Professional Documents
Culture Documents
T308-08 Hardware Troubleshooting
T308-08 Hardware Troubleshooting
TABLE OF CONTENTS
Chapter 8 - 1
T308-08 Hardware Troubleshooting - RevC
8.1.1 Objectives
On completion of this chapter you will be able to:
• Analyze the hardware status
• Check and force I/O signals
• Exchange hardware units
• Check the power supervision
8.1.2 Legend
> Indicates when you go from one menu to a sub-menu
Italic Indicates object and file names
“ “ Indicates dialog box buttons, tabs, menus etc.
Bold Indicates important topics
Indicates start/explanation of student activity
Chapter 8 - 2
System 800xA training
Error
Warning
Warnings are events that are considered to be less serious than errors. Analog input
overflow or underflow or forced IO channels are examples of hardware warnings.
Error
Warning
The errors and warnings in CBM are always transported upwards to the top hardware
container, so that they are visible even if the hardware structure is collapsed.
Chapter 8 - 3
T308-08 Hardware Troubleshooting - RevC
Chapter 8 - 4
System 800xA training
Chapter 8 - 5
T308-08 Hardware Troubleshooting - RevC
Error Warning OK
Chapter 8 - 6
System 800xA training
Chapter 8 - 7
T308-08 Hardware Troubleshooting - RevC
To trace a hardware error from the alarm list to CBM, just right click the alarm and
select Project Explorer:
Chapter 8 - 8
System 800xA training
When the hardware was reinstalled, the alarm list shows you Status cleared.
Chapter 8 - 9
T308-08 Hardware Troubleshooting - RevC
Replace IO Module
What IOs are not working? Connect Module bus
Chapter 8 - 10
System 800xA training
Chapter 8 - 11
T308-08 Hardware Troubleshooting - RevC
3. Left click the appropriate channel in Forced column and the Channel Value will
change color to yellow. The channel value can then be written to with either a ‘1
or 0’ to turn the Output on or off. The .IO Value and Forced components of the
variable are affected, which is reflected in the Status word.
4. To release the Force condition and return to normal operation, left click on the X
in the forced column.
Chapter 8 - 12
System 800xA training
Chapter 8 - 13
T308-08 Hardware Troubleshooting - RevC
1. Remove power from the controller, and ensure all the indicator lights are
extinguished.
2. Release the two captive screws and withdraw the unit.
Captive
Screws
3. The CPU can then be pulled from its base. Replace by carefully inserting the CPU
in the base plate and tightening the captive screws.
4. Restore power.
5. Setup the correct IP address & upgrade the firmware to ensure correct operation.
6. Download your application.
Chapter 8 - 14
System 800xA training
4. Slide the units apart until the unit to be changed has its buses clear of the adjacent
units.
5. Turn the locking device to the OPEN position (1) and remove the base from the
DIN rail.
6. Replace the unit, turn the locking device to the SLIDE position (2) and slide all
the units back together.
7. Turn the locking device to the LOCKED position (3) and restore power.
Chapter 8 - 15
T308-08 Hardware Troubleshooting - RevC
Captive
Screws
Chapter 8 - 16
System 800xA training
In order to change the unit, unscrew the captive screw and withdraw the unit. Gently
insert the replacement module and tighten the screw.
NOTE! It is not allowed to manipulate CEX bus base plates in a
powered and running system. Before changing or
removing a base plate, all CEX modules on that segment
must be removed.
If it is required to change the base, then power must be removed. Use the technique
described earlier to replace the base.
Chapter 8 - 17
T308-08 Hardware Troubleshooting - RevC
Chapter 8 - 18
System 800xA training
2. Choose the setting “User defined: Select COM-Port and speed manually” and
press the button “Next”.
3. Select the COM-Port to be used and type in the path to the image-file.
Chapter 8 - 19
T308-08 Hardware Troubleshooting - RevC
4. Check the box “Disable optimization of speed (Fix to 9600 BD)” and uncheck the
remaining check boxes. Press the button “Download”.
Chapter 8 - 20
System 800xA training
Rotate plastic
switch
2. The green run light will be extinguished and the red fault light will be lit,
indicating that the module is disabled. The module can then be lifted vertically
from the base.
3. On the base there are 2 six position rotary keys marked A - F. Check that the new
module corresponds to the settings of the base. (You may have the wrong
module). The diagram below shows the position of the keys in the compact and
standard TUs.
Keys
4. Carefully push the replacement module into the base. When it is seated the red
fault light should be on.
5. Rotate the rotary switch clockwise through 900 at which point the Red Fault LED
should extinguish and the green (R)un LED light.
Chapter 8 - 21
T308-08 Hardware Troubleshooting - RevC
Locking
tabs
DIN Rail
Release Tabs
3. Locate the locking tab just below the module bus connection and using a thin
screwdriver, gently push down to release the tab and ease the units apart. When
the faulty TU has been mechanically isolated on both sides, using a screwdriver,
pull down on the DIN rail tab to release the TU.
4. Insert the replacement TU by first hooking on the top of the DIN rail, then pulling
down the release tab ease the TU onto the bottom of the DIN rail.
5. Slide the TUs together to reconnect the module bus. Insert the module into the TU
and reapply power. Rotate the rotary switch clockwise through 900 at which point
the Red Fault LED should extinguish and the green (R)un LED light.
Chapter 8 - 22
System 800xA training
4. Ease the modules apart until the module bus connection is clear.
5. Turn the locking device of the unit to be removed to open, and remove the module
from the DIN rail.
6. Replace the module, slide the units back together and turn all locking devices to
the locked position.
7. Replace the field wiring terminal blocks.
8. Reapply power.
Chapter 8 - 23
T308-08 Hardware Troubleshooting - RevC
8.7 Logs
All crash dumps saved in the controller log are translated. You can read all other
information, such as warning printouts, module type, firmware version, etc.
All I/O units are written to the controller log when a hardware configuration is
downloaded. When an I/O module is removed and replaced on line, the event(s) are
written to the controller log. Time stamp, hardware position, I/O unit type and Product
Revision are written to the controller log file as well.
The file is also located on the hard drive in the Control Builder Log Files folder. The
Controller log is fetched from the controller ONLY when asked via the Remote
System tool.
Chapter 8 - 24
System 800xA training
When the controller log is displayed to the user, it is shown in a text editor, such as
Notepad.
Chapter 8 - 25
T308-08 Hardware Troubleshooting - RevC
AC 800M Controllers
For detailed information about power supervision wiring please refer to chapter
AC800M Hardware. If redundant 24V power supplies are used, then one power supply
should be connected to SA, the other to SB.
Chapter 8 - 26
System 800xA training
Fuses for
Modulebus and
CEX-bus
CPU Baseplate
Modulebus fuse
When the modulebus fuse is broken, only the Analog Output modules lose power,
while the AI, DI, DO modules are still working.
Chapter 8 - 27
T308-08 Hardware Troubleshooting - RevC
CEX-bus fuse
When the CEX-bus fuse is broken, all Communication Interface modules on the CEX-
bus lose power. There is no communication between CPU and any CI module, while
the IO modules on the Modulebus are still working.
Chapter 8 - 28