Q2. Design a lighting installation for an office with L=20m; W=12m and 3.25m height to
maintain an E=500lx±5% on a horizontal working plane of 0.75m, using ceiling maintained
fluorescent luminaires of 0.85 lm/W lamp efficacy. The reflectance of the ceiling, walls and
floor are 0.8, 0.6 and 0.15 respectively. Assume SHR=1, MF=0.8. The required utilization
factors are given in the table below. [5]
ρcc% 80 70 50 30
ρwc% 70 50 30 70 50 30 50 30 10 50 30 10
RI ρfc= 20%
2.00 0.68 0.62 0.57 0.67 0.61 0.56 0.59 0.55 0.51 0.57 0.53 0.51
2.50 0.74 0.69 0.65 0.72 0.68 0.64 0.65 0.62 0.60 0.63 0.60 0.58
3.00 0.75 0.70 0.67 0.73 0.70 0.66 0.67 0.64 0.62 0.64 0.62 0.60
4.00 0.78 0.74 0.71 0.76 0.73 0.69 0.70 0.67 0.65 0.67 0.65 0.63
h=10m θ
Figure 1
Kerb=2.0m
Good luck
M
Road w=22m