Professional Documents
Culture Documents
GL IV - Chapter4
GL IV - Chapter4
GL IV - Chapter4
Section 2
Design Loads
Table 2.1 Wind pressure shape coefficients CS A = wind projected area of all exposed surfaces in
either upright or heeled condition [m2]
Shape CS
The exposed surfaces are to be taken in either the up-
Spherical shapes 0,4 right or heeled condition.
Cylindrical shapes (all sizes) 0,5 2.4 Recommendations
Large flat surfaces (hull, deckhouses, smooth – For units with columns, the projected areas of all
1,0
deck areas)
columns are to be included without shielding.
Drilling derrick 1,25
– Areas exposed because of heel, such as under-
Wires 1,2 decks, are to be included using the appropriate
Exposed beams and girders under deck 1,3
shape coefficients.
The design current speed uD(z) is either uW(z), uSS(z) 4.1.3 Forces caused by the action of waves on the
or unS(z), as defined in Section 1, C.2., C.3. or C.4., or installation/unit are to be taken into account in the
a superposition of these values, as applicable. structural design, with regard to forces produced di-
rectly on the immersed elements and forces resulting
3.2 Using qD(z) as defined above, design sea from heeled positions or accelerations due to motions.
current loads F(z) may be calculated according to the Theories used to calculate wave forces and to select
following formula: relevant force coefficients are to be acceptable to
Germanischer Lloyd.
F = qD(z) ⋅ A
4.1.4 Forces on appurtenances such as boat land-
ings, fenders or bumpers, walkways, stairways, grout
where
lines, and anodes shall be considered for inclusion in
F = current force [kN] the hydrodynamic model of the structure. Forces on
some appurtenances may be important for local mem-
qD(z) = current pressure [kPa] ber design. Appurtenances are generally modeled by
A = current projected area [m2] non-structural members that contribute equivalent
wave forces.
Values of the current projected area A may be cor-
rected for effects of marine growth, as applicable, 4.2 Design wave methods
compare Section 1, F.3. Methods to estimate design wave loads depend on the
hydrodynamic characteristics of the structure and on
3.3 Consideration shall be given to the possible the way the structure is held on location, as outlined in
superposition of current and waves. In those cases Table 2.2.
where this superposition is deemed necessary, the
current velocity shall be added vectorially to the wave 4.3 Method I.1: Rigidly positioned, hydrody-
particle velocity. The resultant velocity is to be used to namically transparent structures
compute the total force.
4.3.1 The Morison formula may be used to calcu-
late the force exerted by waves on a cylindrical object,
4. Wave loads such as a structural member. The wave force can be
considered as the sum of a drag force and an inertia
4.1 General force, as follows:
4.1.1 The design wave criteria have to be specified F = FD + FI = ½ ρ ⋅ CD ⋅ A ⋅ U ⋅ |U | + CM ρ V (δU/δt)
by the Owner / Designer. A design value of wave load
on a structural element (local wave load) or on the where
entire structure (global wave load) may be estimated
F = hydrodynamic force vector per unit length
by either using a design wave method, as outlined in
acting normal to the axis of the member
4.2 to 4.6, or a spectral method, as outlined in 4.7.
[kN/m]
4.1.2 Consideration is to be given to waves of less FD = drag force vector per unit length acting on the
than maximum height where, due to their period, the member in the plane of the member axis and
effects on various structural elements may be greater. U [kN/m]
Hydrodynamic characteristics
Kind of positioning
I. Transparent 1 II. Compact 2
1. Rigid 3 Method I.1 (see 4.3) Method II.1 (see 4.5)
2. Flexible 4 Method I.2 (see 4.4) Method II.2 (see 4.6)
1 A structure is considered hydrodynamically transparent if wave scattering can be neglected, i.e., if the structure does not significantly
modify the incident wave. This condition is satisfied if D/L < 0,2, where D is a characteristic dimension of the structure (e.g., diameter of
structural members, such as platform legs) in the direction of wave propagation, and L is the wave length.
2 A structure is considered hydrodynamically compact if scattering of sea waves cannot be neglected. This condition occurs if D/L > 0,2.
If D/L is about 0,2, a design value may be defined as the smaller one of the design values obtained from the alternative application of
methods I and II.
3 A structure is considered rigidly positioned if the wave-induced deviation from its equilibrium position in still-water is negligibly small
when compared to the wave height.
4 A structure is considered flexibly positioned if the wave-induced deviation from its still-water equilibrium position is of the order of the
wave height or more.
Chapter 4 Section 2 B Design Loads IV - Part 6
Page 2–4 GL 2007
FI = inertia force vector per unit length acting some members of conductor guide frames may
normal to the axis of the member in the plane experience their greatest stresses due to vertical
of the member axis and δU/δt [kN/m] drag and inertia forces, which generally peak
when the wave crest is far away from the struc-
CD = drag coefficient ture centerline.
ρ = density of water [kNs2/m4]
4.3.3 If the Morison equation is used to calculate
A = projected area normal to the cylinder axis per hydrodynamic loads on a structure, the variation of
unit length CD as a function of Reynolds number, Keulegan-
Carpender number, and roughness shall be taken into
= D for circular cylinders [m]
account in addition to the variation of the cross-
V = displaced volume of the cylinder per unit sectional geometry:
length
Reynolds number Rn = UmaxD/ν
= π D2/4 for circular cylinders [m2]
Keulegan-Carpenter number KC = UmaxT/D
D = effective diameter of circular cylindrical
member, including marine growth [m] Relative roughness = k/D
4.3.2 The vectorial superposition of local wave Table 2.3 Surface roughness
loads in a phase correct manner defines global wave
loads on the structure. Total base shear and overturn- Surface k
ing moment are calculated by a vector summation of Steel, new uncoated 5 ⋅ 10-6
local drag and inertia forces due to waves and cur-
Steel, painted 5 ⋅ 10-6
rents, dynamic amplification of wave and current
forces (see Section 3, H.), and wind forces on the Steel, highly rusted 3 ⋅ 10-3
exposed portions of the structure (see 2.). Concrete 3 ⋅ 10-3
Slam forces can be neglected because they are nearly Marine growth 5 ⋅ 10-3 to 5 ⋅ 10-2
vertical. Lift forces can be neglected for jacket-type
structures because they are not correlated from mem- 4.3.5 For smooth circular cylinders in steady flow,
ber to member. Axial Froude-Krylov forces can also where the cylinder length is significantly larger than
be neglected. the cylinder diameter, Table 2.4 lists design values of
The wave crest shall be positioned relative to the hydrodynamic coefficients CD and CM for two classes
structure so that the total base shear and overturning of Reynolds number.
moment have their maximum values. The following
aspects need to be considered: Table 2.4 Hydrodynamic coefficients CD and
CM for circular cylinders in steady
– The maximum base shear may not occur at the flow conditions
same wave position as the maximum overturn-
ing moment. Reynolds number (Rn) CD CM
– In special cases of waves with low steepness and < 10 -5
1,2 2,0
an opposing current, maximum global structure > 10 -5
0,7 1,5
force may occur near the wave trough rather
1. Corrections due to marine growth have to be made, as
than near the wave crest.
applicable.
– Maximum local member stresses may occur for 2. CD and CM values for more complicated structural elements
a wave position other than that causing the shall be provided by competent institutions. These values are
maximum global structure force. For example, to be approved by Germanischer Lloyd.
IV - Part 6 Section 2 B Design Loads Chapter 4
GL 2007 Page 2–5
4.3.6 For circular cylinders in supercritical oscilla- 4.4.2 Loads on structural elements not belong-
tory flow at high values of KC, with in-service marine ing to the mooring system
roughness, Table 2.5 lists design values of hydrody-
namic coefficients CD and CM. Wave-induced design loads used for strength analysis
of structural elements that do not belong to the moor-
ing system may be estimated by a phase correct vecto-
Table 2.5 Hydrodynamic coefficients CD and rial superposition of all local wave loads acting on the
CM for circular cylinders in oscilla- rigidly positioned (fixed) structure according to 4.3,
tory flow conditions Method I.1. The corresponding design loads for all
motion-induced loads may be calculated on the basis
Surface condition CD CM of a linear motion analysis. Such an analysis shall
account for all relevant degrees of freedom of the
Multiyear roughness, k/D > 1/100 1,05 1,8
structure being considered. Typical offshore structures
Mobile unit (cleaned), k/D < 1/100 1,0 1,8 may be classified according to the number of degrees
Smooth member, k/D < 1/10000 0,65 2,0
of freedom of rigid-body motions as listed in Table
2.6:
The smooth values will normally apply 2 m above the mean water
level and the rough values 2 m below the mean water level.
Table 2.6 Degrees of freedom of different kinds
The roughness for a mobile unit applies when marine growth is of offshore structures
removed between submersions of members.
Degrees of
Kind of structure
4.3.7 For several cylinders close together, group freedom
effects may be taken into account. If no adequate 6 Drill ships, supply vessels, tugs
documentation of group effects for the specific case is
available, the drag coefficients for the individual cyl- Anchored or dynamically positioned
semisubmersibles
inder may be used.
Loading buoys, storage tanks
4.3.8 The hydrodynamic modeling of jack-up legs Floating cranes, pipelaying vessels
may be carried out by utilizing the ‘detailed’ or the
‘equivalent’ technique. The ‘detailed’ technique mod- 3 Tension-leg platforms
els all relevant members with their own unique de- Guyed towers
scriptions for the Morison term values and with the 2 Articulated towers
correct orientation to determine relative normal ve-
locities and accelerations and the corresponding drag
For a six degree-of-freedom system the motion analy-
and inertia coefficients, as defined in 4.3.6. The hy-
sis may generally be based on the following linear
drodynamic model of the ‘equivalent’ technique com-
motion equations:
prises one ‘equivalent’ vertical tubular located at the
geometric center of the actual leg. The corresponding 6
∑ ⎡⎣ −ωD .(M jk + A jk ) + i.ωD .B jk + C jk ⎤⎦ ⋅ s Dk = Fj
2
(horizontal) relative velocities and accelerations are
applied together with equivalent hydrodynamic coeffi- j=1
To solve these equations for the motion components locities and accelerations caused by the large volume
sDk, the generalized masses Mjk of the structure (in- parts, however, should be accounted for when using
cluding mass moments of inertia for i, j > 3), the re- the Morrison equation.
spective global hydrodynamic added masses Ajk, the
global damping coefficients Bjk (viscous damping for 4.5.3 Hydrodynamic interaction between large
hydrodynamically transparent structures), and the volume parts should be accounted for.
global hydrostatic (restoring) coefficients Cjk need to
be defined. These global hydromechanic coefficients 4.5.4 In the vicinity of large bodies the free surface
may be obtained from calculation of local loads on all elevation (i.e., wave height) may be increased. This
structural elements below the still-water line. Linear increase shall be accounted for not only in the wave-
superposition of all local hydromechanic coefficients induced load calculation, but also when estimating the
determines the required global hydromechanic coeffi- under deck clearance.
cients. Details can be found in related text books.
Appropriate computer codes or a compatible proce- 4.5.5 In many cases second order wave-induced
dure may be applied upon agreement with Ger- loads may be important for the design of hydrody-
manischer Lloyd. namically compact structures.
After determination of the motion components, motion – In addition to first order (linear) loads, mean
induced local loads on all structural elements can be (nonlinear) second order wave (drift) loads and
estimated and added to the local wave loads as deter- nonlinear loads varying in time with twice the
mined for the rigidly positioned (fixed) structure, as first order (wave) frequency act on the structure.
applicable, finally yielding the resulting wave induced Wave-induced load effects of higher order than
(first order) local design loads on structural elements. two are usually neglected.
4.6.3 The second order (slowly varying) difference For a smooth circular cylinder the space averaged
frequency wave-induced loads (see 4.5.5) may be slamming pressure coefficient shall be at least Cps =
important for the design of mooring or dynamic posi- 3,0. For a flat bottom the slamming pressure coeffi-
tioning systems as well as for offshore loading sys- cient shall be at least Cps = 6,3.
tems. For hydrodynamically compact structures with a
small waterplane area, the slow drift forces may cause 4.9.2 Space averaged slamming pressure coeffi-
large vertical motions. cients for other shapes shall be determined using rec-
Second order loads shall be determined by a consistent ognized numerical and/or experimental methods, tak-
second order theory or by appropriate model tests. ing into account three-dimensional effects. Interface
capturing techniques of the volume-of-fluid (VOF)
4.7 Spectral methods may be used to obtain the type, for example, are appropriate numerical methods
response in natural (irregular) seas by linearly super- as they take into account viscosity, flow turbulence,
posing results from regular wave components of dif- and deformation of the free surface.
ferent amplitudes, wave lengths, and propagation
directions, assuming the natural seaway is made up of 4.9.3 Fatigue damage caused by wave slamming
a large number of regular waves of different length shall be taken into account. The fatigue damage
and height. The procedure to follow is outlined in caused by slamming has to be added to the fatigue
Section 1, D.5. contribution from other viable loads.
4.8 Wave impact loads 4.10 Impact related pressure from breaking
Structural members in the splash zone are susceptible waves
to loads caused by wave-induced impact (slamming)
when the member is submerged. These loads are diffi- Breaking waves causing impact pressures on vertical
cult to estimate accurately and should generally be surfaces shall be considered. In the absence of more
avoided by structural design measures. Long horizon- reliable methods, the procedure described in 4.8 may
tal members in the splash zone are particularly suscep- be used to calculate this impact pressure. The coeffi-
tible to impact related loads. cient CS depends on the configuration of the area ex-
posed to this impact related pressure. The impact ve-
4.9 For a cylindrical shaped structural member locity v shall correspond to the most probable largest
the slamming force per unit length may be calculated wave height.
as follows:
4.11 Air gap
FS = ½ ⋅ ρ ⋅ CS ⋅ D ⋅ v2
FS = slamming force per unit length in the direc- The air gap is defined as the minimum clearance be-
tion of the velocity v [kN/m] tween the underside of the unit in the elevated position
and the calculated crest of the design wave with ade-
ρ = density of water [kNs2/m4]
quate allowance for safety. It is usually not practical to
CS = slamming coefficient change the air gap in preparation for a storm and,
therefore, the air gap for an intended operation shall
D = member diameter [m] be determined based on a suitable return period. Omni-
v = relative velocity normal to member surface directional guideline wave heights with a return period
[m/s] of 100 years are recommended to compute wave crest
elevations above storm water level, even if a lower
For a smooth circular cylinder the slamming coeffi- return period is used for other purposes.
cient shall be at least CS = 3,0.
For jack-up platforms, the air gap shall be 1,20 m or
4.9.1 The slamming pressure space averaged over a 10 percent of the combined storm tide, astronomical
broader area (several plate fields) may be obtained as tide, and height of the maximum wave crest above
follows: mean low water level, whichever is less. An additional
pS = ½ ⋅ ρ ⋅ Cps ⋅ v2 air gap shall be provided for any known or predicted
long-term seafloor subsidence.
where
pS = space averaged slamming pressure [kPa] 4.11.2 Air gap for installations
ρ = density of water [kNs²/m4] The air gap is the clearance between the highest water
Cps = space averaged slamming pressure coefficient surface that occurs during the extreme environmental
conditions and the lowest part not designed to with-
v = relative velocity normal to member surface stand wave impingement. For fixed platforms, the air
[m/s] gap to be maintained shall be at least 1,5 m.
Chapter 4 Section 2 B Design Loads IV - Part 6
Page 2–8 GL 2007
5. Vibratory loads due to vortex shedding Drag can be reduced by adding streamlined fins and
splitter plates that break the oscillating flow pattern.
Flow past a structural member may cause unsteady Uneven vortex shedding can be induced by making
flow patterns from vortex shedding, leading to vibra- the member irregular, i.e., by adding spoiling devices,
tions of the member normal or in line to its longitudi- such twisted fins, helical strakes, or ropes wrapped
nal axis. Such vibrations shall be investigated. around the member. Tests should determine the effi-
At certain critical flow conditions, the vortex shedding ciency of the spoiling device to be used.
frequency may coincide with or be a multiple of the
natural frequency of motion of the member, resulting 6. Loads due to climatic conditions
in harmonic or subharmonic resonance vibrations.
The vortex shedding frequency in steady flow with 6.1 Snow and ice accretion
Keulegan-Carpender number KC (see 4.3.3) greater
than 40, such as in a current, may be obtained as fol- 6.1.1 If icing is possible, and ice or snow covers
lows: parts of the structure, the weight of ice or snow shall
be added to the permanent load under any loading
f = Sn ⋅ (U / D) conditions.
For irregular waves characterized by a narrow band 6.1.4 Loads caused by ice and/or snow on open
spectrum, the vortex shedding frequencies are a com- decks and externally exposed walls are to be specified
bination of these two limiting cases. according to recommendations of competent inde-
pendent authorities/institutions. In absence of specific
To reduce the severity of flow-induced oscillations information, new snow may be assumed to have a
caused by vortex shedding, either the member’s shape density of 100 kg/m³, and the average density of ice
or its structural properties should be changed. This can formed on the structure may be taken as having a
be achieved by altering the member’s mass or the density of 900 kg/m³.
member’s damping characteristics. As a result, its
natural frequency will be changed so as to lie outside 6.2 Temperature influences
the range for the onset of resonant vortex shedding.
Stresses in and deformations of the structure or parts
Spoiling devices are often used to suppress vortex of it, which are induced by extreme temperature gradi-
shedding lock-on. The underlying principle is to either ents in the structure, shall be added to the permanent
reduce drag on the member or to cause the shed vor- load induced stresses and deformations under operat-
tices to become uneven over the length of the member. ing conditions, where they are deemed to be relevant.
IV - Part 6 Section 2 C Design Loads Chapter 4
GL 2007 Page 2–9
7.2 Ice loads are to be evaluated for a range of – incomplete ability to describe natural processes
ice-structure interactions. The range of interactions is in engineering models
determined by the ice environment of the area of op-
– human participation in engineering processes
erations, see Section 1, G., and may include the fol-
lowing aspects: In case of ice-structure interaction, the most signifi-
– ice pressure loads from continuous first or multi- cant uncertainties arise from the available models. It
year level ice should always be considered that none of the publicly
available methods delivers reliable results.
– loads from collision with first and/or multi-year
ridges within the ice field 7.8 Model tests are recommended for evaluation
of global loads and confirmation of expected ice fail-
– impact loads caused by drifting ice floes (sea ice ure modes.
or glacial ice)
– impact loads caused by icebergs 7.9 Further details are described in Germanischer
Lloyd Rules IV – Industrial Services, Part 6 – Off-
7.3 Ice load evaluations are to include the forces shore Technology, Chapter 7 – Guideline for the Con-
exerted by ice on rubble ice or other ice pieces that are struction of Fixed Offshore Installations in Ice In-
in firm contact with or held by the structure. This is of fested Waters.
particular concern for multi-legged structures and for
structures designed to cause ice failure in modes other
than crushing.
C. Permanent Loads
7.4 The brittle nature of ice can lead to periodic
dynamic loading, even during ice-structure interac-
1. Permanent loads are loads acting throughout
tions where this is not initially apparent. Dynamic
the lifetime of the unit/installation or during prolonged
amplification of the structure’s response in its natural
operating periods. Such loads may comprise the
vibratory modes shall be evaluated.
weight of structures (dead load), equipment, perma-
nent ballast, and effects of hydrostatic pressure ex-
7.5 When calculating ice loads, the following erted on parts of the submerged structure (buoyancy).
parameters specifying the condition of the ice have to
be considered:
2. Permanent Loads shall be clearly stated and
– thickness of a level ice sheet accounted for in the design documents and calcula-
tions.
– temperature or temperature gradient in the ice
– orientation of the ice crystals 3. In cases where loads/weights may be acting
– bulk salinity over longer periods, but not necessarily at all times
(e.g., when using certain kinds of equipment), these
– total porosity of the ice (brine volume, gas pock- cases may have to be investigated to account for the
ets, voids) most unfavorable condition.
Chapter 4 Section 2 E Design Loads IV - Part 6
Page 2–10 GL 2007
These minimum values correspond to a vessel of 5000 2.3 Accidental impact loading
t displacement with an impact speed of 2 m/s. A re-
duced impact energy may be acceptable if the size of In cases where the stiffness of the impacted part of the
the visiting vessels and/or their operations near the installation is large compared to stiffness of the im-
offshore installation are restricted. In this instance, a pacting part of the vessel, as for example in collisions
reduced vessel size and/or a reduced impact speed involving concrete installations or fully grouted ele-
may be considered. ments, the impact energy absorbed locally by the in-
stallation may be low. In such cases, it is important to
examine damage caused by the impact force.
2.2.2 Impact speed
The impact force may be calculated as follows:
The reduced impact speed may be estimated from the
following empirical relationship: F = P0
or
v = ½ ⋅ HS
F = v⋅ c⋅a ⋅Δ
where
whichever is the less, where
v = impact speed [m/s]
F = impact force [kN]
HS = significant wave height [m]
P0 = minimum crushing strength or punching
Here the significant wave height HS is to be taken shear, as appropriate, of the impacting part of
equal to the maximum permissible significant wave the vessel and the impacted part of the instal-
height for vessel operations near to the installation. lation [kN]
2.2.3 Energy absorbed by the structure v = impact speed [m/s]
The energy absorbed by the installation during the c = total spring stiffness of the vessel and instal-
collision impact will be less than or equal to the im- lation related to the impact point [kN/m]
pact kinetic energy, depending on the relative stiffness
a = vessel added mass coefficient, see 2.2.1
of the relevant parts of the installation and the impact-
ing vessel that the installation comes in contact with, Δ = displacement of the vessel [t]
the mode shape of the collision, and the vessel’s op-
eration. These factors may be taken into account when
considering the energy absorbed by the installation. 3. The regulations of competent Authorities
and/or Administrations have to be observed, particu-
For a fixed steel jacket structure, it is recommended larly regarding collisions.
that the energy absorbed by the installation should not
be taken less than 4 MJ unless a study of the collision 4. According to Section 3, C.4., loading condi-
hazards and consequences specific to the installation tion 4 – Accidental loads, the choice of accident cases
demonstrates that a lower value is appropriate. Exam- and the determination of loads will be considered on a
ples of such structures are small, occasionally manned case to case basis.
and infrequently supplied installations, or structures
where there is a restriction on the size of the visiting
vessel. 5. Consequences of damage
For vessels of less than 5000 t displacement, the The primary structure shall be designed to ensure that
minimum energy to be absorbed by the installation accidental damage does not cause complete collapse.
may be reduced to a value given by the following Damaged members shall be considered to be totally
relationship: ineffective unless it can be shown by analysis or tests
that they retain residual load-carrying capacity.
Ea = 0.5 + Δ2 (4,2 × 10-7 - 5,6 x 10-11 Δ)