Professional Documents
Culture Documents
Project Book Document in Word
Project Book Document in Word
1
INTRODUCTION TO POWER QUALITY
1.1. Introduction
"Power quality" is a term used to describe the most important aspects of the
electricity supply. Both electric utilities and end-users of electrical power are becoming
increasingly concerned with power quality. For the last two decades, the term "power quality"
has become the most commonly used buzzword in the power industry, more so with the rapid
variations, wiring and grounding are all issues related to power quality. Power quality is
becoming a very important area of research since unreliable electrical supply can have large
economic impact. With the trends of increased densities of integrated circuits that results with
faster processor speeds matched with decreasing costs, increasingly sensitive equipment, and
rapid growth in automation use, the chance of interference occurring will undoubtedly rise unless
appropriate preventive measures are taken.
Apart from those trends, end-users are becoming more concerned on issues
related to power quality. This is due to recurring electrical supply disturbances with associated
damages on electrical equipment as a result of deterioration in the quality of power supply. It has
been seen to have a direct implication to economic losses, especially within the industrial and
commercial consumers; thus the need for solutions to power quality problems grows rapidly and
provides new challenges for engineers within the electrical supply industries.
2
Voltage quality concerned with deviations of voltage from the ideal. The ideal
voltage is a single frequency sine wave of constant frequency and constant magnitude.
Current quality is concerned with deviation of current from ideal. The ideal
current is again a single frequency sine wave of constant frequency and constant magnitude.
Thus power quality is concerned with deviations of voltage and/or current from the ideal.
1.3.1. Transients
These are sub cycle disturbances with a very fast voltage change. They typically
have frequencies often to hundreds of kilohertz and sometimes megahertz. The voltage
excursions range from hundreds to thousands of volts. Transients are also called spikes, impulses
and surges. Two categories of transients are described, impulsive transient and oscillatory
transient. Examples of transients include lightning, electro-static discharge; load switching, line/
cable switching, capacitor bank or transformer energizing and Ferro-resonance.
Over voltage: An over voltage is an increase in the rms voltage greater than 110 percent at
power frequency for duration longer than 1 min. Examples include load switching, incorrect tap
settings on transformers, etc.
Under voltage: An under voltage is a decrease in the rms ac voltage to less than 90 percent at
power frequency for duration longer than 1 minute. Examples include load switching, capacitor
3
Sustained interruptions: These come about when the supply voltage stays at zero longer than 1
min. They are often permanent and require human intervention to repair the system restoration.
Examples include system faults, protection maltrip, operator intervention, etc.
Short-duration variations encompass the voltage dips and short interruptions. Each
type of variations can be designated as instantaneous, momentary, or temporary, depending on its
duration these variations can be categorized as:
Interruptions: This occurs when the supply voltage or load current decreases to less than 0.1 pu
for a time not exceeding 1 min. The voltage magnitude is always less than 10 percent of nominal.
Examples include system faults, equipment failures, control malfunctions, etc.
4
Sags (dips): Sag is a decrease to between 0.1 and 0.9 p.u. in rms voltage or current at power
frequency for durations from 0.5 cycle to 1 min. Examples include system faults, energization of
heavy loads, starting of large motors, etc.
Swells: A swell is an increase to between 1.1 and 1.8 p.u. in rms voltage or current at power
frequency for durations from 0.5 cycle to 1 min. Swells are not as common as sags. Sometimes
the term momentary over voltage is used as a synonym for the term swell. Examples include
system faults, switching off heavy loads, energizing a large capacitor bank, etc.
5
Waveform distortion is defined as a steady-state deviation from an ideal sine wave of power
frequency principal characterized by the spectral content of the deviation. Three types of
waveform distortion are listed below:
Harmonics: These are steady-state sinusoidal voltages or currents having frequencies that are
integer multiples of the fundamental frequency. Harmonic distortion originates in the nonlinear
characteristics of devices and loads on the power system. Examples include computers; fax
machines, UPS systems, Variable Frequency Drives (VFDs), etc.
Inter harmonics: These are voltages and currents having frequency components which are not
integer multiples of the fundamental frequency. Examples include static frequency converters,
cyclo-converters, induction motors and arcing devices.
Noise: This is unwanted electrical signals with broadband spectral content lower than 200 kHz
superimposed on system voltage or current in phase conductors, or found on neutral conductors
or signal lines. Examples include power electronics applications, control circuits, solid-state
rectifiers, switching power supplies, etc.
The main causes of poor power quality come from the customers themselves (internal),
generated from one customer that may impact other customers (neighbors), and also from the
utility. Neighbors here include those in separate buildings near the customer and separate
businesses under the same roof such as a small business park. The types and causes of power
quality variations are as follows.
6
Table 1.1 Internal Causes of Power Quality Variations
Type Cause
Short- Sags and swells occurs whenever there is a sudden change in the
duration load current or voltage. Sags result when a load turns on suddenly
voltage (e.g. starting of large motors). Sags do not directly cause damage but
variations initiate problems indirectly. Swells caused by the sudden turning off
of loads can easily damage user equipment.
7
noise indirectly causes damage and loss of product Process control
equipment and telecommunications are sensitive to such noise.
Long Changing currents interact with the system impedance. Loads in the
Short neighbor’s facility must be large and changing enough to affect the
duration voltage feeding the customer’s facility or office. If shared wiring is
voltage present, then even simple devices may cause similar concerns.
variations Overloading may be the cause as well.
8
Table 1.3 Utility Causes of Power Quality Variations
Type Cause
Long- These voltage variations are the result of load switching (e.g. switching
duration on/off a large load, or on/off a capacitor bank). Incorrect tap settings on
voltage transformers can also cause system over voltages. Overloaded circuits
variations can result in under voltages as well.
Power The frequency of the supply voltage is not constant. This frequency
frequency variation is due to unbalance between load and generation. Short circuits
9
variation also contribute to this variation.
CHAPTER 2
DISTRIBUTION STATIC
COMPENSATOR (DSTATCOM)
10
DISTRIBUTION STATIC COMPENSATOR (DSTATCOM)
FACTS employ high speed thyristor for switching in or out transmission line
components such as capacitors, reactors or phase shifting transformers for desirable performance
of systems. The FACTS technology is not a single high power controller, but rather a collection
of controllers, which can be applied individually or in coordination with others to control one or
more of system parameters. it started with the high voltage DC current (HVDC) transmission,
static VAR compensator (SVC) systems were employed later for the reactive power
compensation of power transmission lines . Subsequently, devices like thyristor controlled series
compensator (TCSC), static compensator (STATCOM), static synchronous series compensator
(SSSC), unified power flow controller (UPFC) were proposed and installed under the generic
name of flexible AC transmission systems (FACTS) controllers.
11
2.2. Principle and Operation of Converters
The switching converter forms the heart of the FACTS controllers. Controllable
reactive power can be generated by the DC to AC switching converters which are switched in
synchronism with the line voltage with which the reactive power is exchanged. A switching
power converter consists of an array of solid state switches which connect the input terminals to
the output terminals. It has no internal storage and so the instantaneous input and output power
are equal. Further the input and output terminations are complementary, that is, if the input is
terminated by a voltage source (charged capacitor or battery), output is a current source (which
means a voltage source having an inductive impedance) and vice versa. Thus, the converter can
be voltage sourced (shunted by a capacitor or battery) or current sourced (shunted by an
inductor).
Single line diagram of basic voltage sourced converter scheme for reactive power
generation is shown in fig2.1 for reactive power flow bus voltage V and converter terminal
voltage V0 are in phase.
12
Q = VI = V (V- V0) / X (Eq. 1.2)
The switching circuit is capable of adjusting V0, the output voltage of the converter. For
V0 < V, I lags V and Q drawn from the bus is inductive, while for V 0 >V, I leads V and Q drawn
from the bus is leading. Reactive power drawn can be easily and smoothly varied by adjusting V 0
by changing the on time of the solid state solid state switches. It is to be noted that the
transformer leakage reactance is quite small, which means that a small difference in of voltage
(V- V0) causes the required I and Q flow. Thus the converter acts as the static synchronous
condenser or VAR generator. As the converter draws only reactive power, the real power drawn
from the capacitor is zero. Also at DC (zero frequency) the capacitor doesn’t change and the
capacitor establishes only a voltage level for the converter.
The development of FACTS controllers has followed two different approaches. The first
approach employs reactive impedances or a tap changing transformer with thyristor switches as
the controlled elements, the second approach employs self commutated static converters as
voltage sources. In general these are three categories.
This may be variable impedance, variable source or combination of these. All shunt
controllers inject current into the system at the point of connection. Combined series-series
controllers can be combination of separate series controllers which are controlled in a
coordinated manner. Combined series and shunt controllers either controlled in coordinated
manner as in fig. or a unified power flow controller with series and shunt elements as in fig. for a
unified controller there can be real power exchange between the series and shunt controllers via
dc power link.Tasks of dynamic shunt compensation:
13
Damping of active power oscillations
Improvement of system stability
2 . 4 . 1 . S t at i c V A R C om p e n s a t o r ( S V C )
Shunt-connected Static Var Compensators (SVCs) are used extensively to control the
AC voltage in transmission networks. Power electronic equipment, such as the thyristor
controlled reactor (TCR) and the thyristor switched capacitor (TSC) have gained a significant
market, primarily because of well-proven robustness to supply dynamic reactive power with fast
response time and with low maintenance. With the advent of high power gate turn-off thyristors
and transistor devices (GTO, IGBT, …) a new generation of power electronic equipment,
STATCOM, shows great promise for application in power systems .Installation of a large
number of SVCs and experience gained from recent STATCOM projects throughout the world
motivates us to clarify certain aspects of these devices.
14
Fig 2.2 shows a schematic diagram of a static var compensator. The compensator
normally includes a thyristor controlled reactor (TCR), thyristor-switched capacitors (TSCs) and
harmonic filters. It might also include mechanically switched shunt capacitors (MSCs), and then
the term static var system is used. The harmonic filters (for the TCR-produced harmonics) are
capacitive at fundamental frequency. The TCR is typically larger than the TSC blocks so that
continuous control is realized. Other possibilities are fixed capacitors (FCs), and thyristor
switched reactors (TSRs). Usually a dedicated transformer is used, with the compensator
equipment at medium voltage. The transmission side voltage is controlled, and the Mvar ratings
are referred to the transmission side.
15
Fig.2.3 Static Compensator (STATCOM)
Custom power provides an integrated solution to the present problems that are faced
by the utilities and power distributors. Through this technology the reliability of the power
delivered can be improved in terms of reduced interruptions and reduced voltage variations. The
proper use of this technology will benefit all the industrial, commercial and domestic customers.
The compensating devices used for active filtering, load balancing, power factor
correction and voltage regulation. The active filters, which eliminate harmonic currents, can be
connected in both shunt and series. However, the shunt filters are more popular than the series
16
filters because of their ease of protection. Some of these devices are used as load compensators
and some others are operated to provide balanced, harmonic free voltage to the customers. The
family of compensating devices has the following members
17
Fig. 2.4 Dynamic Voltage Restorer (DVR)
Under normal operating conditions (no sag), the DVR injects only a small voltage to
compensate for the series reactance of the injection transformers and device losses. During sag,
the DVR control system calculates and synthesizes the voltage required to maintain the output
voltage and injects this voltage in synchronous real time.
18
shown in Fig. 2.5. It consists of a dc capacitor, one or more inverter modules, an ac filter, a
transformer to match the inverter output to the line voltage, and a PWM control strategy. In this
DSTATCOM implementation, a voltage-source inverter converts a dc voltage into a three-phase
ac voltage that is synchronized with, and connected to, the ac line through a small tie reactor and
capacitor (ac filter).
2 . 6 DSTATCOM Components
19
Fig. 2.6 An IGBT based Voltage Source Converter
For each arm of the VSC shown in Fig. 2.6 pulses are generated by PWM generator.
It compares a triangular carrier waveform to a reference modulating signal as shown in Fig. 2.7.
The modulating signals can be generated by the PWM generator itself. Three reference signals
are needed to generate the pulses for a three-phase, single or double bridge. The reference signals
used here are three-phase sinusoidal signals. These are generated by controller circuit. The
output of PWM generator is given by:
20
Fig. 2.7 Sinusoidal Pulse Width Modulation (SPWM) technique
21
2.7. Principle of DSTATCOM of Voltage Regulation
22
Fig 2.10 Phasor diagram of the compensated line
As shown in Fig 2.8 voltage E and V mean source voltage and PCC voltage respectively.
Without a voltage compensator, the PCC voltage drop caused by the load current, IL is given by:
ΔV = ( R + j X )( P −VjQ )
S S
L L
So that,
= (R P S L−
V
XSQ L
) (X P
+J
S L+
V
RS Q L
)
=Δ V R+ Δ V X
(Eq. 2.6)
23
V, relative to the supply voltage E, are the functions of magnitude and phase of load current, i.e.
voltage drop depends on the both the real and reactive power of the load. The component ∆V can
be written as,
ΔV=ISRS+ j ISXS (Eq. 2.7)
Fig. 2.10 shows the vector diagram with voltage compensation. By adding a
compensator in parallel with the load, it is possible to make |E|=|V| by controlling the current of
the compensator.
I =I +I
S L R (Eq. 2.8)
Where, IR is compensator current.
24
of faults and if the load voltage leads the system voltage, then the real power from the capacitor
or the DC source will be supplied to the AC system to regulate the system voltage.
Hence, the exchange of real power and reactive power of the voltage source
converter with AC system is the major required phenomenon for the regulation in the
transmission as well as in the distribution system.
CHAPTER 3
25
DECOUPLED CURRENT CONTROL ALGORITHM
3.1 Introduction
26
Calculation of compensating signals
Generation of firing angles of switching devices
Generation of proper PWM firing is the most important part of DSTATCOM control
and has a great impact on the compensation objectives, transient as well as steady state
performance. Since a DSTATCOM shares many concepts to that of a STATCOM at
transmission level, a few control algorithms have been directly implemented to a DSTATCOM,
incorporating Pulse Width Modulation (PWM) switching.
(Eq. 3.1)
27
Assuming a balanced three-phase system (xo= 0), a three-phase vector representation
transforms to dq0 vector representation (zero-axis component is 0) through the transformation
matrix T, defined as:
(Eq. 3.2)
Where,
(Eq. 3.3)
(Eq. 3.4 )
(Eq. 3.5)
28
Fig. 3.1 Park’s transformation
The inverse transformation matrix (from dq_to_abc) is defined as,
(Eq. 3.5)
(Eq. 3.6)
29
the voltage is always zero, the real (P) and the reactive power (Q) injected into the system by the
DSTATCOM can be expressed under the d-q reference frame as
From the above expressions, I d and Iq completely describe the instantaneous value
of real and reactive powers produced by the DSTATCOM when the system voltage remains
constant. Therefore the instantaneous three phase current measured is transformed by
abc_to_dqo transformation.
30
Fig. 3.2 Block Diagram of Decoupled Theory based control of DSTATCOM
The decoupled d-axis component Id and q axis component Iq are regulated by two separate PI
regulators. The instantaneous Id reference and the instantaneous Iq reference are obtained by the
control of the dc voltage and the ac terminal voltage measured. Thus, instantaneous current
tracking control is achieved using four PI regulators.
A Phase Locked Loop (PLL) is used to synchronize the control loop to the ac
supply so as to operate in the abc_to_dqo reference frame.
31
CHAPTER 4
32
Algorithm development
Data acquisition
Modeling, simulation, and prototyping
Data analysis, exploration, and visualization
Scientific and engineering graphics
MATLAB is an interactive system whose basic data element is an array that does not
require dimensioning. This allows solving many technical computing problems, especially those
with matrix and vector formulations, in a fraction of the time it would take to write a program in
a scalar non-interactive language such as C or FORTRAN.
The Three-Phase Source block implements a balanced three-phase voltage source with
internal R-L impedance. The three voltage sources are connected in Y with a neutral connection
that can be internally ground.
33
The Three-Phase V-I Measurement block is used to measure three-phase voltages
and currents in a circuit. When connected in series with three-phase elements, it returns the three
phase-to-ground or phase-to-phase voltages and the three line currents
4.2.3. Scope
Display signals generated during a simulation. The Scope block displays its input
with respect to simulation time. The Scope block can have multiple axes (one per port); all axes
have a common time range with independent y-axes. The Scope allows you to adjust the amount
of time and the range of input values displayed. You can move and resize the Scope window and
you can modify the Scope's parameter values during the simulation
The Three-Phase Series RLC Load block implements a three-phase balanced load
as a series combination of RLC elements. At the specified frequency, the load exhibits constant
impedance. The active and reactive powers absorbed by the load are proportional to the square of
the applied voltage.
34
Fig 4.5 Three-Phase Breaker block
The Gain block multiplies the input by a constant value (gain). The input and the
gain can each be a scalar, vector, or matrix.
35
and MOSFET). The Universal Bridge block is the basic block for building two-level voltage-
sourced converters (VSC).
The PWM Generator block generates pulses for carrier-based pulse width
modulation (PWM) converters using two-level topology. The block can be used to fire the
forced-commutated devices (FETs, GTOs, or IGBTs) of single-phase, two-phase, three-phase,
two-level bridges or a combination of two three-phase bridges.
The abc_to_dq0 Transformation block computes the direct axis, quadratic axis, and
zero sequence quantities in a two-axis rotating reference frame for a three-phase sinusoidal
signal.
36
The dq0_to_abc Transformation block performs the reverse of the so-called Park
transformation, which is commonly used in three-phase electric machine models. It transforms
three quantities (direct axis, quadratic axis, and zero-sequence components) expressed in a two-
axis reference frame back to phase quantities.
4.2.11. Terminator
The Terminator block can be used to cap blocks whose output ports are not connected
to other blocks. If you run a simulation with blocks having unconnected output ports, Simulink
issues warning messages. Using Terminator blocks to cap those blocks avoids warning messages.
4.2.12. Constant
The Constant block generates a real or complex constant value. The block generates
scalar (1x1 2-D array), vector (1-D array), or matrix (2-D array) output, depending on the
dimensionality of the Constant value parameter and the setting of the Interpret vector parameters
as 1-D parameter
37
heavy inductive and capacitive load is connected to the system to study the performance of the
DSTATCOM
38
Fig 4.14 Test system with DSTATCOM
V LL = 0.612MaVd
Where,
V d = Input DC voltage
40
5.1.2 DSATCOM circuit:
41
Fig 4.16 MATLAB based model of DSTATCOM circuit
42
Fig 4.17 MATLAB based model of Control Circuit
Rms value of system voltage is compared with nominal voltage (i.e. 1 p.u.)
to produce the reference d-axis component of current. DC voltage of capacitor is compared with
reference I p.u. value to produce quadrature axis component of DSTATCOM current. Actual
values of dq components of current are compared with these reference values to produce
reference signals to PWM generator and are transformed into inverse dq transformation (i.e.
dq0_to_abc).
Supply Voltage 25 KV
43
Fundamental Frequency 60 Hz
DC capacitance 10000 µF
44
CHAPTER 5
45
5.1. Simulation Results
5.1.1. Voltage Sag
Voltage sag is created by applying heavy inductive load (i.e. by closing the circuit breaker
BIL) from .2 seconds to .3 seconds and response is shown in Fig 5.1. At the first cycle breaker
BDL is closed (i.e. DSTATCOM is included in the circuit) and response is shown in Fig. 5.2
Fig 5.1 Load voltage with inductive load with uncompensated line
46
Case 2: With Compensation
Fig 5.2 Load voltage with inductive load with compensated line
47
Voltage swell is created by applying heavy capacitive load (i.e. by closing circuit breaker
BCL) from.2seconds to .3 seconds and response is shown in Fig. 5.3. At the first cycle breaker
BDL is closed (i.e. DSTATCOM is included in the circuit) and response is shown in Fig 5.4
Fig 6.4 Load voltage with capacitive load with uncompensated line
48
Case 2: With Compensation
Fig 5.4 Load voltage with capacitive load with uncompensated line
5.2. CONCLUSIONS
49
Different types of power quality problems and their causes are explained. A new
generation of power electronic based equipment called Distribution Static Compensator
(DSTATCOM) is introduced and its operating principle is explained.
50
REFERENCES
1. Deepika Masand, Shailendra Jain and Gayatri Agnihotri and Maulana Azad, “Control
Algorithms for Distribution Static Compensator,” IEEE ISIE 2006, July 9-12, 2006.
51
52