SS002-Suspended-Ceiling Rev 0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

JKT02 SS2/1

MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

SECTION 2

2.0 SUSPENDED CEILING SYSTEM

2.1 GENERALLY

Whenever a material, item, article or product is specified by trade/brand name,


manufacturer's name or catalogue reference, the Contractor may propose to use its
equivalent in the Works, subject to the written approval of the Architect.

Suspended ceiling systems used in the Works shall be of proprietary design, proven
in use and erected to approval by the manufacturer/supplier's erection service.
Proprietary fire rated ceiling shall be constructed to specialist supplier’s
specifications.

All components shall be compatible with each other and when assembled, the
system shall form a functional and aesthetic whole.

Upon completion of the ceiling works, remove debris and excess materials, clean or
replace dirty or damaged material and leave the work clean and neat.

All components of the suspension system to be metal.

All components of ceiling panels and suspension systems in exterior, non air-
conditioned or exposed location to be external quality, humidity resistant and non-
ferrous.

The suspended ceiling includes the suspension system, acoustical materials, ceiling
boards, stainless steel trimmers/framing/lighting trough, egg crate diffusers and
aluminium trimmers/framing for the integration of lighting and ventilation
components.

The Contractor shall provide all penetrations for ducting, diffuser grilles, fire
protection services, cables etc trim and seal around all ducts and registers
penetrating the ceiling.

The Floor to ceiling heights shown on the drawings must be achieved and the
contractor will have allowed all necessary measures in the services and structure to
maintain the specified ceiling heights while meeting all other requirements of the
contract drawings and specifications.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/2
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

100% of all ceilings, by cost and surface area, meet the general emission evaluation
or inherently non-emitting source criteria as required for the LEED Gold rating.

The ceiling product category includes all ceiling panels, ceiling tile, surface ceiling
structures such as gypsum or plaster, suspended systems (including canopies and
clouds), and glazed skylights. Documents must be provided to support the claim.

For atleast 90% of the regularly occupied floor area, meet or exceed the thresholds for
area-weighted average surface reflectance i.e. 90% for ceilings.

2.2 STANDARDS

Unless otherwise agreed by Architect, ensure all of the works comply with the
relevant requirements of the Standards and Codes listed below or referenced in the
body of the Specification. Alternative Standards and Codes may be submitted to the
Architect provided it can be demonstrated that the alternative Standards and Codes
comply with the requirements of the standards specified. All standards and Codes
quoted are the current version, unless specific year references are noted.

Other Standards

BS EN 1461 Hot Dip Galvanised Steel

BS EN 10152 Steel Finishes

BS EN 20354 Acoustics of sound in reverberation rooms

BS CP 290 Code of Practice for Suspended Ceiling using Metal Fixing


Systems

BS 1191 Gypsum building plaster

BS 5368: Part 3 Methods of testing window: Wind resistance test

BS 5821 Sound Transmission

BS 6375: Part 1 Performance of Windows: Classification of weathertightness

BS 6496 Specification for powder organic coatings for application and


stoving to aluminium alloy extrusions, sheet and preformed
sections for external architectural purposes

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/3
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

BS 6497 Powder Coating Steelwork

BS 8290 Suspended ceilings

ASTM C 636 Standard Practice for Installation of Metal Ceiling Suspension


Systems for Acoustical Tile and Lay-In Panels

ASTM E 84 Test Method for Surface Burning Characteristics of Building


Materials

ASTM E 580 Standard Practice for Installation of Ceiling Suspension Systems


for Acoustical Tile and Lay-in Panels in Areas Subject to
Earthquake Ground Motions.

2.3 COORDINATION WITH M&E AND OTHER SERVICES

Co-ordinate the ceiling works particularly the interfacing with the following trades

a) Partition and heads of partition

b) Affected mechanical and electrical services installations interfacing with the


suspended ceilings both above and below the ceiling line, including forming
openings for modular lighting, air diffusers, smoke and heat detection systems,
sprinkler installations, signage and the like,

c) The air-conditioning duct/grilles, light trunking/ fittings and other M&E services
will be done by other specialist contractors.

The Contractor will also have to liaise and co-ordinate with the other contractors on
the work sequence and structured cabling works, building construction works, etc.

2.4 CEILING LAYOUT AND SHOP DRAWINGS

The Contractor is required to submit shop and detailed drawings for the ceiling for
the Architect's approval before proceeding with the works.

Although the ceiling layout is indicated on drawing, this is only indicative and the
Contractor must submit a larger scale plan showing the exact layout after
coordination between MEP, structure and any specialist services and to indicate any
cutting of ceiling boards/panels.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/4
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

2.4.1 Work Submissions

Upon commencement of the works, submit technical information and data


demonstrating conformance with the design intent as shown in the drawings.
Contractor to prepare shop drawings showing clear and complete details of each
assembly, component and connection together with detailed information relative to
their fabrication, material, surface treatment and erection.

Include information on:

a) Setting out plans

b) Sectional details of typical and non-typical elements and associated elements

c) Sectional details of all interfaces with adjoining structures and disciplines

d) Dimensions of overall assembly

e) Procedures and sequence to produce distortion-free components and


assemblies

f) Identification of type and extent of protective coatings to be applied

g) Methods of meeting performance requirements for thermal insulation, fire


resistance, sound transmission and the like

h) Identification of type and location of attachments to be built in to the building


structure

i) Identification of junctions and trims to adjoining surfaces

2.5 SAMPLES AND MOCK-UPS

2.5.1 Samples

Contractor to submit samples of part of each ceiling showing face materials, and
grid supports and technical data.

In addition, the contractor is required to submit fire and acoustic test certificates and
assessments for each type of ceiling assembly, where applicable.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/5
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

2.5.2 Mock-ups

The Contractor is required to install a mock up ceiling of each different type


indicated on the drawings, for the Architect’s approval, before proceeding with the
works. Mock-ups to reflect all typical junctions and features in the ceiling design.
Unless otherwise agreed, selected area to be 4500mm x 4500mm. Complete the
mock-up and submit to the Architect prior to procurement and fabrication.

2.6 TEST

2.6.1 Tensile pull out test

Unless otherwise directed, conduct tensile pull out test for all ceiling works at one
location per 5 floors of building. At least one pull out test shall be conducted per
project. The location of pull out tests shall be selected by the Architect.

2.6.1.1 Mineral Fibreboard ceiling

Tensile pull out test results shall exceed:

a) For 1200mm x 600mm ceiling panel – 2kg

b) For 600mm x 600mm ceiling panel – 4kg

c) For suspension system (or wall-mounted ceiling grid system)

i. At anchor points – 50kg

ii. At mid span of suspension grid – 12kg before L/20


deflection.

2.6.1.2 Seamless fibrous plasterboard

Tensile pull out test results shall exceed:

a) For plasterboard at centre of suspension grid – 20kg

b) For suspension system

i. At anchor points – 50kg

ii. At mid span of suspension grid – 12kg before L/20


deflection.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/6
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

2.6.1.3 Skim Coat Ceiling

Conduct tensile pull out test between 21 days to 28 days after


application. Average result of pull out test shall exceed 0.40N/mm2.
Test result of each location shall not be less than 0.30N/mm2.

2.6.2 Moisture Penetration

Conduct inspection of plasterboard ceiling after operating building M&E services for
48 hours to observe for wet or damp locations due to leakage or condensation.

Conduct inspection of plasterboard ceiling after completion of roof shelter works to


check for evidence of rainwater drips to plasterboard ceiling.

Mark and annotate on a relevant reflected ceiling plan drawing with description of
causes for moisture or damp.

Submit remedial measures to eliminate moisture due to leakage or condensation, to


SO before commencement of the measures. Include approved remedial measures
in the maintenance manual.

2.7 CEILING SPECIFICATIONS

2.7.1 Types of Suspended Ceilings

Suspended ceiling system(s) for the project may consist of one of the following types:

a) Mineral fibreboard acoustic ceiling: Modular, regular mineral fibreboard suspended


ceiling tiles, on a pre-finished metal suspension system, in either concealed or
exposed manner.

b) Metal ceiling: Modular, metal suspended ceiling either in tiles or as planks (strips)
on concealed suspension systems.

c) Seamless fibrous plasterboard suspended ceiling system with a skim coat of


plaster finish, supported on concealed metal suspended system

d) Skim coating to soffit of exposed concrete slab where there is no suspended


ceiling.

e) Semi -concealed resin-bonded glass fibre ceiling.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/7
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

2.7.2 Mineral Board Acoustic Ceiling

Where described in the schedule, mineral board ceiling shall be manufactured from
acoustic mineral fibre or high-density resin bonded glass fibre finished with
microporous white textured surface and fully sealed painted edges or equal and
approved.

The acoustic ceiling boards shall be in 1200/600x600x40mm thick suspended on an


exposed, concealed or semi-recessed on all 4 sides. The visible surface and edges
shall be factory painted finish with light reflectance of  84% and light diffusion of 
87% providing optimum light efficiency for indirect lighting. The microporous painted
surface provide good air permeability for excellent sound absorption properties. The
back of the boards shall be faced with clear glass tissue to provide a fully sealed,
high performance acoustic ceiling board. All cut edges of the ceiling board for
edging, opening, etc shall be painted/ sealed with emulsion paint on site.

Colour of board shall be in RAL9010 (otherwise stated by Architect).

a) Total Moisture Resistance

The boards shall meet the Standard for Total Moisture Resistance (TMR) in
accordance with ISO 461 and shall withstand relative air humidity exposure of

up to 95% at 40o C without causing visible sagging, warping or delamination.


No hygroscopic ceiling materials shall be used.

b) Thermal Insulation

The boards shall have U value not exceeding 0.031W/m2.

c) Fire Safety Performance

Fire resistance shall meet with FSSD or local Fire Bureau requirements.

The boards shall be non-combustible meeting Class 0 rating as defined in the


Building Regulations BS 476 Fire Propagation Test and Surface Spread of
Flame Test. Ceiling materials or any of its parts shall not contain any
substance, which will emit toxic fumes as a result of overheating or combustion
and also meeting DIN Classification. Alternatively, Surface Burning
Characteristics of Maximum 25/450 flame spread/smoke developed index
when tested in accordance with ASTM E 84.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/8
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

Where a Ceiling is penetrating by Multi-service runs, e.g. pipework, ductwork,


trunking, cabling, etc., the relevant section or sections of the barrier shall be
replaced with materials which are equally incombustible and to details
approved by Architect.

Mineral wool wire reinforced mattress cavity barriers shall be installed where
necessary as per fire safety report/ local fire regulations.

d) Sound Absorption

The absorptive boards and reflective boards shall achieve sound absorption
Class A and C respectively tabulated below in accordance with the BS EN
20354, obtained by testing in accordance with the room method (EN ISO 354).
Boards shall be laid in accordance with the ceiling layout plans.
Absorptive Boards with 200mm Air Gap

Frequency 125 250 500 1000 2000 4000


(Hz)

Absorption 0.10 0.45 0.65 0.75 0.85 0.8


Coefficient
Noise Reduction Coefficient (NRC) is 0.9

Reflective Boards with 200mm Air Gap

Frequency 125 250 500 1000 2000 4000


(Hz)

Absorption 0.40 0.30 0.30 0.25 0.15 0.10


Coefficient
Noise Reduction Coefficient (NRC) is 0.95

The method of testing shall conform to EN ISO 354 and carried out by any of
the following accredited laboratories:

1) SP – Swedish National Testing and Research Institute

2) Institute of Sound and Vibration Research, University of Southampton, UK

3) Acoustical Investigation and Research Organisation Ltd, UK

4) Sound Research Laboratories Ltd, UK

Products tested in laboratories not listed above shall be accompanied by or full


laboratory technical report for Consultant’s verification.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/9
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

e) Reverberation Time Results

The performance of the combined absorptive and reflective ceiling system shall
meet the reverberation time (RT) criterion recommend by Acoustical society of
America or Building Bulletin 87 (UK). Contractor shall ensure that the RT does
not exceed 0.8 seconds (mean of 500Hz and 1000Hz) in an unoccupied
classroom.

f) Suspension System
[Applicable to proposed Ceiling Type 1 & 2]
Suspension system shall be of Armstrong Ceiling system Ultima+ Op or
approved equivalent, unless otherwise specified by Architect. The ceiling shall
conform to BS EN 13964.

Ceiling Type 1 :

Armstrong Ultima+ Op Clean Room System 7684M, White

• 1200mm x 600mm x 20mm grid with square lay-in

• Suspension System: Clean room 24mm grid system; Colour to match

• Accessories: PVC hold down clip for lay-in board

• Location: As specified in Finishes Key Plan Series

Ceiling Type 2 :

Armstrong Ultima+ Op Square Lay-In 7682M, White

• 600mm x 600mm x 20mm grid with square lay-in

• Suspension System: Prelude Grid Square Lay-in, 24mm exposed tee grid;
Colour to match

• Location: As specified in Finishes Key Plan Series

Suspension system may be of the following types, comply with BS CP 290:

a) Joint-less systems

b) Frame and tile systems (exposed grid)

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/10
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

Mineral fibreboard ceiling panel relying on self-weight on exposed metal grids


shall not be used in areas where there are open fenestrations. No ceiling board
shall be dislodged resulting from wind uplift pressure.

Exposed Ceiling grid & tee system colour shall match with selected ceiling
board colour, unless otherwise stated by Architect, to be submitted for
Architect’s approval.

g) Indoor Air Quality

The boards shall be suitable for clean and hygienic environment usage, tested
and achieve cleanroom class M3.5/100 according to US Federal Standard
209E. The boards shall also conform to the Swedish Asthma and Allergy
Association Certification, or equivalent local Standards.

h) Environmental Impact

The boards shall be environmental friendly and of sustainable materials to


achieve intended LEED Gold Rating.

100% of all ceilings, by cost and surface area, meet the VOC emission
evaluation or inherently non-emitting source criteria as required for the LEED
Gold rating.

The ceiling product category includes all ceiling panels, ceiling tile, surface
ceiling structures such as gypsum or plaster, suspended systems (including
canopies and clouds), and glazed skylights. Documents must be provided to
support the claim.

i) Cleaning and Maintenance

The board surface shall withstand and can easily be cleaned by dusting,
vacuum, dry cloth or damp sponge.

2.7.3 Seamless Fibrous Plaster Board Ceiling

The fibrous plaster ceiling shall be 12.5 mm thick and to be moisture resistant and
external quality. Where ceiling is used externally, such as walkways, corridors or car
porches, submit waterproofing additives for water resistance.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/11
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

a) General Composition

Plasterglass shall consist of Gypsum Plaster reinforced with strands of


Fibreglass at the ratio of 365 gms per m² for 12.5mm thickness. Gypsum
plaster shall be manufactured to the relevant AS Gypsum Plaster for Building
purposes.

Fibreglass shall be Siland sized Type C glass, filament dia. 19 ±0.8 microns.

Water moisture resistant fibrous plaster ceilings shall be an approved


Plasterglass ceiling incorporating a silicone based additive, which when added,
forges a close knit crystalline gypsum particle, reducing porosity and has a
water repellent surface.

b) Perimeter Treatment

At all perimeter interfaces use aluminium profile to stiffen edge, either straight
or curved as necessary. Edging material shall be capable of receiving skim
coat in a manner consistent with a ceiling soffit.

Jointing of perimeter trims shall be carried out neatly without lipping and
twisted. Use mitred joints at all internal and external corners and the longest
lengths of trims available from the manufacturer to keep immediate butt joints
to a minimum. Coordinate joints of straight runs to coincide with grid locations.

c) Early Fire Hazard Properties

Plasterglass shall be tested in accordance with AS 30 and results confirmed in


respect of:

Fire Hazard Properties

Ignitability Index 0

Spread of Flame Index 0

Heat Evolved Index 0

Smoke Develop 0

Fire Rating 0

Test results indicating that Plasterglass materials supplied to projects have


qualified for Fire Resistance rating in accordance with PSB. Alternatively,

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/12
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

Surface Burning Characteristics of Maximum 25/450 flame spread/smoke


developed index when tested in accordance with ASTM E 84.

d) Workmanship

Installation of fibrous plaster ceiling is to be carried out by competent


tradesmen experienced in fibrous plaster ceiling methods.

e) Metal Suspension System

The ceiling shall be suspended by metal suspension in hot dip galvanised


metal.

Hangers to be suspended at maximum 1000mm centres by means of 22


gauge x 25mm Galvanised metal straps power fixed to concrete soffit at
1000mm centres.

Perimeters to have 50 x 50mm wall plate at joist ends power fixed to wall at
approximately 600mm centres.

f) Fixing of fibrous plaster ceiling by Grouting

i. Where fibrous plaster ceiling are fixed for ceiling by grouting over joists or
battens the background shall be substantially even and free from any
protrusions liable to adversely affect the fixing of the sheets.

ii. Fibrous plaster ceiling shall be fixed to joists or battens with 40mm
temporary pin-up nails, ensuring that each sheet finishes level with the
adjacent sheets. Perimeter of ceiling may be permanently nailed with
25mm galvanised clouts, ensuring such nailing points will be covered by
Plasterglass or other cornice moldings.

iii. Using approved Casting Plaster mixed with water at the ratio of two
plaster to one of clean water by volume and Fibreglass Strands, the
Plasterglass sheets are then grouted over joists or battens. Each grout to
be approximately 35mm wide and are to be spaced at approximately
450mm along each joist. Continuous grouts are to be applied to all joints.

iv. Screws must be rust proof.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/13
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

g) Flush Joints

Where grouting is not applied at the back of the flush joint, the joint shall be
kept open 10mm to facilitate caulking with approved Bonding compound from
the face side. The joint is then trowelled with Stopping Compound to leave a
flush surface in true relationship to the adjacent surface.

h) Services and fittings

Seamless fibrous plasterboard ceiling may house equipment such as light


fittings, electronic alarm sounders, smoke detectors, air grilles and sprinkler
heads. These shall be independently supported without imposing load on ceiling
material and system.

Forming apertures and perforations to receive equipment shall be in accordance


with manufacturer’s procedures using approved tools.

2.7.4 Concealed Grid Ceiling with Fire Rating

[Applicable to proposed Ceiling Type 3 & 4]

Where described in the schedule, the ceiling system shall comprise of Firestop
boards suspended from hanger systems, cross rails, and furring channels. The fire
rating is provided by the complete system.

Ceiling Type 3 :

USG BORAL (or approved equivalent) 2HR Fire Rated Ceiling

• Board : 4 layers of USG Boral Firestop 16mm

• Suspension System :

o JayaBMS Hanger System (Bracket PN 220/221, Clip Adjuster PN


224, Rod PN 226) at 800mm max. center to center

o JayaBMS Top Cross Rail PN 202 at 800mm max. center to center

o JayaBMS Furring PN 205 at 400mm (sub system I) and 600mm


(sub system II) max. center to center

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/14
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

Suspension System for 2hr Fire Rating

Sub System I Suspension Clip PN 224 800mm C/C

Top Cross Rail PN 202 800mm C/C

Furring Channel PN 205 400mm C/C

2 layers of USG Boral Firestop 16mm -

Sub System II Direct Fixed Clip PN 219 800mm C/C

Furring Channel PN 205 600mm C/C

2 layers of USG Boral Firestop 16mm -

• Weight : 54kg/m2

• Location : As specified in Finishes Key Plan Series

• Access Panel (minimum 600mm x 600mm) to specialist’s detail, location &


provision to MEP requirement, detail to Architect’s approval

Ceiling Type 4 :

USG BORAL (or approved equivalent) 1HR Fire Rated Ceiling

• Board : 2 layers of USG Boral Firestop 16mm

• Suspension System :

o JayaBMS Hanger System (Bracket PN 220/221, Clip Adjuster PN


224, Rod PN 226) at 900mm max. center to center

o JayaBMS Top Cross Rail PN 202 at 900mm max. center to center

o JayaBMS Furring PN 205 at 400mm (sub system I) and 600mm


(sub system II) max. center to center

Suspension System for 1hr Fire Rating

Sub System Suspension Clip PN 224 900mm C/C

Top Cross Rail PN 202 900mm C/C

Furring Channel PN 205 400mm C/C

2 layers of USG Boral Firestop 16mm -

• Weight : 28.2kg/m2

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/15
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

• Location : As specified in Finishes Key Plan Series

• Access Panel (minimum 600mm x 600mm) to specialist’s detail, location &


provision to MEP requirement, detail to Architect’s approval

2.7.5 Skim Coat to Exposed Slab Soffit

[Applicable to proposed Ceiling Type 6]

Use premixed plastering compound to achieve level surface on the soffit of RC slabs
and beams where there is no suspended ceiling. Completed skim coat surface shall be
suitable to receive paint. Use proprietary edge beading to all corners and edges.

a) Material

Use pre packed plastering compound conforming to BS 1191 and consisting


mainly of gypsum with chemical additives. When accepted by Architect includes
aggregates and/or fibres for added adhesion and bulk. Unless otherwise agreed
apply one finishing coat 3mm thick plaster conforming to BS 1191 class C & D.

b) Fire Performance

Where fire performance is indicated in drawings, use only non-flammable and


non-fire hazardous pre packed plaster.

2.7.6 Semi-Concealed 1200 x 600 mm resin-bonded glass fibre ceiling

The suspended resin-bonded glass fibre acoustic ceiling board ceiling shall be semi-
concealed system. The ceiling boards shall be of 1200 x 600 x 20mm thick high
density (120kg/m3) resin-bonded glass fibre.

The boards must be able to withstand continuous exposure to high humidity without
causing visible sagging, warping or de-lamination under our extreme local conditions.

The visible surfaces and edges of the ceiling boards shall be factory painted finish in
White (F157) colour. The painted surface shall be partly porous giving good air
permeability for excellent sound absorption properties. The back of the boards shall
be faced with glass tissue.

When necessary, the surface of the boards can be easily cleaned using vacuum
cleaner, dry cloth or damp sponge.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/16
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

a) Acoustic Performance

The sound absorption coefficient shall be in conformance with ISO 354 and are
measured as follows:

20mm thick boards with 200mm air gap

Absorptive Boards with 200mm Air Gap

Frequency 125 250 500 1000 2000 4000


(Hz)

Absorption 0.41 0.59 0.66 0.62 0.76 0.64


Coefficient
Noise Reduction Coefficient (NRC) is 0.65

b) Fire Characteristics

The ceiling boards shall achieve Class 0 (zero) rating tested in accordance
with BS 476: Part 6 & 7; or Surface Burning Characteristics of Maximum
25/450 flame spread/smoke developed index when tested in accordance with
ASTM E 84.

c) Suspension System

The suspension system shall be standard 15/24mm T-grid hot dip galvanised
steel or galvanised steel finish with pre-coated low sheen white colour capping
and shall be supported by 12/14 gauge hanger wires or other equal and
approved suspension system.

d) Installation System

The suspended ceiling boards shall be installed by suspending on T-grid for


edge profiles S/R2/R4 or fine-line true grid system for edge profile R5 or
fastening them directly on the back of the ceiling with glue, box slats or
mechanical fasteners for edge profiles S/R1.

e) Perimeter Trim

Provide and fix 14 x 10 x 10 x 20 x 3000mm long aluminium shadow line W-


angle trim and edge trim at wall junctions. Provide 14 x 40mm aluminium L-
angle trims where abutting walls are curved in plan.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/17
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

f) Accessibility

Provide 100% accessibility to the ceiling space.

g) Installation

Examine the substrate and conditions under which work of this section will be
performed. Do not proceed until conditions detrimental to timely and proper
completion of the work have been rectified.

The ceiling grid shall be set out as indicated on the Drawings.

Confirm the positions of all exposed building services e.g. light fittings, fire
protection systems, speakers, air supply and exhaust grilles etc prior to setting
out the ceiling grid.

Confirm the temporary openings to be left for installation or commissioning of


equipment or the running of cables by trades or services not directly employed
within the scope of this Contract, prior to laying any panels.

Work shall be done by competent experienced tradesmen in the fixing of


suspended ceilings. The Contractor shall furnish the Architect with evidence of
experience and skill of his tradesmen before work is commenced.

The ceiling panels shall be stored for at least 24 hours before installation in the
rooms in which they are to be installed to allow for temperature adjustment.

The relative humidity of the area to be installed shall not exceed 90%.

Ceiling panels shall be neatly and accurately cut. Panels shall be placed to fit
snugly into the main and cross tees, with no space between the bottom of the
panels and the grid system, and without gaps or panel edges showing in the
completed installation

2.8 INDEMNITY FOR CEILING WORKS

Prior to commencement of ceiling works, the Contractor shall lodge with the
Architect a 5-year indemnity against defects in the ceiling works.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/18
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

Under this indemnity, the Contractor will be required to make good any defects and
failure in the materials or installation and will be responsible for any consequential
loss attributable to any failure in the ceiling works during the warranty period.

If in the opinion of the Contractor, the Specifications are sufficient for him to give the
specified indemnity then the Contractor shall allow in his tender for upgrading the
Specifications as necessary to enable him to so indemnify.

2.9 RECESSED OPENINGS

Where a/c diffuser grilles, return air grilles and recessed light fittings etc, occurs,
provide recessed opening in suspended ceilings including all additional frames to
suit. These shall be included in the rates for the ceiling.

2.10 CO-ORDINATION AND CEILING PROGRAMMING SCHEDULE

The Contractor shall co-ordinate with the ceiling specialist to ensure that the installed
suspended ceilings are not unnecessarily taken down, altered or damaged due to the
omission of work in the ceiling space.

The contractor shall verify all measurements and dimensions at the job site and shall
co-ordinate and schedule his work with the work of other specialist contractors
affected by his installation, with particular attention to the Mechanical and Electrical
Trades.

It will be the contractor’s responsibility to ascertain actual dimension on site and to


obtain complete information regarding the exact position of all items that occur in the
ceiling which are installed by other specialist contractors prior to the installation of the
ceiling.

2.11 ACCESS PANEL/ INSPECTION HATCH

All access panels and inspection hatches shall be constructed by the Contractor as
required by the Architect/MEP drawings. Access panels/inspection hatches shall
have approved framing, ironmongeries and finished with matching colour of the
whole ceiling.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/19
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

• Access Panel (minimum 600mm x 600mm) to specialist’s detail, location &


provision to MEP requirement, detail to Architect’s approval

2.12 PROTECTION / DELIVERY / STORAGE

All ceiling panels to be covered by a foil protecting them during delivery, unpacking
and installation.

Ceiling panels and all components of the suspension system shall be delivered to the
job site in the original packages of the manufacturer.

All material shall be stored in dry areas where the temperature and humidity will be
maintained during the building occupancy.

2.13 INSTALLATION

Installation shall be performed by skilled installers following the manufacturer’s


printed installation instruction.

The installer must examine the conditions under which the ceiling work is to be
performed and notify the contractor of any unsatisfactory conditions before
proceeding.

2.14 CLEANING AND PROTECTION

The Contractor shall maintain and provide sufficient protection for the completed
ceiling until handing over at completion. Until such time the Contractor shall be
responsible for and shall replace and/or make good any soils, dents or defacements
to the finished work at his own cost.

2.15 MAINTENANCE & SPARES

The Contractor shall provide spares of the following quantity or rounded up to the
closest (higher) whole number :

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/20
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

a. 5% spares of each of the ceiling type used in the project for maintenance
stock

b. 2% of exposed suspension system components.

Material should be delivered in manufacturer’s standard packages clearly marked with


the contents.

2.16 METAL CEILING PANELS

2.16.1 The metal ceiling panels to be used within corridors & specified areas are to be
Hunter Douglas Lay-in Panels or any other approved equivalent.

2.16.2 Specifications

The panels are simply laid on the exposed suspension grid system, allowing simple
and easy access to the plenum. This is especially useful for areas that require
frequent maintenance.

Material 0.5 - 0.8mm thick aluminium plate.


Surface Finish PVF2
Dimension 575mm x 575mm; 585mm x 585mm (otherwise stated by
Architect)
Colour White and other colours to be approved by the Architect

[Refer Design drawings where applicable]

2.16.3 Perforation

Panels are either plain or perforated.


The standard perforation is 1.8mm dia. holes on 3.3 mm diagonal square pattern
giving a 19% open area. Open area perforated shall comply with M&E requirements.

2.16.4 Sound Absorption

The back of the perforated panels come with acoustic material, SOUNDTEX C 1986
S/W. This material is non-flammable and meets the requirement of building material
class B1. This material has been approved by British (BS) and European (EN)
standards.

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/21
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

SOUNDTEX acoustic non-woven C 1986, in conjunction with perforated steel sheet


panels, has been tested for its sound absorption performance by The Building Test
Centre in East Leake, Loughborough, UK under the report numbers BTC 3327 A to
BTC 3329 A. In accordance with BS EN 20 354 : 1993 (ISO 354 : 1985) on 10th
September 1997.

The Noise Reduction Coefficient (NRC) was calculated in accordance with ASTM
C423-90a. The degree of Sound Absorption was determined as follows for three
perforation patterns with a ceiling cavity of 400mm.

Curve 1 1.8mm diameter holes with 20% open area


Curve 2 1.6mm diameter holes with 25% open area
Curve 3 2.5mm diameter holes with 16% open area

2.16.5 Fire Resistance

Ceiling panels shall be tested by PSB in accordance with British Standard 476, Pt 6 :
1989 "method of test for Fire Propagation for products" and BS 476, Pt : 1997 on
Flame Spread. They also meet the stringent requirements of Class O fire rating, or
equivalent local Authority/ Code requirements and FM Global Standards.
Alternatively, Surface Burning Characteristics of Maximum 25/450 flame
spread/smoke developed index when tested in accordance with ASTM E 84.

2.16.6 The Suspension System

All main and cross carriers as well as brackets and clips are made of galvanized
steel.
Rod Hanger 4mm hanger with adjustable clip.
Angle Aluminium capping wall angle or painted steel wall angle.
Size 24mm x 24mm

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.
JKT02 SS2/22
MARCH 2022 ISSUED FOR CONSTRUCTION SECTION 2 - SUSPENDED CEILING

2.16.7 Code Compliance

Contractor is to ensure that the acoustic and other relevant qualities meet the client’s
requirements and Architect’s approval. The ceiling panels are to comply with Local
Code requirements and FM Global Standards.

2.16.8 Packing

Each panel is protected by an individual plastic cover. Each carton box contains 20
panels

2.17 SEISMIC DESIGN & ANALYSIS FOR CEILING GRID SYSTEM

Seismic design to specialist’s design & detail shall be included and provided as a
part of the Suspended Ceiling Grid system. In order to prevent damage and
reduce the risk of damage caused by within Data Hall/ critical M&E Room areas
(where applicable).

Seismic Design requirements shall be completed and comply with the following:


The seismic restraints for the ceiling system shall be designed using ASCE 7
Chapter 13 or SNI1726 Chapter 9.
• The development is specified as Risk Category III (RC III).
• Soil class D at site location
• The peak ground acceleration, PGAM, shall be considered as 0.358g for the
project.
• The ground motion (0.2s), SS, shall be considered as 0.729g.
• The ground motion (1.0s), S1, shall be considered as 0.302g.
• The short period spectral acceleration co-efficient, SDS, shall be considered as
0.591g for the project.
• The spectral response acceleration parameter at 1 second, SD1, shall be
considered as 0.403g for the project.
Seismic design, assessment & analysis (incl. necessary drawings, calculations,
simulation, etc) shall be submitted for Structural Engineer’s or Seismic Consultant’s
review & approval, prior fabrication & installation on Site.

Seismic design (design intent)


[Design, installation details & provision subject to final assessment reviewed by
Structural Engineer’s or Seismic Consultant’s in due course].

The following components/ systems shall be included, but not limited to:

i. Bracing system with seismic cable, brackets, fasteners, etc.


ii. Rod hangers and/or stiffeners

COPYRIGHT BY M/S AWP PTE LTD. THIS SPECIFICATION IS THE PROPERTY OF M/S AWP PTE LTD AND CANNOT BE COPIED, REPRODUCED PARTLY OR
WHOLLY WITHOUT THE WRITTEN PERMISSION OF M/S AWP PTE LTD.

You might also like