PROJECT:

2GW WAFER & INGOT PLANT, MUNDRA, KUTCH

OWNER: MUNDRA SOLAR TECHNOLOGY LIMITED

DISTRICT KUTCH, GUJARAT, INDIA

CONTRACTOR: : INDO TECH TRANSFORMERS LIMITED

DOCUMENT NAME: Data Sheet

DOC.NO: 5063-E-EPC-PTR-DE-D-V-001 Revision - 01

PROJECT DOC. TITLE: Data Sheet

CONTRACTOR DOC. NO.: 5964 – E25 Revision -1

APPROVAL STATUS:

SS RP MMK
01 21.11.22 SS RP MMK Revised as per comments
SS RP MMK
00 04.11.22 SS RP MMK For Approval

INITIALS SIGN INITIALS SIGN INITIALS SIGN DETAILS OF REVISION


REV DATE
PREPARED CHECKED APPROVED

Categories:

 Cat-I Approved. Good for Manufacturing/Construction/Fabrication

AMIT Digitally signed


 Cat-I* Approved with minor comments. No resubmission is required.
by AMIT To be incorporated in As-Built. Good for Manufacturing/
AGRA AGRAWAL
Date: Construction/ Fabrication subject to incorporation of comments.
2022.11.28
WAL 16:04:59 +05'30'

Reviewer
 Cat-II Approved. Released for Manufacturing/fabrication/construction
subjected to incorporation of comments. Modification as
Noted. Resubmission is required.

Amit
Digitally
signed by  Cat-III Not Approved
Amit

Asha Asharfilal
Date:
2022.11.28
 Cat-IV For Information & Records

rfilal 17:54:49
Approver
+05'30' Note: “Approval of this document does not absolve the Contractor/ Supplier/
Fabricator from fulfilling Contractual obligations in any way”
SECTION-3: TECHNICAL DATA SHEETS & SCHEDULES
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 2 of 28
Cluster, Mundra

TABLE OF CONTENTS

SUBSECTION – 3.1 : TECHNICAL DATA SHEET FOR POWER TRANSFORMER AND REACTOR.....................

.................................................................... TECHNICAL DATA SHEET FOR NITROGEN INJECTION SYSTEM………


TECHNICAL DATA SHEET FOR HVIC/TRV Coating
SUBSECTION – 3.3 : PERFORMANCE GUARANTEES ................................................................................

SUBSECTION – 3.4 : DEVIATION SCHEDULE TO TECHNICAL SPECIFICATION ............................................

.............................................................................................................................................................

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 3 of 28
Cluster, Mundra

SUBSECTION – 3.1: TECHNICAL DATA SHEET FOR POWER TRANSFORMER


50 MVA 66/11.5 kV, 3-Phase Power Transformer
S.No. Description Unit TECHNICAL PARAMETERS Data (Offered)
1. Voltage ratio (Line-to-Line) kV 66/11.5 66/11.5
2. Rated capacity (HV and LV) MVA 50 50
3. No of phases 3 (Three) 3
4. Vector Group Dyn11 Dyn11
5. Type of transformer Power Transformer Power Transformer
6. Applicable Standard IEC 60076 / IS 2026 IEC 60076 / IS 2026
7. Cooling type ONAN/ONAF ONAN/ONAF
8. Rating at different cooling % 80 / 100 80% / 100%
9. Cooler Bank Arrangement 1 X 100% 1 X 100%
10. Frequency Hz 50 50
11. Tap changer
i) Type On-load tap changer (CFVV) On-load tap changer (CFVV)
ii) Tapping range and steps -15% to +5% in steps of -15% to +5% in steps of
1.25% for HV variation 1.25% for HV variation
iii) Location of tap changer On HV neutral end Electrical Middle of HV
12. HV-LV Impedance at 75 °C, at
highest MVA base
i) Max. Voltage tap % 13.2 13.2% (+/- IEC Tol)
ii) Principal tap % 12.5 12.5% (+/- IEC Tol)
iii) Min. Voltage tap % 11.8 11.8% (+/- IEC Tol)
13. Tolerance on Impedance % As per IEC As per IEC
14. Service Outdoor Outdoor
15. Duty Continuous Continuous
16. Overload Capacity IEC 60076-7 IEC 60076-7
17. Temperature rise over 50°C
ambienttemp.
i) Top oil measured by thermometer OC 45 45degC Max

ii) Average winding measured OC 50 50degC Max


by resistance method
18. Winding hot spot rise over 61 61
yearlyweighted temperature of 32
°C
19. Tank hot spot temperature 110 110

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 4 of 28
Cluster, Mundra

S.No. Description Unit TECHNICAL PARAMETERS Data (Offered)


20. Maximum design ambient OC 50 50
temperature
21. Windings
i) Lightning Impulse withstand
Voltage
HV kVp 325 325
LV kVp 75 75
LV Neutral kVp 75 75
ii) Chopped Wave Lightning Impulse
Withstand Voltage
HV kVp 358 358
LV kVp 83 83
iii) Switching Impulse withstand
Voltage
HV kVp NA NA
iv) One Minute Power Frequency
withstand Voltage
HV kVrms 140 140
LV, LV Neutral kVrms 28 28
HV Neutral kVp - -
v) Neutral Grounding (HV and LV)
HV - -
LV Resistance Grounding Resistance Grounding
vi) Insulation
HV Uniform Uniform
LV Uniform Uniform
vii) Tan delta of winding % ≤0.5% ≤0.5%
22. Bushings
i) Rated voltage
HV kV 72.5 72.5
LV, LV Neutral kV 17.5 17.5
ii) Rated current (Min.)
HV A 1250 1250
LV, LV Neutral A 3150 3150
iii) Lightning Impulse withstand

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 5 of 28
Cluster, Mundra

S.No. Description Unit TECHNICAL PARAMETERS Data (Offered)


Voltage

HV kVp 325 325


LV and LV Neutral kVp 95 95
iv) One Minute Power Frequency
withstand Voltage
HV kVrms 155 155(dry)
LV and LV Neutral kVrms 42 42(dry)
v) Tan delta of bushing at ambient % ≤ 0.5 ≤ 0.5%
Temperature
vi) Minimum total creepage distances (Specific creepage distance: 31mm/kV
31mm/kV corresponding to
the line-to-line highest system
voltage)
HV mm 2248 2248
LV and LV Neutral mm 543 543
Maximum Partial discharge level pC 10 10
at Um on HV
23. Maximum Partial discharge level pC 100 100
at 1.58*Ur/√3
Maximum Noise level at rated 70 70
voltage, at principal tap & no load
24. dB
and all cooling active
25. Maximum Permissible Losses of 80 MVA 50 MVA 31.5MVA 50MVA
Transformers
i) Max. No Load Loss at rated kW 35 25 18 25
voltageand frequency
ii) Max. Load Loss at rated current kW 200 125 110 125
and frequency and at 75°C at
principal tap between HV & LV
iii) Max. I2R Loss at rated current kW 170 105 93.5 105
and frequency and at 75°C at
principaltap between HV & LV
iv) Max. Auxiliary Loss at rated kW 5 3 2 3
voltage and frequency
Notes:
1. For parallel operation with existing similar transformer, percentage impedance, OLTC connection and range, vector
group and the winding configuration (if necessary) are to be matched.

2.No external or internal Transformers/ Reactors are to be used to achieve the specified HV/IV, HV/LV and IV/LV
impedances.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 6 of 28
Cluster, Mundra

GUARANTEED AND OTHER TECHNICAL PARTICULARS FOR POWER TRANSFORMERS (To be filled in for each type of
transformer by the manufacturer)
Sl.No. Description Unit Specified Offered by
by Buyer manufacturer
1. General Information i) Indo tech
Transformer
i) Supplier
ii) Indo tech
ii) Name of Manufacturer
Transformer
iii) Place of Manufacture (Country & City) iii) India &
iv) Type of transformer (Core/Shell) Kancheepuram
iv) Core Type
2. Applications
i) Indoor/Outdoor i) Outdoor
ii) 2wdg/3wdg/Auto ii) 2 Wdg
iii) GT/Step-down/ICT/Station Start-up/ Auxiliary/ Rail Trackside iii) Step – down
Supply
3. Corrosion Level at Site
i) Light ii) Medium iii) Heavy iv) Very Heavy Very Heavy Very Heavy

4. Site altitude above mean sea level m <1000

5. Seismic zone and ground acceleration at site (both in horizontal & As per Zone V
verticaldirection)
6. Maximum and minimum ambient temperature at site 47.8 Deg °C &
-1.1Deg °C
7. Applicable Standards Applicable
Standards
i) IEC: 60076
IEC: 60076 /
ii) IS : 2026
IS: 2026
iii) Any other, please specify

8. Rated Capacity / Full load rating (HV/IV/LV) MVA 50


9. 3-Phase/Bank of Three Single Phase (A, B, C) 3-Phase
10. Rated No Load Voltages (HV/IV/LV) kV 66/11.5
11. Currents at normal tap (HV/IV/LV) Amp HV - 437.38 A
LV - 2510.2 A
12. Rated Frequency Hz 50
13. Connections and phase displacement symbols (Vector Group) Dyn11
14. Weight Schedules (Minimum with no negative tolerance) (Approx Weights)
i) Active part (Core + coil) kg 43600
ii) Insulating Oil (excluding mass of extra oil) kg R1 16150
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 7 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
iii) Tank and Fittings kg 20000
iii) Total weight kg R1 79750
iv) Transportation Weight kg 69500
v) Overall dimensions L x B x H mm 8000 x 6100 x
R1 6000 Approx
vi) Size of heaviest package L x B x H mm 6350 x 2600 x
3850 Approx
vii) Weight of heaviest package kg 69500 Approx
R1
viii) Weight of 5% extra oil kg 780 Approx

ix) Weight of core Kg 26000 Approx


R1
x) Weight of copper (HV/IV/LV/ Regulating) kg HV:6550 LV:4200
Reg:1600 Approx
R1 (with winding
insulation)
xi) Insulating Oil volume (excluding 5% extra oil) Ltrs R1 18145 Approx

xii) Quantity of oil in OLTC Ltrs 185 Approx

15. Transport limitation LXWX 6350 x 2600 x


H 3850 Approx
16. LV Winding
i) Stabilizing tertiary (Yes/No) Not applicable
ii) Loaded (Yes/No)
17. Tappings i) OLTC – Easun
MR Make
i)Type (OLTC/OCTC) and make of tap changer
ii) Electrically
ii)Position of Tapping on the winding
Middle/line end
iii)Variation on
iii) HV for HV
iv)Range of variation %
iv)+5% to -15% @
v)No. of Steps 1.25%
vi) Whether control suitable for: v)16 Steps
• Remote/local operation vi)
• Auto/manual operation Yes

• Parallel Operation Requirements Yes


Yes
18. Impedance and Losses

i) Guaranteed No load loss at rated voltage and frequency kW 25 kW max


We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 8 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
Tolerance (to be considered for loss evaluation) % Nil

ii) Guaranteed I2R Loss at rated current & frequency (at 750C) kW 105kW max
at principal tap
Tolerance (to be considered for loss evaluation) % Nil
iii) Eddy current and stray loss at rated current & frequency (at kW ≤ 20.0 kW
750C) atprincipal tap

iv) Load Loss (I2R+Eddy and Stray) at rated current & frequency kW ≤ 125 kW Max
(at 750C)at principal tap
v) Guaranteed Auxiliary loss at rated voltage and frequency kW 3
Tolerance (to be considered for loss evaluation) % Nil
vi) Calculated Fan Loss kW 3
vii) Calculated Pump Loss kW NA
viii) Air core reactance of HV winding % >20%
ix) Guaranteed Impedance (at Highest MVA base) %
(a) HV-IV (at Principal tap) NA
(b) HV-LV (at Principal tap) 12.5%
(c) IV-LV (at Principal tap) NA

Tolerance (+/-IEC Tol)


x) Impedance at extreme tappings at Highest MVA base [for %
HV-IV for 3winding transformers (or)
HV-LV for two winding transformers]
a) Max. Voltage tap a)13.2%
b) Min. Voltage tap b)11.8%
Tolerance % (+/-IEC Tol)
xi) Zero sequence impedance at principal tap (for 3-phase >80% of positive
transformers) sequence
impedance
19. Capacitance to earth for HV/IV/LV pF 3327/NA/4566
Capacitance values
provided are
indicative. Exact
values will be
provided after
final testing.
20. Regulation at full load at 75 0C winding temperature at:

a) upf 1.03%

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 9 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
b) 0.8 pf 8.18%

21. Guaranteed maximum Magnetizing Current at rated Voltage % <1% of full load
rated current
22. Efficiency: %
At 100% load upf
0.8 lead 99.70%
0.8 lag 99.63%
At 75% load upf
0.8 lead 99.75%
0.8 lag 99.68%
At 50% load upf
0.8 lead 99.78%
0.8 lag 99.72%
23. Load at Maximum efficiency % 44.72%
24. Any limitations in carrying out the required test? Short Circuit test
not considered.
If Yes, State limitations
25. Fault level of system (in kA) and its duration (in sec) kA (sec) 40kA (3 sec) for HV
& LV
26. Calculated short Circuit current (in kA) withstand capability for 2 kA HV Wdg – 3.5 kA
seconds (3 seconds for generator transformers) without exceeding
LV Wdg – 20.08 kA
temperature limit(i.e. Thermal ability to withstand SC current)
Approx

27. Test current (in kA) and duration (in ms) for short Circuit current kA As per IEC-60076-5
test (i.e.Dynamic ability to withstand SC)
(Dynamic short
circuit test is not
considered)
28. Over fluxing withstand time (due to combined voltage & msec
frequencyfluctuations):
110 %
110% continuously
125% 125 % for 1 minute
140% 140 % for 5
seconds
150%
150 % for 1
170%
seconds approx.
170 % for 0.25
seconds approx..

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 10 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
29. Free space required above the tank top for removal of core 7200mm approx.
30. Maximum Partial discharge level at 1.58 Ur/√3 pC 100pc

A. MAGNETIC SYSTEM
Sl. Description Unit Specifiedby Offered by
Buyer manufacturer
No.
1. Core Type:
i) 3 Phase 3 Limb (3 wound limbs)
ii) 3 Phase 5 Limb (3 wound limbs) 3 Phase 3 Limb (3
wound limbs)
iii) 1 Phase 2 Limb (2 wound limbs
iv) 1 Phase 3 Limb (1 wound limb)
v) 1 Phase 4 Limb (2 wound limbs)
vi) 1 Phase 5 Limb (3 wound Limbs)
2. Type of Core Joint:
i) Mitred Yes
ii) Step Lap Yes
3. CRGO: Posco/Nippon/JF
E/Equi. Country:
i) Make & Country of Origin
Korea/Japan/Equi
ii) Thickness, mm 0.23mm
iii) Max. Specific loss at 1.7 T, 50Hz, in Watts/kg 0.923
iv) Grade of core as per BIS MOH-0.23
v) Insulation between core laminations Carlite
vi) BIS certified (Yes/No) Yes
4. Minimum Gross & Net Area of: cm2
i) Core Core: 3177.76
Approx.
ii) Limb
Limb: 3177.76
iii) Yoke Approx.
iv) Unwound limb Yoke: 3177.76
(May be verified during manufacturing stage – at the discretion Approx.
of buyer) Unwound limb:
NA

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 11 of 28
Cluster, Mundra

Sl. Description Unit Specifiedby Offered by


Buyer manufacturer
No.
5. Stacking Factor % 0.975 approx.
6. Voltage per turn V 118.563 approx.
7. Apparent Core Density for Weight Calculation 7.65 gm/cm3
8. Minimum Net Weight of Silicon Steel Lamination CRGO (may kg R1 26000 (Approx.)
be verified during manufacturing stage by calculation)
9. Maximum Flux density at 90%, 100% and 110% voltage and T 90 % - 1.554 T
frequency(may be verified during manufacturing stage by
100 % - 1.727 T
calculation)
110% - 1.9 T
10. W/kg at working flux density 0.864 Approx
11. Building Factor Considered 1.08 Approx
12. Calculated No Load Loss at rated voltage and Frequency(Net kW 25 Max
Weight x W/kg x Building factor)
13. Magnetizing inrush current Amp 10-12 times of
Full load rated
current
14. No load current at normal ratio and frequency for : Amp
85% of rated voltage <1% of FLRC
100% of rated voltage
105% of rated voltage
15. Core Isolation test kV 2.5kVrms
16. Core bolt in limb / yoke Yes/No No
17. Core bolt insulation withstand voltage for one minute kV NA
18. Maximum temperature rise of any part of core or its support 0C <120degC
structure incontact with oil

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 12 of 28
Cluster, Mundra

B. CONDUCTING SYSTEM
Sl. Description Unit Offered
No. by manufacturer
HV IV LV Regulatin
g
1. Type of Winding Helical/Disc/Layer/inter wound Disc NA Helical Disc
2. Type of Conductor PICC/CTC/CTCE/CTCEN/BPICC BPICC NA CTC PICC
3. Minimum Yield Strength of Conductor for0.2% elongation N/mm2 80-140 NA 140 80 Approx.
Approx. Approx.

4. Maximum Current density at CMR and conductor area at any A/mm2 3.5 NA 3.5 3.5 A/Sqmm
tap: A/Sqmm A/Sqmm
&sq. 72.15 Sqmm
mm 72.15 717.2 min
i) HV Sqmm min Sqmm Min
ii) IV
iii) LV
5. Maximum current density under short circuit: A/mm2 28 NA 28 28
i) HV
ii) IV
iii) LV
6. Bare Weight of copper without paper insulation and lead Kg 6290 NA 4060 1530
(Minimum) R1
Approx. Approx. Approx.
7. Per Phase Maximum resistance of winding at rated tap at 75 ohm 0.2209 NA 0.00271 0.0603
OC
(Approx.) (Approx.) (Approx.)
8. Number of Turns/Phase 472 NA 56 111
9. Insulating material used for HV/IV/LV winding Kraft Paper NA Kraft Paper Kraft Paper

10. Insulating material used between:


i) HV and IV winding NA
ii) IV and LV winding NA
iii) LV winding and core PCB Cylinder & Ducts

iv) Regulating winding and adjacent winding/core PCB Cylinder as Phase Barriers

11. Details of special arrangement provided to improve surge SER NA NA NA


voltage distribution in the winding Consider
ed.
12. Dielectric Shielding used:
i) Interleaved winding No NA No No
ii) Wound in Shield No NA No No
iii) Others No NA No No

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 13 of 28
Cluster, Mundra

Sl. Description Unit Offered


No. by manufacturer
HV IV LV Regulatin
g
13. Magnetic Shielding used:
i) Yoke Shunt on core clamp NO NA NO NO
ii) Magnetic shunt on tank Yes NA Yes Yes
iii) Electromagnetic (Copper/Aluminum) shield on tank NO NA NO NO
iv) Others NO NA NO NO

14. Noise level when energized at normal voltage and frequency dB 70db
without load

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 14 of 28
Cluster, Mundra

C. COOLING SYSTEM
Sl.No. Description Unit Specified Offered by
by Buyer manufacturer
1. Type of Cooling
[ONAN (or) ONAN/ONAF (or) ONAN / ONAF / OFAF (or) ONAN / ONAN/ONAF
ONAF/ODAF (or) ONAN / ONAF1 / ONAF2 etc.]
2. Percentage Rating Corresponding to Cooling Stages (HV/IV/LV) 80/100%
3. No. of Cooler banks (2x50% / 2x100% / 1x100% etc.) 1 X 100%
4. Temperature gradient between windings and oil < 18 Deg C Approx
5. Time in minutes for which the transformer can run at full min 10minutes
load withoutexceeding maximum permissible temperature at without hotspot
reference ambient temperature when supply to fans and / or temperature
pumps is cut off exceeding
140degC
6. Guaranteed Maximum Temperature rise at 1000 mts. altitude 0C
and at actual altitude at site at ambient temperature at cooling
specified at sl. No.1:
45
i) Top Oil by thermometer
50
ii) Average Winding by resistance
61+ 32 Deg Avg.
iii) Winding hot spot Ambient Temp
7. Type of Cooler:
i) Radiator Bank Yes
ii) Oil to Air Heat Exchanger (Unit Cooler) NA
iii) Oil to Water Cooler (Single Tube) NA

iv) Oil to Water Cooler (Double Tube) NA

v) Tank Mounted Yes

vi) Header Mounted NA


NA
vii) Separately Mounted
NA
viii) Degree of Protection of terminal box

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 15 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
8. Cooling Fans:
i) Type Propeller type
ii) Size 610 sweep approx.
iii) Rating (kW) 0.5kW approx.

iv) Supply voltage 400/415V AC

v) Quantity (Running + Standby) per cooler bank 6 main + 2 SB

vi) Whether fans are suitable for continuous operation at


85% of theirrated voltage calculated time constant:
• natural cooling Yes
• forced air cooling Yes

vii) Degree of Protection of terminal box IP55

9. Oil Pumps:
i) Type
ii) Size
iii) Rating (lpm and kW)
iv) Supply voltage NA

v) Quantity (Running + Standby) per cooler bank


vi) Efficiency of motor at full load
vii) Temperature rise of motor at full load
viii) BHP of driven equipment
10. Coolers (Oil to Air):
i) Quantity (Running + Standby) NA
ii) Type and Rating
11. Coolers (Oil to Water):
i) Quantity (Running + Standby)
ii) Type and Rating NA
iii) Oil flow rate (lpm)
iv) Water flow rate (lpm)
v) Nominal Cooling rate (kW)
vi) Material of tube

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 16 of 28
Cluster, Mundra

Sl.No. Description Unit Specified Offered by


by Buyer manufacturer
12. Radiators:
i) Width of elements (mm) 520
ii) Thickness (mm) 1.2
iii) Length (mm) 2400

iv) Numbers 7

13. Cooler loss at rated output, normal ratio, rated voltage, rated kW 3kW for fans
frequency atambient temperature of 50oC

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 17 of 28
Cluster, Mundra

D. DIELECTRIC SYSTEM
Sl.No. Description Unit Offered by
manufacturer

1. Geometric Arrangement of winding with respect to coree.g: Core-LV- Core-LV-HV-Reg


IV-HV-Reg Coarse-Reg Fine

2. Regulating Winding:
i) Body Tap NO
ii) Separate YES
3. HV Line Exit point in winding:
i) Top Yes
ii) Center No
4. Varistors used across WindingsIf yes, Details Yes/No No
5. Insulation Levels of windings HV IV LV HV-N LV-
N
i) Lightning Impulse withstand voltage (1.2/50µs) kVp 325 NA 75 NA 75
ii) Chopped wave Lightning Impulse withstand voltage kVp NA NA NA NA NA
iii) Switching Impulse withstand voltage (250/2500µs) kVp NA NA NA NA NA
iv) Power frequency withstand voltage (one minute / 5 minutes) kVrms 140 NA 28 NA 28
6. Tan delta of windings at ambient temperature % 0.5%

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 18 of 28
Cluster, Mundra

E. ACCESSORIES
Sl.No. Description Unit Specifiedby Offeredby
Buyer manufacturer

1. Tap Changers
i) Control
a-Manual b-Automatic Yes
c-Remote d-Local
ii) Voltage Class and Current Rating of Tap Changers 72.5kV 350A
iii) Make and Model Easun MR VIII model
iv) Make and Type of Automatic Voltage Regulator EMCO/Pradeep sales
(AVR) Microprocessor based
v) Tie-in resistor requirement (to limit the recovery Not applicable
voltage to a safevalue) and its value
vi) OLTC control and monitoring to be carried out Y/N Yes
through SubstationAutomation System
vii) Power Supply for control motor
(No. of Phases/Voltage/Frequency) 3 / 415V / 50hz
viii) Rated Voltage for control circuit V
(No. of Phases/Voltage/Frequency) 1 / 230V / 50hz
2. Tank
i) Tank Cover: Conventional/Bell/Bottom Plate Conventional
ii) Material of plate for tank Mild Steel
iii) Plate thickness: side, bottom, cover mm 12/20/16
iv) Rail Gauge mm 1676
v) Minimum Clearance height from rail for lifting Mm 8500
Active Part
vi) Wheels: Numbers/Plane/Flanged/Uni- 4/Flanged/Bi-
Directional/Bi- Directional
Directional/Locking Details
vii) Vacuum withstand Capability mm of Hg
(a) Tank 760mm
(b) Radiators/Conservator/Accessories As per CBIP

viii) High Pressure withstand Capability mm of Hg


(a) Tank 760mm
(b) Radiators/Conservator/Accessories As per CBIP

ix) Radiator fins/ conservator plate thickness Mm 1.2 / 5 thk

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 19 of 28
Cluster, Mundra

Sl.No. Description Unit Specifiedby Offeredby


Buyer manufacturer

x) Tank Hot spot temperature OC <110degC

3. Bushings: HV IV LV HV-N LV-N

i) Termination Type Outdoor Bare Cable


Bushing Box
a-Outdoor
b-Cable Box (oil/Air/SF6)c-Plug in Type
ii) Type of Bushing: OIP/RIP/RIS/oil communicating OIP Oil
Comm
iii) Bushing housing - Porcelain / polymer Porcelain Porcelain
iv) Rated Voltage Class kV 72.5 17.5
v) Rated Current A 1250 3150
vi) Lightning Impulse withstand voltage (1.2/50µs) kVp 325 95
vii) Switching Impulse withstand voltage (250/2500µs) kVp NA NA
viii) One minute Power frequency withstand voltage kVrms 140 38
(dry & wet)
ix) Minimum Creepage Distance Mm 2248 543
x) Quantity of oil in bushing and specification of oil used 2.5 NA
Lit/Mineral
Oil
xi) Make and Model ABB/GE/CGL/ CJI/Eq
Eq
xii) Tan delta of bushings % < 0.5% NA
xiii) Max Partial discharge level at Um pC 10pC NA
xiv) Terminal Pad details As per IEC- As per
60137 IEC-
60137
xv) Weight of assembled bushings Kg 40 Kg / 13 Kg /
bushing Bushing
Approx. Approx.
xvi) Whether terminal connector for all bushings Yes Yes
included in the scope
of supply
4. Minimum clearances between bushings (for HV, IV and LV) HV / LV
(a) Phase to phase 700 / 130
(b) Phase to ground 660 / 80
5. Indicator / Relay

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 20 of 28
Cluster, Mundra

Sl.No. Description Unit Specifiedby Offeredby


Buyer manufacturer

i) Winding temperature thermometer/ indicator:Range 0-150 Deg C , 1.5


Accuracy
ii) Oil temperature thermometer/ indicator:Range 0-150 Deg C , 1.5
Accuracy
iii) Temperature sensors by fiber optic (if provided) No
iv) Oil actuated/gas operated relay Yes
v) Oil level Indicators: Yes
Main ConservatorOLTC Conservator Yes
vi) Oil Sight Window:
Main Tank Yes
Main Conservator Yes
OLTC Conservator Yes
6. Conservator:
i) Total volume 7.5% of Total oil in
Tank
ii) Volume between highest and lowest visible oil
levels 75% of Conservator
volume
7. Conservator Bag (air cell)
i) Material of air cell Nitrile Rubber
ii) Continuous temperature withstand capacity of air 100 Deg C
cell
8. Air cell rupture relay provided Yes / No Yes

9. Pressure Relief Device:


i) Number of PRDs provided 2
ii) Location on the tank Mounted on Top Cover
iii) Operating pressure of relief device 0.49 Kg/Sqcm

10. Sudden Pressure Relay / Rapid Pressure rise relay Y/N


provided; if yes,
No
i) Location on the tank
ii) Operating pressure
11. Dehydrating Breathers (Type & No. of breathers) a) Maintenance Free
Silica Gel Breather –
(a) For main Conservator tank
1No
(b) For OLTC conservator b) Maintenance Free
Silica Gel Breather –
1No
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 21 of 28
Cluster, Mundra

Sl.No. Description Unit Specifiedby Offeredby


Buyer manufacturer

12. Flow sensitive Conservator Isolation Valve Provided Y/N Yes


13. Tap Changer protective device OSR
14. Type and material of gaskets used at gasketed joints Nitrile Rubber
15. Bushing CTs: (HV side and IV/LV side)

i) Voltage class kV
ii) No. of cores
iii) Ratio
iv) Accuracy class VA Refer Drawing 5964/C-
03 for complete details
v) Burden
vi) Accuracy limit factor ΩV
A
vii) Maximum resistance of secondary winding
viii) Knee point voltage
ix) Current rating of secondaries
16. Neutral CTs:
i) Voltage class kV
ii) No. of cores Refer Drawing 5964/C-
03 for complete details
iii) Ratio
iv) Accuracy class VA

v) Burden
vi) Accuracy limit factor Ω
VA
vii) Maximum resistance of secondary winding
viii) Knee point voltage
ix) Current rating of secondaries
17. Transformer Oil As per Annexure-L &
i) IS 335 / IEC60296 / as per specification IEC 60296
ii) Inhibited/ un-inhibited Uninhibited
iii) Mineral / Natural Ester / Synthetic Ester Mineral

iv) Spare oil as percentage of first filling 5%

v) Manufacturer Apar/Savita/Raj Petro

vi) Quantity of oil (before filling and before R1 18145 Lit – Approx.
commissioning) IEC 60296
vii) Moisture content (mg/L or ppm)
IEC 60296
We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 22 of 28
Cluster, Mundra

Sl.No. Description Unit Specifiedby Offeredby


Buyer manufacturer

viii) Tan delta (Dielectric Dissipation Factor) at 90oC IEC 60296

ix) Resistivity (Ω-cm))


x) Breakdown Voltage (before and after treatment) (kV) IEC 60296

xi) Interfacial tension at 20 oC (N/m) IEC 60296


IEC 60296
xi) Pour point (oC)xii)Flash point(oC)
IEC 60296
xiii) Acidity (mg KOH/gm)
Not Applicable
xiv) Inhibitors (for inhibited oil) (%)
xv) Oxidation Stability
IEC 60296
18. Press Board: Raman board / Equiv
i) Make Pre-Compressed
Cellulose
ii) type
19. Conductor Insulating Paper
i) Kraft paper Yes
ii) Thermally upgraded Kraft paper No
iii) Nomex No

20. Provision for fire protection system (as per spec), if yes, Y/N Yes, NIFPS considered.
provide details CTR make
21. Insulation of core bolts, washers, end plates etc. NA
22. Weights and Dimensions: Approx. weights
i) Weights:
a. Core 43600
b. Windings (CCA Weight)

c. Tank 13000

d. Fittings 7000
R1 16150
e. Oil
79750
f. Total weights of complete transformers with oil
R1
and fittings
ii) Dimensions:
a. Overall height above track 6000
b. Overall length 8000
R1
c. Overall breadth 6100

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 23 of 28
Cluster, Mundra

Sl.No. Description Unit Specifiedby Offeredby


Buyer manufacturer

iii) Minimum bay width required for installation of LxW 8500 x 6100
the transformer
R1
iv) Weight of the heaviest package of the transformer 69500
arranged fortransportation

23. Lifting Jacks


i) Number of jacks included 4
ii) Type and Make Hydraulic Type
iii) Capacity 30 T

iv) Pitch As per Supplier

v) Lift 150 mm Approx.

vi) Height in close position 260 mm Approx.

24. Rail Track gauges


i) 2 Rails or 3 rails or 4 rails 2
ii) Distance between adjacent rails on shorter axis 1676
iii) Distance between adjacent rails on longer axis 1676

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 24 of 28
Cluster, Mundra

2.0 Parameters of Current Transformer of 50 MVA (3-ph), 66/11.5 kV Transformers


Description Current Transformer Parameters

HV HV NeutralSide LV LV NeutralSide
Side Side
Ratio

CORE 1 800/1 - 3150/1 3150/1

CORE 2 800/1 - 3150/1 3150/1


CORE 3 800/1 - - -
Minimum knee point voltage or burden and accuracy class

CORE 1 800V, PX / PS - 3150V,PX/PS 3150V, PX/PS

CORE 2 0.2S Class 15VA ISF ≤ 5 - 3150V,PX/PS 3150V, PX/PS

CORE 3 800V, PX / PS - - -

Maximum CT Secondary Resistance 4 4

CORE 1 1.5 Ohm - 18 Ohm 18 Ohm

CORE 2 - R1 - 18 Ohm 18 Ohm


R1

CORE 3 1.5Ohm - - -

Application

CORE 1 Restricted - REF REF


Earth Fault(REF)

CORE 2 Metering - Differential SEF

CORE 3 Differential - - -

Maximum magnetization current (at knee point voltage)

CORE 1 100 mA - 25 mA 25 mA

CORE 2 - - 25 mA 25 mA

CORE 3 100 mA - - -

a. Notes:
i. Parameters of WTI CT for each winding shall be provided by the manufacturer / contractor.
ii. The CTs used for REF protection must have the identical parameters in order to limit the
circulating current under normal condition for stability ofprotection.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 25 of 28
Cluster, Mundra

TECHNICAL SCHEDULES of HVIC/RTV Coating (Data to be furnished along with the Bid)
S.NO. Specification Requirement Supplier’s Compliance
in Y/N
1 Product Silicon based Yes
(Note- Other materials such as Fluorourethanes do not
have the long-term UV resistance or adhesion of properly
formulated Silicon, hence not accepted)
2 Product type RTV Type I or RTV II silicon. Yes RTV - I
(Note:-RTV Type I (also written as RTV-I or RTV-1) silicon
refers to a silicone that is 1-component and does not
require the addition of catalyst or other chemicals during
the application process in order to cure the product.
RTV II refers to multiple component materials and these
components are to be mixed by operators in the field
before application.)
3 Product must contain Alumina Tri-Hydrate (ATH), Yes ATH
in the formulation-
Size = _____
(Note:-larger grain
size ATH is preferred
and vendor should
indicate the grain size
of ATH).
4 Method Application Spray/Brush Spray/Brush
5 Product must not Peel, chalk, crack, craze, blister or bubble. Yes
6 Product must have porcelain, glass or nonceramic Yes
strong adhesion to
insulators
7 Product must NOT use of primers in order to Yes
require
achieve adhesion
8 Product must never Develop tracking marks longer than 100 millimeters. Yes
9 Product must never Erode in areas greater than 500 sq millimeters. Yes
10 Product must retain Equal to or better than Class Yes
hydrophobic
HC3 as per the STRI Guide
performance
92/1.
11 The coating should be Salt, fog, coastal and desert condition, water, UV, Yes
resistant to chemicals and other atmospheric conditions.
12 Product must eliminate appreciable leakage current over the long term resulting in the elimination of surface
discharge, visible discharge at nightfall and hotspots (as indicated through infrared thermal imaging).
13 Coating Material
properties in liquid
form
Basic Components RTV silicone coating containing optimally sized ATH Yes
(alumina tri hydrate) present in optimal concentration.
ATH (alumina tri Between 10 and 20 microns, 13 to 15 microns preferred Yes
hydrate) Grain Size
Percent of Solids by > or =70% Yes

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 26 of 28
Cluster, Mundra

S.NO. Specification Requirement Supplier’s Compliance


in Y/N
Weight
Track-Free Time in 30 - 45 min. Yes
Minutes
Color White or Grey shade Yes, Grey Shade
14 Coating Material properties in its solid form (As Cured) (atleast)
Dielectric Strength > 280 kV /cm Yes

Tracking & Erosion Minimum grade 1A 4.5 Yes


Resistance (IEC
60587 test)
Minimum Required Between 380 and 520. Yes
Coating Thickness
(DFT) in microns
Dielectric Constant < 4.0 (at 100 Hz)/ < 3.9 (at 100 kHz) Yes

Dissipation Factor 0.03 (max.) (at 50 Hz)/0.0292 (max) & 100 Hz 0.0864 Yes
(max.) (at 100 Hz)/ 0.0788 (max.)(at 100 kHz)
Dry Arc Resistance > 115 seconds (for Track) > 420 seconds (for burn Yes
Out)
Volume resistivity Yes
2.4 x 1015 ohm cm (minimum)
at 25°
Water repellency Yes
Angle > 110 °
15 Copy of following Type Test Certificates issued by any Government approved lab like CPRI, etc., to be
submitted along with quotation.
a Accelerated Yes
· Minimum 5,000 hours testing clause 5.3 Annex C of the
Weathering Test as
IEC 61109 test standard;
per IEC 61109.
· Maximum allowable leakage current pulses during 5,000
hours 1.10 mA
· Maximum allowable 100 data point moving average
during 5,000 hours 0.75mA
b Tests as per IEC – · Artificial Pollution test by Yes
60507 Salt-Fog method.
· Hydrophobic recovery by corona test
c Test as per IEC Yes
60587 Tracking & Erosion Resistance Test.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 27 of 28
Cluster, Mundra

S.NO. Specification Requirement Supplier’s Compliance


in Y/N
16 Ten (10) years at least Yes 10 Years

A guarantee starting
from the date of the
final taking over
certificate shall be
given by the Coating
Manufacturer and
contractor for the
silicon coating of the
insulator confirming
that no flash over &
no arcing will occur
on the coated
insulator within the
guarantee period.

Only oil communicating type porcelain bushing shall be provided with RTV coating.
For RIP bushing RTV coating is not applicable.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY
MUNDRA SOLAR TECHNOLOGY LIMITED
Doc.No.
2 GW WAFER & INGOT MANUFACTURING
MSTL-E-SEP-PTR-TE-S-I-001
Electronic
Manufacturing Bid Proposal Sheet for Power Transformer (Section - 3) Page 28 of 28
Cluster, Mundra

SUBSECTION 3.2: PERFORMANCE GUARANTEES


Unit of Guaranteed Value
Sl. No. Item Measurement

1 No load loss at rated voltage and kW 25.0


rated frequency (Maximum)
2 Load Loss at rated power kW 125.0
(Maximum)
3 Auxiliary loss (Cooler loss) at rated kW 3.0
power (Maximum)

4 Percentage efficiency at rated % 99.64 %


voltage and rated Power at 0.85 PF
@ 100 %Load &
(including load loss, no load loss &
0.85 PF
aux. loss)
5 Impedance at Principal tap on % 12.5% +/- IEC Tol.
Rated maximum MVA base
6 Temperature rise of top oil over 50 °C 45
deg.C ambient
7 Temperature rise of Winding over °C 50
50 deg.C ambient
8 ONAN rating MVA 40
9 ONAF rating MVA 50

Note: The loss figures indicated shall be as a maximum and inclusive of IS/IEC tolerances.

SIGNATURE OF ___________________________
BIDDER

NAME ________________________________

DESIGNATION_____________________________

COMPANY SEAL DATE __________________________________

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. FOR TENDER
PURPOSE ONLY