15.1 250 kg/h of air saturated at 2°C is mixed with 50 kg/h of air at 35°C and 80% RH/
Determine the final state of air.
Given:
Schematic Diagram:

250 kg/h
2°C DBT
100%RH
1

50 kg/h
35°C DBT Mixing Box
80% RH 2 3
Cooling coil
h =109 kJ

ω =0.029 k

h =29 kJ /
h =13 kJ /

ω =0.0044

T=
T= T=
Psychrometric Chart:

Solution:

As per steam table, At T DP 1=2 ℃

pv =0.0007056 MPa=0.7056 kPa


pv
ω =0.622 0.7056 kgw. v.
=0.622× =0.00436
1
pb− 101.325−0.7056 kgd . a .
pv

As per steam table, At T DP 1=35 ℃

ps=0.005628 MPa=5.628 kPa


pv pv
RH = →0.80=
ps 5.629

pv =4.5032
kPa 4.5032 kgw . v .
pv =0.622× =0.0289
ω =0.622
2
pb− 101.325−4.5032 kgd . a .
pv

Mixing Process: moisture and enthalpy balance


ω1 m1+ ω2 m2=ω3( m1 +m 2 )
(0.00436) (250)+( 0.0289) (50)=ω3 (250+50)

( 0.00436 )( 250 )+ ( 0.0289 ) (50 ) kg w . v .


ω3 = =0.00845
(250+50 ) kgd. a .
h1=h=ha+ ωh v
h2=h=ha+ ωh v
h1=1.005 T DB+ω (2501+1.88 T DB)
h2=1.005 T DB+ ω(2501+1.88 T DB)
2501+1.88 (35)
2501+1.88(2)h2=(1.005 ×35)+0.0289 ¿
h1=(1.005 × 2)+0.0044 ¿

h1=12.9308 kJ / k g
h2=109.3556 kJ / k g

h1 m 1 +h2 m 2 =h 3 ( m1 +m2 )

(12.93) (250)+(109.3556) (50 )=h3 (250+50)

( 12.93 ) ( 250 ) +( 109.3556 ) ( 50 )


h3= =29.001 kJ / kg
(250+50)

Final state of air:


ω =0.00845 kgw. v . h =29.001 kJ
3 3 atT DP 3 =7.6 ℃
kgd . a . kg
15.3 500 kg of air is supplied per minute to an auditorium maintained at 21°C and 40% RH. The
outside air at 5°C DBT and 60 RH is first passed over heating coils and is heated until its WBT
is equal to room WBT. It is then passed through an adiabatic saturator and is finally heated at
45°C before being supplied to the room. Determine:
i) The heat added in both the heating coils
ii) The mass of water evaporated in the air washer.

Schematic Diagram:
5°C DB
60% RH

m = 500 kg/min Adiabatic SaturatorT


Heating Auditorium
Outside air Coil WBT =WBT room =45 ℃

h =70 kJ

h =h =37 kJ

ω =0.0095
h =13 kJ
ω =0.0061
ω =0.0032

T=13 T= T =45
T= T=

Psychrometric chart:
ion:

So
lut
kg
500
m min kg
m 1= = =489.405
1+ ω1 1+ 0.0032 min

i) The heat added in both the heating


coils Solving for heat added on first coil:

kJ 1 min
ma ( h2−h1 )=498.405 ( 37−13 )=11961.72 ×
min 60 sec

Heat added on first coil=199.362kW

Solving for heat added on second coil:


kJ 1 min
ma ( h2−h1 )=498.405 ( 70−37 )=16447.365 ×
min 60 sec

Heat added onsecond coil=274.123 kW

ii) The mass of water evaporated in the air washer.

ma ( ω3−ω1 ) =498.405(0.0095−0.0032)

kg
Mass evaporated = 3.140
min
15.5 In an auditorium which is to be maintained at a temperature not exceeding 24°C, and a
relative humidity not exceeding 60%, a sensible heat load of 132 kW and 84 kg/h of moisture has
to be removed. Air is supplied to the auditorium at 15°C.
a. How many kg of air per hour must be supplied?
b. What is the dew point temperature of supply air and what is its relative humidity? 13.8
c. How much latent heat is picked up in the auditorium?
d. What is the sensible heat factor?
e. What is the ADP of the coil, and what is its BPF?
Given:
TR=24 ℃ QS=132 kW RH =60 %

T S=15 ℃ ma=84 kg/ h

Solution:
h =52.9

h =39.7

T=13
ADP=1
As per psychrometric chart, As per steam table, at T R =24 ℃
kJ
h =52.9 kJ / kg h =39.7 kJ / kg h =2444.7
R S fg
kg
a. How many kg of air per hour must be supplied?
Solving for QL:
QL=ma hfg
kg 1 h kJ
Q =84 × ×2444.7 =57.043 kW
L
h 3600 s kg

Solving for mass of air per hour that must be supplied:


QT =QS+QL=ma(hR−hS)
kJ
QS + Q L (132+57.043) s
m= = =14.3214 kg/ s
a − h kJ
Rh S (52.9−39.7)
kg
kg 3600 s
m =14.3214 ×
a
s 1hr
kg
m =51557.1818
a
h
b. What is the dew point temperature of supply air and what is its relative humidity?
As per the psychrometric chart, the dew point temperature of supply air is:
TDP=13.9 ℃

As per steam table via Single Interpolation:

pv (kPa) T DP(℃) 13.8−13 x −1.4974


=
14−13 1.5984−1.4974
1.4974 13
? 13.8
1.5983 14 pv @ 13.8 ℃=1.5781 kPa

ps@ 15℃ =1.7051 kPa

Solving for relative humidity:


pv 1.5781
RH = ×100 %= × 100 %
ps 1.7051
RH =92.5518 %

c. How much latent heat is picked up in the auditorium?


QL=ma hfg
kg 1h kJ
Q =84 × ×2444.7
L
h 3600 s kg
QL=57.043 kW

d. What is the sensible heat factor?


QS
SHF =
QS +Q 132
L = 132+57.043

SHF =0.69825

e. What is the ADP of the coil, and what is its BPF?


As per the psychrometric chart, the ADP of coil is
ADP=13.5 ℃
Solving for BPF:
T S −ADP 15−13.5
BPF = =
T R − ADP 24−13.5

BPF =0.1429
15.7 Given for the air conditioning of a room
Room Conditions: 26.5°C DBT and 50% RH
Room sensible heat gain = 26.3 kW
Room sensible heat factor = 0.82
Find:
i. The room latent heat gain
ADP=1

ii. The apparatus dew point


iii. The cmm of air if it is supplied to the room at the apparatus dew point.
iv. The cmm and specific humidity of air if it is supplied to the room at 17°C.
Solution:
i. The room latent heat gain

Qs 26.3
SHF= → 0.82=
Qs+QL 26.3+QL

QL=5.7732 kW

ii. The apparatus dew point

As per the psychrometric chart, the ADP is:

ADP=13.8 ℃

iii. The cmm of air if it is supplied to the room at the apparatus dew point.
QS
cmm=
0.0204(T R −ADP = 26.3
) 0.0204 (26.5−13.8)

cmm=101.5130 m3
min

iv. The cmm and specific humidity of air if it is supplied to the room at 17°C.

QS
cmm= 26.3
0.0204 (T R −ADP = 0.0204 (26.5−17)
)

cmm=135.7069 m3
min
15.9 An air washer cools and dehumidifies 18,200 kg of dry air per hour from 41°C DBT and
24°C WBT. Chilled water enters the washer at 7°C with flow of 18,500 kg per hour. The washer
is 88% effective. What is the heat removed from the air in kW?
Schematic Diagram:

ma = 18200 kg/h

DBT = 41 C

MW = 18500 kg/h WBT = 24 C

DBT = 7 C

Psychrometric Chart:

h =72.8 kJ /
h =63 kJ / k

ω =0.0011
Given:
kg
T =41℃ m =18200
T =7 ℃
DB 1 a DB
h
kg
TWB 1 =24 ℃ mw =18500 η=88 %=0.88
h

Solution:
T DB 1− TWB 1 41−24
η= → 0.88= =21.68 ℃
T DB 1−TWB 41−TWB 2
2

As
per
psyc
hro
metr
ic
chart
:
At

TWB
2=2
1.68

h2
=6
3
kJ
/
kg
Solv
ing
for
heat
rem
oved
:
kJ 1h kj kj
ma ( h2−h1 )=18200 × (72 −63 )
h 3600 s kg kg
Heat removed=45.5 kW
15.11 300 cmm of outside air at 5°C and 60& RH are heated and humidified to maintain room
condition at 21°C and 40% RH. Devise a suitable system for the air conditioning and find the
kW of various heaters and the moisture added. The supply air temperature at 45°C and the room
sensible heat factor is 0.75.
Given:
Schematic Diagram:

0.75 SHF
Supply Air = 45C
21C DBT
100%RH

5°C DBT
60% RH Mixing Box
Cooling coil

ω =0.0085

ω =0.0032
Solution:
m 1min
300 3
×
min 60 sec
Qs=ma ( 1.005+1.88 ω o ) ( t ) Qs= ( 1.005+1.88 (0.0032) ) (45−5)
s−t o
3
m
0.791
kg
Qs=255.63 kW

m3 1 min
300 ×
min 60
QL =ma (2500) ( ω s−ω o ) QL= (2500) (0.0085−0.0032)
sec
3
m
QL=83.7547 kW 0.791
kg
15.13 A summer air conditioning plant mixes 70 cmm of outside air at 35°C DB and 23°C WB
with 210cmm of return air at 24°C DB and 50% RH. The mixture passes over a cooling coil. Air
off the coil is 90% RH. The room is SHF is 0.7.
Schematic Diagram:

210 cmm
24 CDB
50% RH
70 cmm

35 CDB
90% RH
23 CWB

Psychrometric Chart:

h 0=68.25 kJ / kg 0.8875 m 3 / kg
hm=53 kJ / kg 0.856 m 3 / kg
o
h R=48.25 kJ / kg h B=42 kJ / kg
hs=27.25 kJ / kg
8.2 C R m
7 Cs
B
i. Find the ADP, and air off the coil dew point and dry bulb temperatures.
70 kg 210 kg
m= =78.873 m= =245.33
o
0.8875 min R
0.856 min

kg
m =78.873+245.33=324.203
m
min

DBT = (78.873 × 35 + 245.33× 24=26.68


) C
m
324.203

DBT m=26.68 ℃

DBTR =24 ℃

DBTo=35 ℃

DBTs=10 ℃

ADP=7 ℃

DBTs=8.2℃

ii. How much cooling in kW is unit doing?


mm kg 1 min
Ref Load= ( h −h )=324.203 × (53−27.25)
60 m s min 60 s

Ref Load =139.14 kW

iii. How much of the total load is sensible, and how much latent is latent?
kg 1 min
Q =m ( h ) =324.203 × (48.25−42)
−h

L m R
B min 60 s
QL=33.771 kW
kg 1 min
Q =m ( h − h ) =324.203 × (42−27.25)
s m B
S min 60 s

QS =79.7 kW