Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

CHEYYAR CO-OP SUGAR MILLS LTD.

DELTAROTOTECH(P)LTD., (15MW CO-GEN POWER PLANT)


ANAKKAVOOR, CHEYYAR.
PROJECT: 15MW CO-GEN
Format No. :PWR-QAC-FT-835 /Rev 0
POWER PLANT
TEST REPORT FOR SYNCHRONISING Report No. : SUGAR
OWNER : CHEYYAR SUGAR MILL
RELAY (SKE11) MILL/MCSP/SKE11
CONSULTANT :
Date : 01/NOV/2022
DELTAROTOTECH(P)LTD.

LOCATION : Control Room


PANEL DETAILS/FEEDER NO : Metering Cum Sync Panel -1
VOLTAGE RATING : 11KV

1. Name Plate Details:


Report No : SUGAR MILL/MCSP/SKE11 Date : 01/11/2022
Panel Name : GRP-1 System Voltage : 11KV
Make :AREVA Serial no.: 31574576
Model :SKE11BF8012BCH
Rating Voltage: 63.51/110V AC Built-in rated auxiliary voltage (DC):110-125V DC
CT ratio: 1250 / 1 A PT ratio: 11 / 0.110 KV

2. Synchronising: (25)
%Differential Lockout: 2
Time: 1Sec

Applied Voltage(I) Applied Voltage (II) Relay Function


63.51V@0⁰ 63.51V@0⁰ Acted
63.51V@0⁰ 58.00V@0⁰ Not Acted
57.00V@0⁰ 61.00V@0⁰ Not Acted

Applied Hz(I) Applied Hz (II) Relay Function


50.0Hz 50.0Hz Acted
49.0Hz 47.0Hz Not Acted
50.0Hz 48.5Hz Not Acted

Result:
The Relay was tested and found its ok.

For M/s KE Global Services For Delta Rototech(p) Ltd For Cheyyar Co-operative Sugar Mill
Limited

Mr Dayalan
Testing Engineer

Page 1 of 1