DC Ground Fault

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

Ground Fault Detection and

Isolation on Ungrounded DC
Systems

Jose´ A. Marrero

Southern Company
DC SME
General Comments

The interaction of you detection


system/equipment and your DC system must be
understood along with their respective limitation.

Also the limitations of your detection method


must be understood. The figure below shows us a
typical system and some of the interaction during
a ground fault.
Concerns
 Must let all know what to expect, cooperation
from Maintenance and Operation Management
 Preparation and planning
– Early/quick problem detection, isolation and
resolution
 If multiple grounds are present or suspected
– Caution is needed
 4-8 mili-Amps and 30 - 46V is all that is needed for certain relays and
solenoids to actuate/drop out.

 In other words High Visibility


– Must remain focused
Basic Problem
 Identify and locate low level DC ground
fault current
– Low-to-high impedance ground faults in the
presence of larger DC load current
 Identify them in a complex multi-feeder
source(s) and loads
 Perform quickly and efficiently
– Without interrupting the service of critical
control and plant systems
Quasi Typical DC System
Simpler Example
Types of DC Ground Faults
 Continuous or Transient
Types of DC Ground Faults(GFs)

 Steady
– comes in and stay in at the same level
 (can ⇑ or ⇓)

 Intermittent
– Comes in & out, increasing or decreasing
levels, but with ‘Long’ durations(>>15min.)
 Transients
– Pluses
– Spikes
Types of DC Ground Faults(GFs)

 Their periods can be either of a fixed or


‘random’ nature, this can pertain to the either
on/off portion equally
 All GFs are of large enough amplitude to be
detectable
 There is no such thing as zero crossing
Caution
Multiple GFs

 Multiple GFs of opposing polarities, can


cause components/system failure without
indication

 Reliability of your system may have been


compromised
General Comments
Detection Scheme
THERE CAN BE ONLY ONE
Location of Detection Scheme

 DC System monitoring
– Local and Remote Point(s)
 Charger(s)
 Inverter(s)
 UPS
 Load(s) Control System like Mark V & VI
 Plant DAS
 Battery Monitors
Detection Scheme
 Voltage Divider System
– Numerous variations to this scheme
 Resistor can be replaced with relay coil to annunciate

 Voltmeter can be replaced with amp meter to detect

magnitude of the ground fault


 Symmetrical & Asymmetrical forms

 System utilizes voltage imbalance measurements


– Only indicate that a fault condition exists
– Are unable to determine the source, location or
number and magnitude of fault(s)
Some Commercial Avaliable
Detection Units
A Common Detection Scheme
 Voltage Division
– There are many variations

Fault

+ 1

Load
2
- PN
What Information Is Needed?
 What type of indication do you have?
– Ex. Lighting, amp meter, alarm circuit
 Always check light bulb and fuses prior to

continuing
 What is the alarm trigger point?
 What are the limitations and what
information can be obtained?
– What side is it on?
– What is the magnitude?
– Is it a constant or transient ground fault?
What Information Is Needed?
 Important parameters to know on your system
(especially on multi-feeder distribution system)

– DC voltages between battery polarities


– DC voltages between the polarities (pos. &
neg.) with respect to site ground
– DC ground fault from both polarities(pos. &
neg.) with respect to site ground
– AC voltage between polarities with respect to
site ground (phantom ground)
Methodologies
 Voltage measurements
 Selective tripping, isolations, circuit breaker
 AC signal injection
 DC signal injection
 DC Ground Loop Interrupt
– (Resistive)/Magnetic coupling
– Use of differential current
 Event analysis
Capabilities/Limitations
 Voltage Measurements
– Provides detection and limited (inaccurate)
information on location
– Considerable amount of time required to locate
the fault
– Expect considerable interference from system
– With multiples grounds on the system, reading
can be very misleading
Capabilities/Limitations
 Selective tripping, isolation of circuit
breaker, fuses and other interrupting devices
– Must be methodical
– Considerable amounts of time required to locate
fault
– Interruption of critical equipment and service
– Interruption of circuits
– May inadvertently trip circuits due to transients
caused by opening and closing breakers.
Capabilities/Limitations
 AC signal injection
– Will locate fault, minimizes circuit and service
interruption
– High system knowledge is required
– Ineffective and should not be used on system with
large stray capacitance or High AC Ripple Content
– Ineffective in multi-feeder distribution systems
having large stray capacitance and strong
electromagnetic field interference between the
distribution line and ground
Capabilities/Limitations
 AC signal injection
– Requires a large AC signal to overcome low
impedance to ground
– Sensitivity varies in proportion to signal
strength
– Use of large amplitude AC signals may trip or
damage sensitive devices/circuits
Capabilities/Limitations
 DC signal injection
– Will locate fault, minimizes circuit and service
interruption
– High system knowledge is required
– Use of large amplitude DC signals may trip or
damage sensitive devices/circuits
Capabilities/Limitations
 DC Ground Loop Interrupt (Resistive)
– Can use magnetic coupling & sensors
 allowing you to take reading through conduits and in wire
bundles
– Locates fault with minimal circuit/service interruptions
– Usable on energized/de-energized circuits
 (w/power supply)

– Uses differential current (fault current ) to locate


ground
– Sensitivity of around 3 mA (greater sensitivity
depending on unit and experience)
– Accommodates large range of cable and circuits
Injection Point & Length:
Does it Matter?

 Power Bus
 Site Ground
 Continuous
 Pulsed
Event Analysis
 This involves the use of multiple event
recorders (with voltage & current inputs)
placed/positioned around your distribution
network in a methodical manner then
waiting for events
 Time & Date stamp all units used(to the
same ref)
 Give or request equipment start/stop logs to
operators
Event Analysis
 Look for events occurring at the ~same
time(slope & amplitude)
 Particular circuit in question can be isolated
by the use of an external power supply &
opening the associated breaker to the
suspected circuit
 Monitor upstream points for transient
reoccurrence(at least one period)
Caution

 Injection of any large amplitude signals in a


distribution system has been known to
damage sensitive digital equipment and/or
inadvertently operate or prevent from
operating critical loads
Note
 Multiple ground faults
– Largest will only be detected first
– Must be isolated to detect others
– Ground faults can be of opposing polarities

 Re-evaluation must occur upon removal of each


GF

 Magnitude of remaining GF can increase


significantly
Predictive Maintenance
 Measuring and trending of the following
parameter should be performed periodically
– DC overall voltage
– DC polarity voltages with respect to ground
– Monitor ground faults on your different DC
buses
– AC voltages between polarities and ground
 Train maintenance personnel on DC ground
fault troubleshooting & isolation
How We Help Ourselves
How We Help Ourselves
Ground Faults in Batteries
 Concerns about ground faults in batteries.
 Causes of ground faults in batteries.
 Results of Ground Faults.
 Methods to Detect Possible Ground Faults
in VRLA.
Voltage to Ground –
UPS Battery Systems
 Due to the elimination of the input
transformer in most large UPS systems
there is a very large and dangerous voltage
to ground.
 On a 240 Cell battery system the voltage
ranges from 200 to 500 V depending on the
point along the battery the measurement is
taken.
Voltage to Ground Waveform
Causes of Ground Faults in
Batteries
 Dirt on the surface of the container.
 Hole in the container.
 Jar to cover seal failure.
 Post seal leak.
Results of Ignored Ground
Faults
FIRES!
Useful Tool
Insulation resistance tester.
2gohm @ 1000VDC

You might also like