Professional Documents
Culture Documents
7051 TransmissionLineParameter AS 20220317 Web2
7051 TransmissionLineParameter AS 20220317 Web2
Presented at the
25th Annual Georgia Tech Fault and Disturbance Analysis Conference
Atlanta, Georgia
May 2–3, 2022
Abstract—This paper describes a method to estimate provides better Z0 estimates for transposed and untransposed
transmission line parameters in traveling-wave (TW) relays. The lines.
proposed method uses time-synchronized voltage and current Faults that launch small TWs and certain evolving faults
measurements from both ends of a line and TW fault location
(TWFL) data available in the event report. Positive-sequence line impact the dependability of TW-based and incremental-
impedance (Z1) is estimated using pre-fault positive-sequence quantity-based protection elements. For these scenarios,
quantities. Incremental zero-sequence quantities and TWFL data phasor-based protection elements provide backup protection.
are used for zero-sequence line impedance (Z0) estimation. The use Phasor-based protection elements require accurate line
of incremental quantities provides better Z0 estimates for both parameters. The estimated line parameters can be used to check
transposed and untransposed lines. Line parameter estimates the accuracy of line parameter settings in the relay. When
from both simulation and field events demonstrate the robustness
of the proposed method. estimated line parameters are used to correct line impedance
settings in the TW relay, it increases dependability for phasor-
I. INTRODUCTION based protection elements. For a non-TW relay (used as backup
for a TW relay), the accurate line parameters improve both
Transmission line parameters (i.e., positive-sequence and
security and dependability for protection elements and the
zero-sequence line impedances) are used in power system
impedance-based fault locator.
studies and protective relaying applications, such as power flow
This paper is organized into sections. Section II provides a
calculations, stability analysis, short circuit analysis, relay
short summary of various line parameter calculations methods
settings, impedance-based fault location, and relay testing [1].
described in the literature. A brief overview of TWFL and
The positive-sequence impedance (Z1) can be calculated using
incremental quantities is mentioned in Sections III and IV,
the tower configuration and conductor properties. Zero-
respectively. Section V describes the proposed line parameter
sequence impedance (Z0) is usually found to be inaccurate [2],
estimation method in detail. Simulation and field results that
and typically, Z0 has higher errors than Z1. Z0 depends on
demonstrate the accuracy of the proposed method are presented
ground resistivity, which varies with temperature, moisture,
in Sections VI and VII. Finally, concluding remarks are
mineral content, and compactness [3]. Inaccurate Z1 and Z0
presented in Section VIII.
impedances can result in overreaching or underreaching issues
in distance elements and can lead to misoperation [4].
II. LINE PARAMETER CALCULATION METHODS
Similarly, line impedance errors can impact fault location
accuracy when impedance-based fault location methods are Line parameter estimation methods can be broadly classified
used. into two groups.
Reference [2] describes various methods to calculate • Offline methods
alternating current (ac) transmission line parameters. These − Line constants tools
methods use offline and online measurements. Offline methods − Signal injection methods
require the line to be taken out of service and inject signals − Event analysis using known fault location
using test sets. Online methods use synchrophasor data to • Online methods
estimate line parameters. Most of these methods require − Synchrophasor measurements
dedicated equipment, like test sets and phasor measurement − Single-pole open (SPO) method
units; hence, these methods are costly, labor-intensive, and
time-consuming. A. Line Constants Tools
This paper describes methods to estimate transmission line Line constants software tools are widely used in the industry
parameters using traveling-wave fault location (TWFL) data, to calculate line parameters. To produce line parameter values,
time-synchronized voltage, and current measurements from these tools require transmission line data (e.g., tower structure,
both ends of a line that are available in a traveling-wave (TW) distance between the phase and ground wires, line sag, ground
relay event report. Using pre-fault positive-sequence quantities, resistivity, and detailed information of the conductors). Ground
Z1 is estimated by solving the PI equivalent line model. A novel resistivity and sag may change based on the ambient conditions,
incremental zero-sequence quantities-based method is used to which could cause a variation in the line parameters estimated
estimate Z0. Incremental zero-sequence quantities are by these tools. These tools can also model nonhomogenous
calculated by subtracting zero-sequence quantities from the lines by splitting the transmission line into multiple sections.
pre-fault and faulted network. The use of incremental quantities
2
line breaker while keeping another end breaker open. Based on the negative pre-fault voltage at the fault location (–VF) is
this test, propagation velocity can be calculated using the line included. The pure-fault network currents and voltages are zero
length and time duration between closing of the breaker and the before the fault. Any currents and voltages in the pure-fault
reflected wave. Relay manufacturers recommend using a line network depend only on the network parameters and pre-fault
energization test to calculate the propagation velocity [9]. conditions. The pre-fault network provides the initial condition
DETWFL accuracy depends on the line length setting and for the pure-fault Thevenin source.
propagation velocity setting. DETWFL accuracy also depends Incremental quantities (i.e., superimposed quantities)
on the time-stamping accuracy. Even 1 microsecond of error in represent signals that appear in the pure-fault network [11] [12]
time accuracy can cause 300 meters of fault location error. [13]. These quantities are typically represented with the delta
Modern relays have inherent time-stamping accuracy better prefix (Δ) to indicate the change, with respect to the pre-fault
than 0.2 microseconds, which results in 60 meters of fault network signals. Relays measure both the pre-fault and faulted
location error [8]. Line sag can cause errors in line length network signals directly. The incremental voltage and current
estimation, and as a result, affects the propagation velocity quantities are expressed in (2).
estimation. Nevertheless, TWFL methods provide accuracies as
low as 300 meters or close to one tower span in real-world fault
events [10].
The pure-fault network can be solved either in the time-
IV. INCREMENTAL QUANTITIES domain or in the frequency domain. In the time-domain, the
To analyze faults on a transmission line in a complex pure-fault network looks like a lumped parameter resistance,
network, the overall network can be simplified into a two- inductance, and capacitance (RLC) network in the transient
source power system connected by the transmission line of state. The relationship between incremental voltage and current
interest using Thevenin’s theorem. Further, the principle of quantities are governed by differential equations. Protective
superposition can be used to represent any faulted network as a elements developed by solving incremental quantities in the
summation of two separate networks, a pre-fault network, and time-domain have considerable improvement in speed. In the
a pure-fault network. Fig. 2 shows these three networks for a frequency domain, a pure-fault network is solved by using
fault on the line with fault resistance, RF. phasors. Algebraic equations govern the relationship between
incremental voltage and current quantities. When phasors are
used, there is an inherit delay associated with the phasor filter
required for accurate phasor estimation. This delay impacts the
speed at which phasor-based incremental elements can operate.
In a power network with balanced voltage sources,
transposed lines, and balanced loads, only positive-sequence
current and voltage exist in the pre-fault network. Negative-
sequence and zero-sequence quantities are zero. For such a
network, the calculated negative-sequence and zero-sequence
quantities in the faulted network are incremental negative-
sequence and zero-sequence quantities in the pure-fault
network [13]. Positive-sequence incremental quantities are the
exception and can be calculated by subtracting positive-
sequence quantities between faulted and pre-fault networks.
In practice, transmission lines are often untransposed due to
several factors, including the cost [1]. Untransposed lines create
unbalance in the pre-fault network and result in the generation
of negative-sequence and zero-sequence voltages and currents.
These sequence quantities impact performance of many power
system components, including protective relaying. With non-
zero negative-sequence and zero-sequence quantities in the pre-
fault network, incremental negative-sequence and zero-
sequence quantities in the pure-fault network are no longer the
negative-sequence and zero-sequence quantities in the faulted
network. In the next section, we discuss the impact of these
Fig. 2. Faulted network as the superposition of pre-fault network and pure- quantities in the pre-fault network for line parameter
fault network [11]. estimation.
The pre-fault network drives the load current through the
network and establishes the voltage, VF, at the fault location. In
the pure-fault network, all pre-fault network voltage sources are
short-circuited, and the Thevenin source voltage that is equal to
4
The zero-sequence line impedance is only estimated if the By using incremental zero-sequence phasors in the pure-
fault type is identified as a line-to-ground fault (LG) or double fault network, zero-sequence line impedances (Z0) are
line-to-ground fault (LLG) in the event report. For faults estimated for FltWin data window. Maximum and minimum
involving ground, convert the TWFL data in the event report to calculated values are discarded, and an average of the
a per-unit value (mTW). Refer to (8). remaining estimates is the Z0 estimate for the given line. Refer
to (12).
6
location is known, Z1 and Z0 are estimated using Equations (13) B. Untransposed Line Model—Faulted Network Method
and (14) by solving the faulted negative-sequence and zero- For the second test scenario, the transmission line was
sequence network. Fig. 6 and Fig. 7 show the estimated Z1 and modeled as an untransposed line. In reality, most transmission
Z0 for 81 fault cases, as described previously. In both figures, lines are often untransposed due to several factors, including
the triangle, circle, and diamond represent line parameter the cost [2]. Untransposed lines lead to unbalance in three
estimates for faults at 30, 50, and 80 kilometers, respectively. phases and result in the generation of negative-sequence and
With this method, the inaccuracy of estimated values for faults zero-sequence voltages and currents. With untransposed lines,
at 30 kilometers is slightly higher that 5 percent. sequence networks are no longer independent. Positive-
sequence current flowing in an unbalanced system produces
voltage drops in all three sequence networks [15]. Similarly,
negative-sequence and zero-sequence current also produces
voltage drops in all three sequence networks. If a sequence
network is used by ignoring the voltage drops created by two
remaining sequence networks, it impacts accuracy.
Assuming the fault location is known, Z1 and Z0 are
estimated using Equations (13) and (14) by using the faulted
data window. Fig. 8 and Fig. 9 show the estimated values Z1
and Z0. The inaccuracy of estimated values is high. These two
figures demonstrate that we cannot use Equations (13) and (14)
to estimate line parameters for untransposed lines.
Fig. 6. Z1 estimates for a transposed line model using the faulted network
method.
Fig. 7. Z0 estimates for a transposed line model using the faulted network Fig. 9. Z0 estimates for an untransposed line model using the faulted
method. network method.
8
Fig. 10. Z1 estimates for an untransposed line model using the proposed
method.
Fig. 12. Z0 estimates for an untransposed line model using the proposed
method with +300 meters TWFL inaccuracy.
Fig. 11. Z0 estimates for an untransposed line model using the proposed
method.
9
Fig. 15 shows the voltage and current signals from both line
terminals for an internal CG fault for Event 1. The relays at both
terminals detect and isolate the fault by opening Breaker
Pole C. The TW relay estimates the fault location at
60.995 miles from the local terminal. The fault location of
61.501 miles is confirmed by the field. Fig. 16 shows the
sequence quantities and binary signals required to run the
proposed line parameter estimates. The proposed method
estimates Z1 as 22.86 ∠80.75° ohms secondary and Z0 as 48.81
∠73.78° ohms secondary, respectively. When compared with
line impedance magnitude settings in the relay, the errors are
2.82 percent for Z1 and 4.75 percent for Z0.
Except for Events 2A and 2B, the estimated Z1 values are
within 5-percent magnitude error and 1-degree phase angle
error of the relay settings. For these two events, the load angles
δ (∠V1S – ∠V1R) in PreFltWin are 1 degree and 1.4 degrees,
respectively. When PI equivalent model of transmission line is
used, Z1 estimates have high error for load angle less than
Fig. 13. Z0 estimates for an untransposed line model using the proposed 5 degrees [4]. For small load angle, small CT and VT errors are
method with –300 meters TWFL inaccuracy.
greatly amplified, leading to inaccurate Z1 estimates.
Fig. 14 shows the impact of TWFL inaccuracy on Z0 Event 3 has the highest magnitude and phase angle error for
estimates for a fault at 30 kilometers. The TWFL error has Z0 estimates. The error can be the result of various power
minimum impact on the Z0 phase angle. However, Z0 system phenomena, as described in Section VI. Event 4 is an
magnitude error increases linearly with an error in TWFL data. AB fault, and as a result, only Z1 is estimated for this event.
Fig. 14. Z0 magnitude and phase angle error due to inaccuracy in TWFL.
TABLE II
LINE PARAMETERS FOR A 400 KILOVOLT OVERHEAD LINE
For the given line, RLC matrices at 60 Hz are listed in (15). The two-source power system model used for real-time
simulation to test the proposed line parameter estimation
algorithm is shown in Fig. 17.