Professional Documents
Culture Documents
Appendix C - Example Building EB1 DBR
Appendix C - Example Building EB1 DBR
Table of Contents
S.NO. DESCRIPTION PAGE NO.
The plan shape of the building is rectangular as shown in figure 1, with a length and
width of about 100m x 34m. Service core is placed in the center embraced by office
wings on either side.
The floor to floor height is proposed as 3.9m in the office floors, 3.5m at the stilt level
and 4m in the basement. Double height columns are proposed at the entrance lobby.
The elevation of example building 1 is shown in Figure 2. The height of the building is
about 54m above ground.
100m
34m
13th floor
12th floor
11th floor
10th floor
9th floor
8th floor Shear
54m
6th floor
Floor
5th floor System
4th floor
3rd floor
Columns
2nd floor
1st floor
Stilt floor
Basement
Foundation
Figure 2: Elevation of example building 1
2 Structural system
One of the most important and desirable attributes for any office building is the
flexibility in interior planning of space, and the column and grid spacing as well as the
structural system has been decided in consideration of this.
Columns are spaced at 11m as indicated in the architectural drawings in the office
space for effective and efficient interior space planning as well as efficient car parking
in the stilt. In central service area, the columns are positioned at lower spacings, as
indicated in the architectural drawings.
The floor system is proposed to be a combination of post-tensioned flat slab system and
conventional beam and slab system supported by RC walls and columns.
The post tensioned flat slab system is proposed in the office spaces where 11m spans
are required.
2
Toilet areas shall be sunk by 100 mm to achieve slopes in these spaces and to maintain
a level difference of 15mm between office space and toilet space.
The lateral load resisting system of the building is proposed using reinforced concrete
shear walls located at the elevator and staircase cores. Locating walls in these cores
provides the required fire resistance to these spaces, while also resisting in a very
efficient lateral load resisting system due to interconnectivity of the walls.
3 Design loads
The self-weight of the various elements is computed based on the unit weight of
materials as given below:
Normal weight aggregates shall be considered for arriving at self-weight of all concrete
works.
The super imposed loads that are envisaged to act permanently (wherever applicable)
are as following: -
* Floor finish load due to tile (10mm thick), bedding mortar (25mm thick) and 40mm
thick screed.
** The Weatherproof course consists of the following:
*** In office areas only. In the central utility space actual partition loads shall be
calculated and used in the analysis and design.
Live loads are assessed based on the occupancy classifications as per IS: 875 (Part
2) – 1987, and are listed as follows: -
Pantry
3.0 4.5
Mail room
4.0 4.5
House keeping
4.0 4.5
The wind pressure shall be calculated based on the data furnished below and other
provisions laid in IS: 875 (Part 3) – 2015.
The loading due to earthquake is assessed based on the provisions of IS: 1893 – 2016.
Chennai is considered as Seismic zone – III as per IS: 1893- 2016 and this is used to
determine the earthquake loads on the building.
Ductile detailing of reinforced concrete elements is considered as per IS: 13920 –2016.
4 Load combinations
The various loads shall be combined in accordance with table 18 of IS 456. Whichever
The following abbreviations are used in the load combination tables below
DL - Dead load
SDL - Super imposed dead load
LL - Live load
WL - Wind load
EL - Earthquake load
WP - Water Pressure
Combination Remark
1.5DL + 1.5 SDL + 1.5LL Basic gravity system
1.5DL +/- 1.5EQ Mostly governs lateral system design for seismic
loads
1.5DL +/- 1.5WL Wind load combo, mostly governs for wind load
design
0.9DL +/- 1.5EQ Columns in tension and foundations; governs for
axially loaded elements that are below balance
point
0.9DL +/- 1.5WL Columns in tension and foundations; governs for
axially loaded elements that are below balance
point
1.2DL + 1.2LL +/- 1.2EQ Normally does not govern
4.2 Load combinations for serviceability limit state and foundation systems
Combination Remark
DL+ LL Basic gravity system
DL +/- EQ Mostly governs lateral system design for seismic
loads
DL +/- WL Wind load combo, mostly governs for wind load
design
DL + 0.5LL +/- 0.5EQ Normally does not govern
DL + 0.5LL +/- 0.5WL Normally does not govern
6 Design life
7 Design Standards
The relevant Indian Standard codes, as given below, shall be followed for structural
design:
13. IS: 800 – 2007 Code of Practice for General Construction in Steel
8 Design methodology
All R.C.C structures shall be designed according to the limit state method as specified
in IS: 456 – 2000. Prestressed concrete structures shall be designed as per IS: 1343
–2012. Steel structures, if any, shall be designed as per IS: 800 – 2007.
9 Materials
9.1 Concrete
The following concrete grades are used in the design of various reinforced concrete
components:
Component Grade
Slabs and beams M40
Columns and Walls (Foundation - L7) M50
Columns and Walls (L7 - terrace) M40
Footing M30
9.2 Reinforcement
* In post-tensioned work, where tendons are used, the minimum clear cover from sheathing/duct shall
be at least 30 mm or the size of the tendon whichever is bigger.
11 Serviceability requirements
11.1 Drift
Following limitations are considered for drifts under wind and earthquake loads:
11.2 Deflection
The following limiting crack widths are considered for various members
12 Analysis methods
3D analysis of the building is carried out using ETABS V16 and SAFEV14 software
packages.
10