IOLink Channels A and B Soft Failure with IOP
with IOLDRVER Status
ARTICLE NUMBER ARTICLE TYPE INITIAL DATE PUBLISHED DATE
000158600 Solutions March 17, 2022 March 17, 2022

PRODUCT
C200 on Experion PKS

QUESTION / PROBLEM:
IOLink Channels A and B Soft Failure with IOP with IOLDRVER Status

ANSWER / SOLUTION:
SOLUTION # 1-TNQ52B

Feedback
SUMMARY

IOLINK Channels A/B Failure showing Child IOPs with Ioldrver error

The IOLDRVER error, reported against IoLink Module, is IOLink-Driver-error.

IolDrver errors are reported against an IOP when the C300 senses that during a module's response, the EIA485
differential signals do not come within a minimum voltage range of the rails (-Vcc and +Vcc).

It is intended to detect and report marginal or damaged IOL drivers on IOMs before they deteriorate to a point where
they cause communication problems for the entire link

COMMON CAUSES

1) An IOP (hardware) itself could be faulty.

2) When inserting/removing the IOLink-cables, or removing/inserting the IOM could also caused the IODRVER error as
well as others( TknRecv, lpbckErr, etc).

3)+VE and COM screws for the IOTAs had come loose; This particular scenario could give intermittent channel failures

SOLUTIONS

1.- Replace Faulty Module (If Applicable)

2.- Errors due to insert/remove of cables/IOM can be ignored, but its error-counts must be manually Reset ( via I/O-Link
Command) and Enable-Periodic-Swap. Do not force swap/cable-select the IOLink-cable A/B, let it auto-swap after
Enable-Periodic-Swap. The IOLink auto periodic swap is every 1-minute.

3.- Check if +VE and COM screws for the IOTAs had come loose and make sure that they have been properly tighten

ADDITIONAL NOTES

For solution #2, follow steps below:

- From Station, Call IOLINK Processor Detail Display up

- Check error statistic from “Statistic tab”

- Make sure that Statistic error are not increasing

- Go back to Main tab and from IOLINK Command Field Select “RESET ERRORS”

- Go back to Statistic tab and Confirm that errors count have been set to 0 and no longer increasing

- Go back to Main tab and from IOLINK Command Field Select “ENB_PERSWAP”

- Wait till the Error Alarm is cleared off

Was this article helpful?


Feedback
COMPANY PARTNERSHIPS FOLLOW US
Let's About Us Channel Partners

Connect! Contact Us OEM

News Channel Partner Locator


Sign up to receive
Careers
exclusive
Commercial Policies
communications.  SITE SUPPORT

FAQs

SUBSCRIBE RELATED BUSINESSES Need Help

Thermal Solutions

Performix

Sparta Systems

Copyright © 2022 Honeywell International Terms & Privacy Do Not Sell My Personal Global
Cookies
Inc. Conditions Statement Information Unsubscribe

You might also like