Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Categories:

 Cat-I Approved. Good for Manufacturing/Construction/Fabrication

 Cat-I* Approved with minor comments. No resubmission is required.


AMIT Digitally signed
by AMIT To be incorporated in As-Built. Good for Manufacturing/
AGRAWAL
AGRA Date: Construction/ Fabrication subject to incorporation of comments.
2022.11.28

WAL 16:02:31
+05'30'

Reviewer
 Cat-II Approved. Released for Manufacturing/fabrication/construction
subjected to incorporation of comments. Modification as
Noted. Resubmission is required.

Amit Digitally signed


 Cat-III Not Approved

Asha by Amit Asharfilal


Date: 2022.11.28
17:22:18 +05'30'
 Cat-IV For Information & Records

rfilal
Approver Note: “Approval of this document does not absolve the Contractor/ Supplier/
Fabricator from fulfilling Contractual obligations in any way”
1 2 3 4 5 6 7 8

CABLING SCHEDULE
CABLE SIZE CABLE ROUTE
CABLE TAG NO PURPOSE CORE & FERRULES(WIRE) NUMBER SCOPE OF SUPPLY
C X Sq.mm FROM TO
A A
5790/+M.BOX-+RTCC-1 2X2.50 +M.BOX +RTCC LV-RWTI CONNECTION X100,X101 =ITTL

5790/+TRFR-+M.BOX-2 3X2.50 +TRFR +M.BOX FAN MOTOR-7 CONNECTION M710,M720,M730 =ITTL

5790/+M.BOX-+TRFR-3 2X4.00 +M.BOX +TRFR LV-WTI CT C30,C31 =ITTL

5790/+TRFR-+M.BOX-4 4X2.50 +TRFR +M.BOX OLTC MOLG L16,L16A,L17,L17A =ITTL

5790/+OLTC-DM-+RTCC-5 2X2.50 +OLTC-DM +RTCC 110VAC SUPPLY TO RTCC N96,N97 =ITTL

5790/+OLTC-DM-+RTCC-6 3X4.00 +OLTC-DM +RTCC TPI CONNECTION N219,N220,N221 =ITTL

5790/+TRFR-+M.BOX-7 3X2.50 +TRFR +M.BOX FAN MOTOR-5 CONNECTION M510,M520,M530 =ITTL

B 5790/+TRFR-+M.BOX-8 3X2.50 +TRFR +M.BOX FAN MOTOR-2 CONNECTION M210,M220,M230 =ITTL B

5790/+TRFR-+M.BOX-9 3X2.50 +TRFR +M.BOX FAN MOTOR-3 CONNECTION M310,M320,M330 =ITTL

5790/+TRFR-+M.BOX-10 3X2.50 +TRFR +M.BOX FAN MOTOR-6 CONNECTION M610,M620,M630 =ITTL

5790/+OLTC-DM-+RTCC-11 6X2.50 +OLTC-DM +RTCC OLTC-ANNUNCIATOR N250,N251,N252,N253,N254 =ITTL

5790/+TRFR-+M.BOX-12 2X2.50 +TRFR +M.BOX OLTC-OSR K32,K33 =ITTL

5790/+TRFR-+M.BOX-13 3X2.50 +TRFR +M.BOX FAN MOTOR-1 CONNECTION M110,M120,M130 =ITTL

5790/+TRFR-+M.BOX-14 4X4.00 +TRFR +M.BOX HV W-Ph CT C730,C731,C732,C733 =ITTL

5790/+M.BOX-+RTCC-15 8X2.50 +M.BOX +RTCC CCC TO TCMS L400,L401,L402,L403,L404,L405,L406,L407 =ITTL

5790/+TRFR-+M.BOX-16 3X2.50 +TRFR +M.BOX FAN MOTOR-4 CONNECTION M410,M420,M430 =ITTL


C C
5790/+M.BOX-+RTCC-17 17X2.50 +M.BOX +RTCC INDICATION LAMP CONN J6,J7,L120,L121,L122,L123,L124,L125,L126,L127,L128,L =ITTL

5790/+M.BOX-+RTCC-18 3X2.50 +M.BOX +RTCC FAN CONTROL FROM RTCC M71,M72,M73 =ITTL

5790/+TRFR-+M.BOX-19 4X4.00 +TRFR +M.BOX HV V-Ph CT C630,C631,C632,C633 =ITTL

5790/+M.BOX-+RTCC-20 2X2.50 +M.BOX +RTCC ROTI CONNECTION X108,X109 =ITTL

5790/+TRFR-+M.BOX-21 4X4.00 +TRFR +M.BOX HV U-Ph CT C530,C531,C532,C533 =ITTL

5790/+RTCC-+OLTC-DM-22 12X2.50 +RTCC +OLTC-DM OLTC- RTCC INTERCON N102,N106,N107,N113,N114,N118,N119,N126,N98 =ITTL

5790/+TRFR-+M.BOX-23 2X2.50 +TRFR +M.BOX OLTC-PRD K30,K31 =ITTL

5790/+M.BOX-+OLTC-DM-24 4X2.50 +M.BOX +OLTC-DM 415VAC TO OLTC-DM H30,H31,H32,H33 =ITTL


D D
5790/+M.BOX-+RTCC-25 2X2.50 +M.BOX +RTCC HV-RWTI CONNECTION X104,X105 =ITTL

5790/+TRFR-+M.BOX-26 4X4.00 +TRFR +M.BOX LV NEUTRAL CT C430,C431,C432,C433 =ITTL

5790/+TRFR-+M.BOX-27 2X4.00 +TRFR +M.BOX HV-WTI CT C40,C41 =ITTL

5790/+M.BOX-+RTCC-28 14X2.50 +M.BOX +RTCC CCC-ANNUN. CONNECTION L201,L202,L203,L204,L204A,L205,L206,L207,L208,L209 =ITTL

5790/+M.BOX-+RTCC-29 8X2.50 +M.BOX +RTCC CCC-P.F CONTACTS L150,L151,L152,L153,L154,L155,L156,L157 =ITTL

5790/+M.BOX-+RTCC-30 12X2.50 +M.BOX +RTCC CCC-P.F CONTACTS L158,L159,L160,L161,L162,L163,L164,L165,L166,L167,L1 =ITTL

E E

CUSTOMER : M/s. MUNDRA SOLAR TECHNOLOGY LIMITED

P.O.No : - DATED : -

TOL:-

LOCATION : +RTCC

ALL DIMNS. IN mm
TITLE UNLESS OTHERWISE
SPECIFIED.
GA OF RTCC & SCHEMATIC
F SCALE : NTS F
DIAGRAM OF OLTC& RTCC
2022 NAME SIGN DATE W.O. No: 5964

DR'N PR PR 04.11.22 SUB TITLE : RATING : 40/50 MVA ,66/11.5 kV ONAF,OLTC TRAFO

R1 PR 21.11.22 CUSTOMER COMMENTS AMENDED CH'D SS SS 04.11.22 DRG. No.: 5964/C-02 SHEET No : 2 OF 3
CABLING SCHEDULE
REV.NO SIGN DATE MODIFICATION APP'D RP RP 04.11.22 REV. No. : 0 1

1 2 3 4 5 6 7 8

ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL & SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED
1 2 3 4 5 6 7 8

CABLING SCHEDULE
CABLE SIZE CABLE ROUTE
CABLE TAG NO PURPOSE CORE & FERRULES(WIRE) NUMBER SCOPE OF SUPPLY
C X Sq.mm FROM TO
A A

5790/+TRFR-+M.BOX-31 4X4.00 +TRFR +M.BOX LV V-Ph CT C230,C231,C232,C233 =ITTL

5790/+TRFR-+M.BOX-32 4X4.00 +TRFR +M.BOX LV W-Ph CT C330,C331,C332,C333 =ITTL

5790/+TRFR-+M.BOX-33 4X2.50 +TRFR +M.BOX BUCHHOLZ RELAY-A&T K10,K11,L10,L11 =ITTL

5790/+TRFR-+M.BOX-34 4X4.00 +TRFR +M.BOX LV U-Ph CT C130,C131,C132,C133 =ITTL

5790/+M.BOX-+TRFR-35 2X2.50 +M.BOX +TRFR TO AIRCELL RUPTURE RELAY L34,L35 =ITTL

5790/+M.BOX-+TRFR-36 4X2.50 +M.BOX +TRFR BREATHER CONNECTION-OLTC H86,H87,X140,X141 =ITTL

5790/+M.BOX-+TRFR-37 4X2.50 +M.BOX +TRFR BREATHER CONNECTION-MAIN H77,H78,X120,X121 =ITTL


B 5790/+TRFR-+M.BOX-38 3X2.50 +TRFR +M.BOX FAN MOTOR-8 CONNECTION M810,M820,M830 =ITTL B

5790/+TRFR-+M.BOX-39 2X4.00 +TRFR +M.BOX HV U-Ph CT CORE-3 C534,C535 =ITTL

5790/+TRFR-+M.BOX-40 2X4.00 +TRFR +M.BOX HV V-Ph CT CORE-3 C634,C635 =ITTL

5790/+TRFR-+M.BOX-41 2X4.00 +TRFR +M.BOX HV W-Ph CT CORE-3 C734,C735 =ITTL

5790/+OLTC-DM-+RTCC-42 4X2.50 +OLTC-DM +RTCC TAP UPPER & LOWER LIMIT J10,J12,J13 =ITTL

5790/+RTCC-+SCADA-43 3X2.50 +RTCC +SCADA OLTC OPERATION FROM SCADA N106,N107,N123 =ITTL

5790/+TRFR-+M.BOX-44 2X2.50 +TRFR +M.BOX MAIN PRD-2 K28,K29 =ITTL

5790/+TRFR-+M.BOX-45 2X2.50 +TRFR +M.BOX MAIN PRD-1 K26,K27 =ITTL

C
5790/+TRFR-+M.BOX-46 4X2.50 +TRFR +M.BOX MAIN MOLG-LOLA & HOLA L12,L13,L14,L15 =ITTL C

5790/+OLTC-DM-+RTCC-47 8X2.50 +OLTC-DM +RTCC OLTC-RTCC-POTENTIAL FREE N300,N301,N302,N303,N304,N305,N306 =ITTL

D D

E E

CUSTOMER : M/s. MUNDRA SOLAR TECHNOLOGY LIMITED

P.O.No : - DATED : -

TOL:-

LOCATION : +RTCC

ALL DIMNS. IN mm
TITLE UNLESS OTHERWISE
SPECIFIED.
GA OF RTCC & SCHEMATIC
F SCALE : NTS F
DIAGRAM OF OLTC& RTCC
2022 NAME SIGN DATE W.O. No: 5964

DR'N PR PR 04.11.22 SUB TITLE : RATING : 40/50 MVA ,66/11.5 kV ONAF,OLTC TRAFO

R1 PR 21.11.22 CUSTOMER COMMENTS AMENDED CH'D SS SS 04.11.22 DRG. No.: 5964/C-02 SHEET No : 3 OF 3
CABLING SCHEDULE
REV.NO SIGN DATE MODIFICATION APP'D RP RP 04.11.22 REV. No. : 0 1

1 2 3 4 5 6 7 8

ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL & SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED