Soil Test Report 101 (Moghalpura)
Soil Test Report 101 (Moghalpura)
Soil Test Report 101 (Moghalpura)
Month : November-2022
Contents
Introduction 3
Scope of Work 3
Field Investigation 4
Water Table 5
Soil Profile 6
Recommendations 10
Precautions 10
2
NOBTIs Engineering Firm
Soil Test Report
Introduction:
Mr. Asim Alauddin has contracted to carry out preliminary soil investigation for
the proposed Residential Building at Moghalpura, Hyd. In order to design and
construct the foundation, preliminary soil investigation programme at the field
is carried out. The test results of the field have been interpreted/analyzed for
giving recommendation on type of foundation, depth of foundation and
allowable bearing pressure to be adapted for construction of foundations. This
report does not necessarily cover the structural design aspect, supervision and
quality of construction at the site. The method and procedure adopted in the soil
investigation is to provide the client a general idea in the shortest duration
possible and is in no way to replace the detailed investigation as per standards.
Scope of work
The scope of the soil investigation work as given by the client comprises of the
following:
3
NOBTIs Engineering Firm
Soil Test Report
Field investigation
SPT test is conducted at 9 ft below the existing Ground level. Initially bore hole
was drilled at specified location of the site with hand operated and Auger
technique up to refused strata as per the guidelines given in IS 1892-1981.
Calibrated standard penetration test was conducted in the bore hole as per the
guideline given in IS:2131-1981 in order to know the relative stiffness of the
sub-soil strata.
4
NOBTIs Engineering Firm
Soil Test Report
Water Table
Water table was not found in the bore hole upto a depth of 9 ft below the
existing ground level during the field investigation which was carried out in the
month of November 2022, and however partial effect of water table has been
incorporated in the calculation of bearing capacity.
5
NOBTIs Engineering Firm
Soil Test Report
Soil Profile
The sub soil strata in the bore holes generally comprises of debris up to a depth
4 ft from the existing ground level followed by loose silty soil for a depth of
3.5ft and then medium silty soil for remaining depth.
Ground Level
Debris
4 ft.
Open isolated footings are permitted unless the foundations are getting
Bore Hole Soil Profile
overlapped. Width/length of the foundation should not be less than 1.5 m.
6
NOBTIs Engineering Firm
Soil Test Report
7
NOBTIs Engineering Firm
Soil Test Report
Corrected N 5 10 15 20 25 30 35 40 45 50
Ø 28.5 30 32 33 35 36 37.5 39 40 43
There angle of friction is Ø = 37 degrees.
Interpolating the bearing capacity factors from the table of IS:6403 for Ø = 37o.
Considering Sq, dq and iq (shape, depth and inclination factors) from the code
and Water table factor as 0.79 (Partial Effect of Water Table).
8
NOBTIs Engineering Firm
Soil Test Report
9
NOBTIs Engineering Firm
Soil Test Report
Recommendations
Precautions
a) Silty soil with pockets of weathered rock, if met in any of the foundation
pit shall be completely removed and filled with PCC and compact well
before foundations are laid.
b) Any variation in the soil strata other than mentioned in this report is
found at any other footing locations; the same may be brought to the
notice of the undersigned and suitably be examined.
Md Masihuddin Siddiqui,
B.E, M.E, LL.B
GHMC Lic# 93 (Structural Engineer)