80

8A/24 Volts Power Supply


New Product Bulletin No. 037

 High efficiency (reduces power bills and carbon


footprint)

 High reliability

 Cost effective switch mode technology

 Intelligent battery charging monitoring

 Deep discharge protection

 Power Factor corrected

 Remote fault monitoring

 Full rated load plus additional current for battery


charging

 Meets the requirement of the latest EN54 pt4.

The Protec 9800EN 8A/ 24 volts switch mode power supply has been designed for
Description Parameters
use in building fire systems and access control applications. This power supply is
fully compliant and approved to EN54-4:1997, A1:2002 & A2:2006. Rated Mains Input Voltage 93-264 Vac
Rated Frequency 45Hz-65Hz
The 9800EN range includes intelligent battery charging, mains and battery 3.15A 250Vac HBC time delay 20mm x 5mm
Mains Input Fuse FS1
monitoring with independent volt-free output.
Output Voltage 19.0Vdc-29Vdc
The output features electronic short circuit protection under both mains and Output Ripple Voltage 100mV maximum ( peak to peak ) at full output load
standby battery operation.
Output Current 8A Maximum
Battery Fuse FS2 10A Quick Blow 20mm x 5mm glass
Maximum battery life is assured through continuous active battery monitoring and
the use of an intelligent charger with temperature compensated final float phase 2 x 12V (24Ah, 40Ah, and 66Ah) Sealed Lead Acid
Battery capacity/Type connected in series. Only use batteries recommended
depending upon battery condition.
by Protec.
Deep Discharge Protection Battery disconnect at 19V nominal
Deep discharge protection prevents premature battery failure when operating from
Battery Charge current 3.5A ( reduced to 600mA when the output load
standby for extended periods. The 9800EN range provides a volt free solid state exceeds approximately 4.5A
relay output signal, for loss of mains, battery fault, charger fault or loss of output.
Battery Charge Voltage 27.3V at 20 degrees C. Temperature compensated at –
40mV / deg C using a remote temperature probe.
The 9800EN power supply is compatible with the Protec range of Fire Alarm
Maximum Battery Resistance 0.65Ω ( battery internal resistance + lead and
control panels and EVC40 disabled refuge/fire telephone system.
( Ri ) connection resistances
Status Led Indications )
Power On, General Faults
The power supply is capable of charging a battery up to 2x12V66AH capacity.
For further details, please refer to installation, commissioning and maintenance Fault Relay Contact Maximum rating of 1A at 24V DC ( resistive load )
manual N93-592-90 issue1

Description Order Code


Model Dimensions (mm) Humidity IP 8A, 24 Volts Power supply complete with 24AH batteries 9800EN-24AH
9800EN-24AH 440(L) x385(W) x 220 (D) -10°C to 50°C at 95%RH IP30 8A, 24 Volts Power supply complete with 40AH batteries 9800EN-40AH
9800EN-40AH 440(L) x385(W) x 220 (D) -10°C to 50°C at 95%RH IP30 8A, 24 Volts Power supply complete with 66AH batteries 9800EN-66AH
9800EN-66AH 532(L) x980(W) x 200(D) -10°C to 50°C at 95%RH IP30

Protec House Churchill Way, Nelson, Lancashire, BB9 6RT


Tel: 01282 717171 Fax: 01282 717273 Email: sales@protec.co.uk Web: www.protec.co.uk