Programming
Parameter Technical Specification
Installation Procedure Contractor shall submit installation plan to be approved by the user.
Installation plan consist of :
□ Work schedule
□ Procedure
□ Drawings
□ personnel
□ Equipment
□ Safety
Personnel Installation works shall be perform by qualified personnel, as follows
:
□ Device installation : STM or equivalent
□ Cable, termination, networking : STM or equivalent
□ Setting & programming : S1 instrumentation/electronic
□ Application programming : S1 information technology/
computer
Safety Adequate Personal Protective Equipment (PPE) shall be applied to personnel
during installation works.

5
A-13 Solar Power, Solar Panel, 24VDC, 300Wp
Parameter Technical Specification
Cell type Mono or poly crystalline silicon
Power capacity 300 Watt maximum
Enclosure High transparent tempered front glass,
Anodized Aluminum Alloy Frame
Junction box IP-65
A-14 Solar Power, Deep Cycle Battery, 24VDC, 100aH
Parameter Technical Specification
Storage Battery
Battery type Sealed Valve Regulated Lead Acid Gel or Deep-Cycle Battery
Capacity 100Ah 24VDC or 2 X 100Ah 12VDC
Operating temperature - 15 to 45 degC
A-15 Solar Power, Charge Controller/Inverter. 5kVA
Parameter Technical Specification
Controller type Hybrid solar inverter
Rated Voltage 12/24/48 VDC input, 220V AC output
Rated capacity 5 kVA
Include LED/analog status display, main-power charger & inverter,
60A MPPT controller, ATS
A-17 Main Electric Connection, 6.600 watt
Parameter Technical Specification
Installed electric capacity 6.600 watt, 1-phase
Subscription type Pre-paid (using token)
Accessories • Electric power meters including MCB and protective boxes
• Grounding, maximum resistance is 5 Ohms
• Additional electric poles (if needed)
• Down-step transformer to 220V line, if needed

You might also like