Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

IFE ELEVATORS CO.

,LTD
China Factory: Qingxi Town,Dongguan city,Guangdong
Tel:+86-769-82078888 Fax:+86-769-87732448
www.ife.cn

The image and content are just for you reference and please be subject
to the actual products. Please pardon us for not informing you in advance
if anything updated. Please contact IFE for details.
201501 IFE ELEVATOR CO., LTD COPYRIGHT

Atlas ME
Freight Elevator

www.ife.cn
● First group of elevator companies awarded class A certificate in manufacturing, installation,
THE NO.1 EXPORT OF CHINESE ELEVATOR
maintenance certified by National Quality Inspection Department
BRAND FOR LAST FOUR YEARS ● An area of 110,000 m2 global production industrial park as well as international leading elevator
test tower and escalator test tower
● Approved National Hi-tech Enterprises and provincial Elevator Research and Development Center
● With product sales to 5 continents 33 countries and area around the world
● 101 branches and service points in the globe
● More than 1000 after-sale service technicians and engineers

01 02
MORE SAFETY MORE DURABLE

Rope Anti-loose Detection Brake Detection


Australian AS1735 standards Accurate Weighing Device
Singapore HDB standard Photoelectric Sensor Protection Invention patent No. 201410337015.7
Patent No. 201420470694.0
Full time detection, positively Contact-less protection device, forming Utility model patent No. 201420391219.4
Traction rope anti-loose device is
report brake problem, which dense Infrared Ray cross curtain, effectively Accurately measure the load of each floor to
detecting the rope all the time. When
eliminate the risk of brake failure. prevent the clamp injury or fork lift damage avoid the risk from the overloading.
the rope is loose, elevator will
the door during the loading and unloading of
immediately stop running to protect the
goods.
safety of passengers.

Checkered Steel Floor


More Reliable Drum Brake
Using 5mm thick checkered plate as the
Compared with block brake, drum brake is not
Electronic Leveling Switch affected by temperature change, the brake car floor which is more durable.
Integrated Controller
European CE certified
Reliable levelling switch detection switch gap is big, the switch is more
reliable. At the same time, the replacement of the
Dual CPU high precision micro Response time is less than 0.001
brake pad is easier.
computer control integrated with seconds, service life more than Anti-collision Steel and panel
mother board and inverter.Effectively 10,000,000 times, accurate (Optional)
prevent the car slipping down through control without interference. Hall door anti collision steel to prevent
Heavy Duty Freight Elevator
the precise control and start auxiliary the door jamb damage, 300mm high
(Optional) anti collision panel at car wall bottom to
technology so that the elevator can run Made of high strength steel car frame, suitable
smoothly. for fork lift and all kinds of goods transportation.
prevent car wall damage by fork lift.

03 04
MORE SAFETY DECORATION
IFE GOP02
COP and LOP
More durable hairline
stainless steel panel;more
clear Dot matrix LED display
and humanized operation
European EMC
interface.
Low radiation and no electromagnetic pollution
European standard electromagnetic compatibility,
effectively eliminate the interference of
electromagnetic radiation.

Car floor material


Energy saving Door operator
PMSM+VVVF door operator
60% energy saving compared with
traditional door operator, more stable.

Checkered plate Aluminium Alloy


Energy saving driving system AF01 (Optional)
PMSM+VVVF traction motor
Improved the elevator operation
efficiency, small space required, low Car wall color
noise.

Matt Blue Matt Grey Sand grey


(ASC01) (ASC02) (ASC04)

Door Opening

180 degree door opening Side opening 3 panels side opening 4 panels center opening

05 06
DECORATION

Optional Car Acar02


Ceiling: Hairline Stainless steel Wall: Hairline Stainless steel
Light: LED day light Door: Hairline Stainless steel Floor: Checkered Plate

Standard Car Acar01 Standard Landing


Ceiling: Painted steel(Color optional) door Al01
Wall: Painted steel(Color optional) Jamb: Painted Steel Optional Landing
Lighting: LED day light (color optional) door Al02
Door: Painted steel(Color optional) Door: Painted Steel Jamb: Painted Steel
Floor: Checkered plate (color optional) Door: Painted Steel
Sill: Molding Steel Sill: Molding Steel

07 08
HARMONIOUS
Shenzhen Lilang Jewelry Part
Foxconn LIFE WITH IFE

Shenyang Textile City Guangzhou Jinlaite Demonstration Park


Shenzhen Zhaochi Co., Ltd
Shenzhen Yiwu Commercial City
Jiangmen Kaiping City
Dongguan Omlon electrical
Xiamen International Email administration center
Changsha Gaoqiao Market
Xuzhou Global Food city
Taiyuan Wanmashi Commercial City
Tianjin Huicheng International shopping mall
Vtech Group Bolmes Group
Neimenggu Fortune Plaza
Chongqing Ronglong Industrial Zone

Zhengde Square

Wuhan Fashion Plaza

09 10
ATLAS ME Funtion table
Basic functions Basic functions
Operation Functions Special operation

By turning the switch in COP to switch to attendant operation state so the driver could manage the
01 Full selective collection Collect the call signals, analyze and response selectively 31 Attendant operation number of passengers in the car, landing call response and opening /closing doors etc.
02 Full-load by pass If full-load is detected, elevator would not response from outside but only inside signal. In attendant operation state, if pressed by-pass button before starting up, the elevator will not respond
32 By-pass switch to landing hall call in the next course of operation, and only goes to the registered floor in the car COP.
03 Car call reset Passenger can press COP button two times to cancel the wrong registration signal.
When the elevator is in the attendant operation state, buzzer will sound to alert the drivers that someone
33 Buzzer
is calling from HOP.
04 Door open/ close button Door open and close button located at COP for passenger to control the time flexibly.
Set a base station according to the actual situation from the site, the elevator will return to this preset
Door open/ 34 Base floor setting floor after a specific time without any operations, normally it is ground floor.
05 close button light Button light is on when pressed on door open/ close button reflects responding.

Resume initialized Set a firefighting floor according to the actual situation from the site, the elevator will land at this floor
06
When power supply is interrupted, elevator position signal cannot be reserved or unable to locate the 35 Firefighting floor setting when received a fire signals.
operation position of the car, the elevator will return to base station to resume normal operation.
Control the elevator running slow speed as per selected direction with the up/down buttons in the car top
07 Automatic base landing At automatic mode, if there is no call signal and exceed preset time, elevator return to base station. 36 Inspection operation inspection box or close/open button to control the door which makes the maintenance safer and easier
Door reopening by
08 Door will be open again if the same direction landing call button is pressed. 37 Flexible car park set The landing stop could be set as per clients requirements.
landing call

Torque compensation For a better riding experience, system will analyze the load in starting time, compensate the torque 38 Delayed door opening If pressed delayed opening button, the door will be open in longer time (timing adjustable) then door close.
09 in starting accordingly.
Direct Parking Human Machine Interface
10 Technology Micro-processor can calculate the best speed curve based on destination and landing directly.

39 Floor mark customization Special floor mark could be customized as per requirements.
Safety Functions
40 Arrival chime Arrival chime will make a sound when the elevator is arriving at each floor

11 Safety loop protection If elevator break down, system would report preset error code for easy maintenance.

Power supply
Emergency Functions
12 If power supply phase loss or phase error, safety circuit disconnect, elevator stops.
feedback detection
41 Alarm button Passengers can inform the outside in time by pressing the car alert button under special circumstance
13 Overload protection If the elevator is overloaded, buzzer will ring, door keeps opening and elevator cannot start.
42 Emergency car lighting Emergency lighting inside will be on in case of power failure.
System will transmit infrared ray cross lines at entrance which is responsive to all bodies or goods, open
14 Door safety light curtain the door to protect passenger safety. Intercom realized 5 party conversations among car COP, pit, car top, machine room and monitoring
43 Five station intercom center (decide by client). Clients are supposed to supply a wire from monitoring center to the first floor.
15 Reverse force protection If there is reverse force exceed preset value to the opening door, door will reopen. Specification: 4x0.75mm2 (distance less than 1800 meters)

16 Door Interlock protection Elevator can move only if the car door and landing door is closed normally. Once receive the fire signal, elevator will cancel all call and registration signals and go straight to
44 Fire Emergency Landing firefighting station and door keeps open to evacuate the passengers. The elevator will be resumed after
the fire signal is removed by authority.
17 Non-landing protection The door would not open at non-landing stop for safe purpose.
When the safety gear, oil buffer, upper limit switch, lower limit switch and governor switch are active, can
Downward over Elevator downward speed is bigger than specified speed, governor is active, electrical safety circuit 45 Emergency rescue activate emergency rescue function inside the control cabinet which makes the elevator move up or
18 speed protection disconnect and safety gear will stop the elevator at guide rail. down at slow speed for passengers rescue.

Upward over speed Elevator upward speed is bigger than specified speed, governor is active, electrical safety circuit
19 protection disconnect and brake will stop the elevator. Energy saving functions
20 Reverse movement Guard Once the actual running direction is reverse as instructed, stop and alarm immediately.
Parking service When the key switch at specific floor is active, the elevator will return to the locking floor and then switch
46 into sleeping state after responding all the callings
Monitor brake relay signal all the time, if the actual status is not same as instructed, system will stop the
21 Break guard
elevator
Energy saving mode If there is no any operation signals and the door is closed for a preset time, the elevator will switch to
47 energy saving mode, turn off the lights and fans inside the car
Contactor guard Once the contactor is in abnormal state, system will stop the elevator no matter it is in standby or
22 working state.

23 Terminal speed switching If elevator runs to terminal at abnormal speed, system will force speed switching to ensure safety operation.
Additional functions
Buffer guard When elevator is crossing the floor end for a certain reason, elevator will be buffered and safety circuit
24 disconnected.
Microprocessor If the elevator is interrupted, system will scan the controller input and output point, elevator will stop
25 48 Voice announcement Voice announciator will announce in English or Chinese when the elevator arriving at station
self-check protection running if anything abnormal found.
When the power is interrupted suddenly while in normal operation, UPS is active immediately, driving the
26 Anti-lock of motor When elevator traction motor got stuck and cannot move, after a specific time, system will stop the elevator. 49 UPS
elevator to nearest floor at slow speed and open the door for evacuation

Fault storage Computer will save the elevator fault record for factory or technicians analysis. When the elevator door is closing, if passengers pressed the safety edge, the door stops closing and
27 50 Door safety edge reopen to prevent the passengers from injury.
When the brake failed and leads to an unintended movement of elevator, the three-phase winding of After received the fire signal and automatically returned to the firefighting floor, the system can give a
the PM synchronous motor will be in short circuit and turn to power generation state. It makes the 51 Fireman's operation signal to the management center, elevator will stay at firefighting floor waiting for fireman operation.
28 Star closure method elevator running at speed of 0.1 m/s so that eliminates the risk of high-speed slipping to ensure the
safety of passengers 52 Anti-collision bumper panel Install 300mm high bumper panel at wall bottom to protect the wall from fork lift collision.
Rope Anti-loose The hoisting rope is under real-time detection during the elevator operation and when single or multiple
29 Protection 53 Sub-COP Convenient for all the passengers inside the car to give instructions to travel to desired floor.
hoisting ropes are detected slack, the elevator will stop immediately
Electronic Weighing Electronic weighing accurately measures the weight of car in each landing stop and transmit the signal
30 Device
54 Anti-collision angle iron Install angle iron at landing door entrance to protect the door jamb.
to the control system in order to achieve the anti-nuisance, full load by-pass and overload protection
55 Remote monitoring system If elevator breaks down, system will generate sms and email to designated personnel for easier management.

11 12
Shaft section layout

Machine room height MH


ATLAS ME Technical Specification

No. Specifications 1000 1500 2000 3000

01 Load(kg) 1000 1500 2000 3000

02 Speed(m/s) 0.5 0.5 0.5 0.5

03 Control method Full selective collection

Overhead OH
04 Driving method VVVF driving

05 Door operator VVVF control

Opening height HM
06 Motor type PMSM gearless motor

07 Control system CTRL80

08 Communication Serial Communication

Car size
09 1400*1600*2200 1600*2100*2200 1800*2300*2200 2100*2700*2 20 0 2100*2700*2200
(W*D*H)
Door opening size Side opening Side opening Side opening Panels CO Side opening Panels CO Side opening
10
(W*H) 1400*2100 1400*2100 1600*2100 1600*2100 1800*2100 1800*2100 1800*2100
Single Shaft layout
2500*2100 2600*2600 3000*2800 3000*2800 3200*3200 3300*3200 3400*3000
Shaft size opening

Opening height HM
11
(W*D) Dual
2500*2100 2600*2600 2800*2800 3000*2800 3250*3200 3400*3200 3450*3000
opening

12 Rise ≤45m ≤45m ≤45m ≤45m

Shaft depth D
Car depth CB
13 Motor location Above the shaft

Rise TR
14 Overhead 4200 4200 4200 4300

15 Pit depth 1500 1500 1500 1500

16 Motor rated power(kW) 4 6.3 7.1 11.7

Opening height HM
17 Rated current(A) 13 15 20 27

18 Rated starting current(A) 19.5 22.5 30 40.5 Opening width JJ

Brake voltage(V) Car Width CA


19 DV110V
Shaft width W
380V, 50Hz 3 phase 5 wires, zero and ground wire separate, refer construction drawings
20 Main power&cable size

Pit depth PD
3*6mm2+2*6mm 3*6mm2+2*6mm
2 2
3*6mm2+2*6mm
2 2 2
3*10mm +2*6mm

Note: Elevator below 3000kg is not suitable to get fork lift into the car for goods transportation.

13 14