Professional Documents
Culture Documents
Aps2006 Rev0
Aps2006 Rev0
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
ENGINEERING PROCEDURE
APS-2006
Anti-Surge
SVI-IIAP Configuration & Set-up
Asymmetrical Single Acting Actuation
TABLE OF CONTENTS
1) SCOPE
2) SEQUENCE OF OPERATIONS
3) ACTUATOR ASSEMBLY
4) VALVE ASSEMBLY
5) POSITIONER CONFIGURATION
7) POSITIONER CALIBRATION
10) DOCUMENTATION
10) PACKAGING
APS-2006 Rev. 0
Page 1 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
1.0 SCOPE
This procedure details the operations involved and sequence of operations in the configuration, set-up and calibration
of a Masoneilan SVI-IIAP Smart Valve positioner for Anti-Surge control applications with spring return actuators in a
asymmetrical response configuration. Opening, closing times and over-shoot will be measured and evaluated in
compliance to Solar Turbines Specification requirements and “Source Control Drawing” compliance. This procedure
does not cover the performance testing of the over-ride system (Solenoid) in an open loop state.
APS-2006 Rev. 0
Page 2 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
APS-2006 Rev. 0
Page 3 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
a) Fully close needle valve (Feedback/bypass valve), then open (Counter-clock wise) 3 full turns or 50% of it’s
rated capacity (Cv).
APS-2006 Rev. 0
Page 4 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
SOLENOID VALVE
With the valve command at 20 ma, removal of power from the solenoid, shall cause the valve to reach 63.2% of full open in
less than 100 + 100(port size in inches)0.5 milliseconds.
POSITIONER
With a step change from 20 to 12 ma, the valve shall reach 50% open in less than 300 + 100(port size in inches)0.5
milliseconds (maximum half opening time).
OVERSHOOT
The valve shall not overshoot its ultimate destination by more than 60%. Responding to the 20 – 12 ma step change above,
the valve shall have a maximum excursion not to exceed 80% open.
After the overshoot the valve shall return to it’s ultimate position (50% open) in less than 10 times its maximum half opening
time.
OVERSHOOT AREA
The following reduces the area bounded by the preceding two limits by half. This is done by limiting overshoot to an area
beyond the ultimate travel destination (overshoot triangle).
The area beyond the ultimate destination (overshoot triangle) shall be less than 1.5 where:
Area = B*H/2.
Example: A 4” valve, 4.375” port, at maximum overshoot, must return to its ultimate destination in 5.09
seconds.
Example: A 4” valve, 4.375” port, at maximum recovery time, must have no more than 15% overshoot.
If there is a second "ring" returning from the overshoot, it shall not exceed 2.5% of the total valve travel.
Valve minimum resolvable position (stick & slip) shall not exceed 2% of the total travel.
APS-2006 Rev. 0
Page 5 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
b) Using Valvue2.X perform a “Step Test” with the following user testing criteria:
1) Start Position (%): 0
2) Stop Position (%): 50
3) Time (s): 5
4) Sample Rate (Samples/s) : 20
5) Step Size (%): 50
6) One Way (Direction to Open)
This test will provide a graph and analyzed test results which identify T86 or stroking speed to reach 50% of
valve stroke including “Overshoot”.
APS-2006 Rev. 0
Page 6 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
The graph can be analyzed to determine “Dead Time” or sometimes define as “Microprocessor execution”
including “pneumatic lag” and “mechanical response”.
On the sample below, the “Dead Time” is calculated @ 100 milliseconds, “Step Response Test Results” can
be access by selecting “Show Diagnostics Info” icon.
APS-2006 Rev. 0
Page 7 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
a) Using Valvue2.X perform a “Step Test” with the following user testing criteria:
7) Start Position (%): 0
8) Stop Position (%): 100
9) Time (s): 5
10) Sample Rate (Samples/s) : 20
11) Step Size (%): 50
12) Two Way (Both directions)
Step Response Test parameters for 0 to 100% and 100% to 0 of valve stroke
APS-2006 Rev. 0
Page 8 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
The graph can be analyzed to determine “Dead Time” or sometimes define as “Microprocessor execution” including
“pneumatic lag” and “mechanical response”.
On the sample below, the “Dead Time” is calculated @ 100 milliseconds, full stroking speed is reach in 2
seconds. “Step Response Test Results” can be access by selecting “Show Diagnostics Info” icon.
APS-2006 Rev. 0
Page 9 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
10. DOCUMENTATION
For the purpose of documentation, as a minimum using Valvue 2.X, a “Dump File” should be save after all
configuration and final tuning is achieve along with a performance report which is also created by Valvue 2.x.
11. PACKAGING
After completion of testing the complete assembly shall be sealed to protect the end connections and maintain
cleanliness during shipment. End connections should be protected to prevent shipment damage.
.
ENGINEERING _______________________________________
Copyright 2006 as an unpublished trade secret. This document and all information herein is the property of Dresser Inc. It is confidential and must
not be made public or copied and is subject to return upon demand.
APS-2006 Rev. 0
Page 10 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
APS-2006 Rev. 0
Page 11 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
APS-2006 Rev. 0
Page 12 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
APS-2006 Rev. 0
Page 13 of 14
® DRESSER INC.
Masoneilan
1250 Hall Court.• Deer Park , Texas • 281-884-1000 • Fax 281-884-1074
A C
B
Calibration Manual Positioning
Configuration 1 Mode: Setup 1 Valve Position X.X %
1 Reset Basic Config and Cal Defaults 2 Change Mode 2 Full Open
**Device Setup **
2 General 3 Valve Travel 3 Full Close
1 Mode Normal/Manual/Setup
3 Actuator Type 4 Manual Position 4 Set Position
2 Change Mode Set Mode Target
1 Normal 4 Positioning 5 Valve Tuning Data
3 Setup Wizard Sensors
2 Manual 5 Limits/Shutoff 6 Sensors
4 Manual Setup
6 Alarms Setup 7 Reset Cal Factory Defaults 1 Input Current Sensor
5 Configuration B 3 Setup
2 Pressure Sensor
7 Switches
6 Calibration C
7 Commissioning Services 8 HART Enter Value (mA)
Valve Travel Low Range
D 9 Device Info 1 Mode: Setup
2 Change Mode High Range
Air Action Configuration
1 Skip This Task 3 Find Stops Open Stop Adjustment
2 Select Air Action General 4 Open Stop Adjustment
Enter Value XX.XX %
Manual Setup Are you sure? 1 Tag : 5 Manual Stops
1 Mode Setup Select Air Action 2 Descriptor 6 Autotune
ABORT Set Manual Stops
2 Reset Basic Configuration Air To Close 3 Message 7 Manual Tuning
OK
3 Configure Wizard Air To Open 4 Date 1 Low
5 Final Asmbly Nbr P 2 High
4 Find Stops
5 Auto Tune 6 LCD Language I 3 Exit
7 Local Buttons
Find Valve Stops D
8 Pressure Units Aggressiveness Level
1 Skip This Task
9 switch positions DEL
Allow Override Limits 2 Run Find Stops Padj
ABORT
Enabled Beta ENTER
Disabled Actuator Type
1 Air Action : ATO/ATC Stroke Time -9 to +9
Auto Tune
1 Skip This Task 2 Type : Single/Double 0 Normal Tuning
Compens. pos
Select Tight Shutoff 2 Run Auto Tune
Enabled Dead Zone
-9 to +9 Positioning
Disabled 1 Characterization: Linear/EQ50/EQ30/QO/Camflex Boost
0 Normal Tuning
2 Low Signal: 4.00 mA
Value 3 High Signal: 20.00 mA
XX.X 4 Bumpless Transfer: Disabled/Enabled Switches D
Reset to Factory Default 5 Allow Override Limits : Disabled/Enabled 1 DO Switch 1 Action : Commissioning Services
1 Skip This Task 6 Position Sensor: Built-in Sensor / Remote 2 DO Switch 1 Normally Open/Close
Pressure Units 2 Set All Values to Default 1 Mode : Setup
7 Custom and/or Standard Characterization : 3 DO Switch 2 Action:
psi 2 Input Signal: XX.XX mA
4 DO Switch 2 Normally Open/Close 3 Valve Position X.X %
bar Select Cam
kPa 4 Basic Info
Warning Linear HART 5 Manual Position
ABORT Equal % (30) 1 Poll Addr : 0 (Typical) 6 Position Retransmit
OK Equal % (50) 7 Run Diagnostics
Display Language 2 Nbr Of Preambles: 5 (Typical)
Quick Open 3 Phys Sign Code : Bell 202 Current
English Custom 8 Switches
French Please wait 4 Device Flags : 0X00
Camflex-Equal %
ABORT 5 Burst Mode; Off/On
6 Burst Command : CMD 3 **NORMAL MODE **
OK 1 Mode : Normal
Button Lock Level Limits/Shutoff
1 Position Limit Low : Disabled/Enabled Device Info 2 Input Signal : X.XX (mA )
All Enabled Aggressiveness Level 2 Low Limit : 0.0 % (Typical) 3 Valve Position: XX.X (% )
No Config/Cal Manufacturer
DEL 3 Position Limit High: Disabled/Enabled 4 Manual Setpoint: XX.X (%)
No Manual ABORT 4 Limit High : 100.00 % (Typical) Model 5 Read Pressures
Locked ENTER 5 Tight Shutoff: Disabled/Enabled 6 Device Setup A
Device ID
6 Tight Shutoff Value: XX.X % (Signal) 7 Status/Diagnostics
375 Handheld Select Air Action Universal Cmd Rev
Communicator Air To Close -9 to +9
Air To Open 0 Normal Tuning Alarms Setup Hardware Rev
Guide for SVI-IIAP 1 Near Close Value : Value XX.X %
** Read Pressures**
Trans Cmd Rev 1 Pressure Unit psi
Firmware 3.11 2 Pos Error : Disabled/Enabled 2 Actuator Pressure : X.XX
Valve Near Closed Value 3 Pos Error Band : XX.X % Software Rev
XX.X (%) A 4 Pos Error Time: XXX s
Firmware Version
APS-2006 Rev. 0
Page 14 of 14