FPS-003 R1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

3mm. THK.

STEEL PLATE
RACKET SUPPORT
EXPANSION BOLT TO FIRE WATER TANK
(4.5kg.) PORTABLE FIRE EXTINGUISHER
(ABC, C02 OR DRY CHEMICAL TYPE) HORIZONTAL PIPE
(VERTICAL SIZE)
THIS CONTRACTOR BY ELECTRICAL WORKS
75 75

200
SCHEDULE OF PIPE BRACKET / BRACING POC

U-BOLTS W/ NUTS PIPE SIZE U-BOLT DIA. ANGLE BAR EXPANSION BOLT
& WASHER TO SPRINKLER & FHC
50 10 50x50 10

50
65 10 50x50 10
6MM.THK. 75 10 50x50 10
ANGULAR BAR

50
POC
100 12 65x65 12
WALL
(REFER TO ARCHITECTURAL DRAWINGS) EXPANSION BOLTS TO SPRINKLER & FHC

400
FLOW SWITCH
STEEL COLUMN
BY STRUCTURAL

ZONE-2

ZONE-1
SYSTEM PRESSURE GAUGE FROM FIRE PUMP
WORKS

PIPE BRACKET INDICATING TYPE CONTROL VALVE W/


FINISH FLOOR LINE INTERMIDIATE SUPPORT VICTAULIC COUPLING

75mm X 75mm X 6m STEEL TUBE


CONNECTION BETWEEN RAFTERS TO HEADER PIPE
BE PROVIDED BY THIS CONTRACTOR
WOOD STIFFNER
ELEVATION
FFL
FIRE EXTINGUISHER TYPICAL INSTALLATION CONCRETE WALL

SCALE NTS

18.1 [0.7131]
EXPANSION BOLTS 1

TO BE FILLED W/
BOTTOM OF BEAM VALVE STATION ASSEMBLY TYP DETAIL
NON-COMBUSTIBLE 50 50 SCALE NTS
MATERIALS PROPOSED 6MM.THK. 6MM.THK.
PIPE ANGULAR BAR ANGULAR BAR
FIN. FLOOR LINE 75 75

PROPOSED PIPE HORIZONTAL PIPE U-BOLT W/ NUTS HORIZONTAL PIPE


(VERTICAL SIZE) U-BOLTS W/ NUTS
50mm (MIN.)

PIPE SLEEVES (VERTICAL SIZE) & WASHERS


& WASHER
LATERAL BRACE
FIN. FLOOR LINE 4-WAY SWAY BRACE
5mm THK. STEEL FLANGE
WELDED TO PIPE SLEEVES
FOR CONCRETE ANCHORAGE

TO BE FILLED W/ PIPE SLEEVES


NON-COMBUSTIBLE
MATERIALS PROPOSED PIPE WATER FLOW SWITCH
6MM.THK.
1. SLEEVES SHALL BE PROVIDED AROUND ALL PIPING EXTENDING 6MM.THK.
ANGULAR BAR
THROUGH WALLS, FLOORS, PLATFORMS AND FOUNDATIONS. ANGULAR BAR SYSTEM PRESSURE
EXPANSION BOLTS
PROVIDE W/ FIRE GAUGE
2. THE CLEARANCE BETWEEN THE PIPE SLEEVES SHALL RATED SEALANT 'W'x'T' UNISTRUT VERTICAL PIPE HORIZONTAL PIPE BY ELECTRICAL WORKS
EXPANSION BOLTS INDICATING TYPE CONTROL
BE FILLED W/ NON-COMBUSTIBLE FLEXIBLE MATERIAL CLAMP OR APPROVED EQUAL (VERTICAL SIZE) VALVE W/ VICTAULIC
SUCH AS MINERAL WOOL, FIBERGLASS OR EQUIVALENT. TO BE FILLED W/ COUPLING
THIS CONTRACTOR
NON-COMBUSTIBLE 'W'x'T' UNISTRUT VERTICAL PIPE FLOW INDICATOR / SIGHT GLASS
3. MINIMUM CLEARANCE BETWEEN PIPE AND SLEEVES MATERIALS CLAMP OR APPROVED EQUAL
SHALL NOT BE LESS THAN 25mm FOR PIPE 25mm ISOLATION VALVE
THROUGH 75mm & 40mm FOR PIPE SIZE 100mm AND SECTIONAL
LONGITUDINAL BRACE POC
LARGER. FLOOR SLEEVES SHALL BE EXTENDED AT LEAST ELEVATION
HORIZONTAL PIPE
75mm ABOVE THE TOP OF THE FINISH FLOOR LEVEL. FIRE PROTECTION PIPE RISER TO SPRINKLER/FIRE HOSE CABINETS
(VERTICAL SIZE)
FROM VALVE STATION
4. FIRE STOPPING SHALL BE PROVIDED FOR PIPES PASSING
THROUGH FLOORS & FIRE RATED WALLS.
PIPE SUPPORT TYPICAL INSTALLATION ASSEMBLY

SCALE NTS
VALVE OR SIMILAR TO UNION W/ CORROSION
5. FIRE STOPPING SHALL HAVE THE SAME RATING AS THE RESISTANT ORIFICE
FIRE PROTECTION DRAIN PIPE RISER
PENETRATED FLOOR OR WALLS. TAP TO THE NEAREST STORM
DRAINAGE
ALEMITE FITTING (GIVING FLOW EQUIVALENT TO THE
PIPE SLEEVE TYPICAL INSTALLATION SMALLEST SPRINKLER ORIFICE OF THE
SYSTEM)
SCALE NTS HYDRANT CAP/ BONNET

FLAP VALVE/ CHECK VALVE CAP BOLTS & NUTS


BONDED TO ELECTRICAL
EARTHING CONDUCTOR
HOSE/ PUMPER NOZZLE RETAINING
SUPERVISORY VALVE ASSEMBLY TYP DETAIL
HYDRANT CAP "O" RING SCREW SCALE NTS

WITH CHAIN AND TREAD CAP


AND HEXAGONAL HEAD FOR
WRENCH (2 NOS.) UPPER BARREL/
NOZLLE SECTION NOZZLE CAP CHAIN
CHB OR R.C. WALL
UPPER STEM
STEM BREAK COUPLING
4-WAY FIRE DEPARTMENT
SECTION CONNECTION INLET WITH BREAKING RING/ TRAFFIC FLANGE
CAP AND CHAIN (2 HALVES)
1 LOOSE LIFTING HANDLE
PROVIDE ANGULAR
GRADE LEVEL BAR EDGING
150 1000 150

150
LOWER BARREL STEM BREAK COUPLING

4-WAY FIRE DEPARTMENT

150
DSP/ STANDPIPE/ FIRE HYDRANT CONNECTION INLET WITH LOWER STEM DRAIN VALVE
CAP AND CHAIN

VARIES
1
ELBOW BOLTS & NUTS(8)

1000
FLANGE CONNECTION
FROM HYDRANT MAIN
1500m

BONDED TO ELECTRICAL FIRE DEPARTMENT TO HYDRANT


EARTHING CONDUCTOR SCH 40 STORM DRAIN
CONNECTION LINE TO HYDRANT
STORM DRAIN
GRADE FLOOR LINE NEAREST STORM
MAIN VALVE DRAIN

150
ELBOW
BOTTOM PLATE 150 1000 150
PLAN RC WALL (REFER TO STRUCTURAL SECTION
DRAWINGS FOR DETAILS)

FIRE DEPARTMENT CONNECTION TYPICAL DETAIL FIRE HYDRANT TYPICAL DETAIL VALVE PIT BOX TYPICAL DETAIL
SCALE NTS SCALE NTS SCALE NTS

WATER TANK RELOCATION


1
AS PER CLIENT'S REQUIREMENT

FIRE PROTECTION SYSTEM 0 PRELIMINARY


FPS-003
TYPICAL DETAIL & INSTALLATION

00 - 00