Technical Data Sheet Indoor Surge Arrester: 4kV, 10KA Class 2

General: 
Model  MCPA2‐04‐IND 
Arrester housing  Polymeric 
Application  Indoor 
Applicable standard  IEC 60099‐4/ IS 3070 Part 3 
Nominal discharge current  10kA 
Line discharge class  2 
High current impulse 4/10µs  100kA 
Energy capability  4.5 kJ/kV at Ur according to IEC 60099‐4 

Surge arrester characteristics: 
Rated voltage  Ur: 4.0  kV 
Continuous operating voltage  Uc: 3.2  kV 
TOV capability  4.56  kV for 1s     
      4.12  kV for 10 s             
      3.88  kV for 100 s             
Max. app. cant. load  250  Nm 
Impulse voltage 1.2/50µs  75  kV 
Power frequency voltage‐dry  30  kV 
Creepage distance  130  mm 
Height  147  mm 
 
Maximum residual voltages 
Lightning current impulse     Steep lightning current     Switching current impulse    
8/20µs              impulse 1/20µs     30/60µs          
5kA  10kA  20kA  10kA  125A  500A     
12.5kV  13.5kV  15.0kV     14.0kV        9.7kV    10.4kV     
 
 
Power frequency voltage versus Time 
 
 

Text A: MCPA2‐04‐IND
           Text B: Uc 3.2 kV 
           Text C: Ur 4.0 kV 
           Text D: Year 
                                                                                                                                                      Text E: Batch

The information provided here is correct to best of our knowledge and reliable. User, however, should independently evaluate the suitability of the product for
desired application. Product development is a continuous process, therefore specification provided here is subject to change.