PT PEMBANGKITAN JAWA BALI SERVICE

SIAP INTEGRATED MANAGEMENT SYSTEM


BOILER INSPECTION UNIT 1
PLTU BENGKAYANG - 2022
Description INSPECTION SECONDARY AIR FAN A
Equipment MOTOR SECONDARY AIR FAN
MEASUREMENT SHEET Document Number
Issued 21 Desember 2021
Task No. : Revision : Section : Electrical
WO No. : Page : Date : 02 Februari 2022

TYPE : YKK4005-4 TH PHASE : 3 PHASA


POWER : 400 KW S/N :
VOLTAGE : 6000 V CLASS : F
CURRENT : 47,8 A FREQ : 50 HZ

SPECIAL ID : BEFORE CLEANING & HEATING


STATOR MOTOR SECONDARY AIR FAN A
Note :
Waktu
R - N (MΩ) S - N (MΩ) T - N (MΩ) - Insulation Resistance value according with
(menit)
IEEE 43-2000 :
1 (IR) 85.6 84.7 85.6
- If 1 minute ins. Resistance is above 5000 M ohm
2 87.1 84.9 87.1 the calculated PI may not be meaningfull.

3 89.5 85.2 89.5

4 89.9 86.8 89.9


Thermal class min PI
Class A 1.5
5 92.1 89.3 92.1
Class B 2
Class F 2
6 92.4 92.1 92.4
Class H 2

7 94.7 94.5 94.7


min IR (MΩ) Test Specimen
rated kV+1 Winding before 1970
8 94.9 95.7 94.9
most DC armature, Form Wound coil
100
after1970
9 95.6 95.9 95.6
random wound machines & form
5
wound coil below1kV
10 96.1 96..2 96.1

Insulation resistance test


PI 1.1 1.1 1.1 Winding rated volt (V)^a
direct voltage (V)
<1000 500
1000-2500 500-1000
2501-5000 1000-2500
5001-12000 2500-5000
>12000 5000-10000

reference IR rotor (1menit) >100 M ohm

Result : Normal

ACCEPTED / REWORK / REPLACE


RECOMMENDATION
NOTE : Testing was conducted on the condition of the rotor inside the stator
(by Quality Control)

Measuring Tool:

PT. PLN UPDK SINGKAWANG PT. PJB SERVICES


Description
Reviewed & Approved by Checked by Inspected by

Signature

Name Syahru Ramadhan Randi Hadi


Position
Approval Date
PT PEMBANGKITAN JAWA BALI SERVICE
SIAP INTEGRATED MANAGEMENT SYSTEM
BOILER INSPECTION UNIT 1
PLTU BENGKAYANG - 2022
Description INSPECTION SECONDARY AIR FAN A
Equipment MOTOR SECONDARY AIR FAN
MEASUREMENT SHEET Document Number
Issued 21 Desember 2021
Task No. : Revision : Section : Electrical
WO No. : Page : Date : 02 Februari 2022

TYPE : YKK4005-4 TH PHASE : 3 PHASA


POWER : 400 KW S/N :
VOLTAGE : 6000 V CLASS : F
CURRENT : 47,8 A FREQ : 50 HZ

SPECIAL ID : AFTER CLEANING & HEATING


STATOR MOTOR SECONDARY AIR FAN A
Note :
Waktu
R - N (MΩ) S - N (MΩ) T - N (MΩ) - Insulation Resistance value according with
(menit)
IEEE 43-2000 :
1 (IR) 1220 1342 1264
- If 1 minute ins. Resistance is above 5000 M ohm
2 1386 1498 1468 the calculated PI may not be meaningfull.

3 1498 1510 1501

4 1552 1821 1679 min PI


Thermal class
Class A 1.5
5 1572 1993 1810 2
Class B
Class F 2
6 1710 2182 1991 2
Class H

7 1881 2320 2182


min IR (MΩ) Test Specimen
rated kV+1 Winding before 1970
8 2010 2498 2372
most DC armature, Form Wound coil
100
after1970
9 2110 2549 2543
random wound machines & form
5
wound coil below1kV
10 2460 2756 2678

Insulation resistance test


PI 2.0 2.0 2.1 Winding rated volt (V)^a
direct voltage (V)
<1000 500
1000-2500 500-1000
2501-5000 1000-2500
5001-12000 2500-5000
>12000 5000-10000
reference IR rotor (1menit) >100 M ohm

Result : Normal

NOTE : Testing was conducted on the condition of the rotor inside the stator

ACCEPTED / REWORK / REPLACE


RECOMMENDATION
(by Quality Control)

Measuring Tool:

PT. PLN UPDK SINGKAWANG PT. PJB SERVICES


Description
Reviewed & Approved by Checked by Inspected by

Signature

Name Syahru Ramadhan Randi Hadi


Position
Approval Date
PT PEMBANGKITAN JAWA BALI SERVICE
SIAP INTEGRATED MANAGEMENT SYSTEM
BOILER INSPECTION UNIT 1
PLTU BENGKAYANG - 2022
Description INSPECTION CIRCULATING WATER PUMP A
Equipment MOTOR CIRCULATING WATER PUMP A
MEASUREMENT SHEET Document Number
Issued 09 Maret 2022
Task No. : Revision : Section : Electrical
WO No. : Page : Date : 04 April 2022

TYPE : 800LP-25 PHASE : 3 PHASA


POWER : 560 KW S/N :
VOLTAGE : 6000 V CLASS : F
CURRENT : 54 A FREQ : 50 HZ

SPECIAL ID : BEFORE CLEANING & HEATING


STATOR MOTOR CIRCULATING WATER PUMP A
Note :
Waktu
R - N (MΩ) S - N (MΩ) T - N (MΩ) - Insulation Resistance value according with
(menit)
IEEE 43-2000 :
1 (IR) 1500 1630 1690
- If 1 minute ins. Resistance is above 5000 M ohm
2 1540 1670 1750 the calculated PI may not be meaningfull.

3 1710 1810 1870

4 1820 1840 2200


Thermal class min PI
Class A 1.5
5 2310 2100 2280
Class B 2
Class F 2
6 2450 2280 2340
Class H 2

7 2570 2290 2390


min IR (MΩ) Test Specimen
rated kV+1 Winding before 1970
8 2790 2330 2510
most DC armature, Form Wound coil
100
after1970
9 2800 2480 2590
random wound machines & form
5
wound coil below1kV
10 2840 2620 2720

Insulation resistance test


PI 1.8 1.6 1.6 Winding rated volt (V)^a
direct voltage (V)
<1000 500
1000-2500 500-1000
2501-5000 1000-2500
5001-12000 2500-5000
>12000 5000-10000
reference IR rotor (1menit) >100 M ohm

Result : Normal

NOTE : Testing was conducted on the condition of the rotor inside the stator

ACCEPTED / REWORK / REPLACE


RECOMMENDATION
(by Quality Control)

Measuring Tool:

PT. PLN UPDK SINGKAWANG PT. PJB SERVICES


Description
Reviewed & Approved by Checked by Inspected by

Signature

Name Syahru Ramadhan Randi Hadi


Position
Approval Date
PT PEMBANGKITAN JAWA BALI SERVICE
SIAP INTEGRATED MANAGEMENT SYSTEM
BOILER INSPECTION UNIT 1
PLTU BENGKAYANG - 2022
Description INSPECTION CIRCULATING WATER PUMP A
Equipment MOTOR CIRCULATING WATER PUMP
MEASUREMENT SHEET Document Number
Issued 09 Maret 2022
Task No. : Revision : Section : Electrical
WO No. : Page : Date : 04 April 2022

TYPE : 800LP-25 PHASE : 3 PHASA


POWER : 560 KW S/N :
VOLTAGE : 6000 V CLASS : F
CURRENT : 54 A FREQ : 50 HZ

SPECIAL ID : AFTER CLEANING & HEATING


STATOR MOTOR CIRCULATING WATER PUMP A
Note :
Waktu
R - N (MΩ) S - N (MΩ) T - N (MΩ) - Insulation Resistance value according with
(menit)
IEEE 43-2000 :
1 (IR) 3120 3210 3200
- If 1 minute ins. Resistance is above 5000 M ohm
2 3510 3430 3980 the calculated PI may not be meaningfull.

3 3980 3690 4320

4 4200 4200 4590


Thermal class min PI
Class A 1.5
5 4930 4820 5610
Class B 2
Class F 2
6 5100 5080 5740
Class H 2

7 5450 5630 6110


min IR (MΩ) Test Specimen
rated kV+1 Winding before 1970
8 6210 6110 6310
most DC armature, Form Wound coil
100
after1970
9 6340 6280 6460
random wound machines & form
5
wound coil below1kV
10 6610 6440 6530

Insulation resistance test


PI 2.1 2.0 2.0 Winding rated volt (V)^a
direct voltage (V)
<1000 500
1000-2500 500-1000
2501-5000 1000-2500
5001-12000 2500-5000
>12000 5000-10000
reference IR rotor (1menit) >100 M ohm

Result : Normal

NOTE : Testing was conducted on the condition of the rotor inside the stator

ACCEPTED / REWORK / REPLACE


RECOMMENDATION
(by Quality Control)

Measuring Tool:

PT. PLN UPDK SINGKAWANG PT. PJB SERVICES


Description
Reviewed & Approved by Checked by Inspected by

Signature

Name Syahru Ramadhan Randi Hadi


Position
Approval Date