Chapter 5

FCU Selection
Example for selection Diffuser
Room in forth floor : nursing room (NRM-04-02)

No of diffuser= 1
Required flow rate= 188 cfm

We depend on selection by AL-ANDALOSIA FOR AIR OUTLETS


Chapter 5
FCU Selection
Chapter 5
FCU Selection

We choose the number closest to 188 cfm and It is located in the


green area is (224 cfm) size (9"*9")
Chapter 5
FCU Selection
Example for selection Grill
Room in forth floor : patient room (PRM-04-01)

No of Grill= 1
Required flow rate= 639 cfm

We depend on selection by ZAMZAM ENGINEERING INDUSTRIES


Chapter 5
FCU Selection

We choose the number closest to 639 cfm , Sound level less than
30 so outlet velocity 600-700 FPM and It is located in the white area
Is (30 width and 8 height)