Trox (U.K.

) Ltd
Caxton Way
GB-Thetford
Norfolk IP24 3SQ
Telephone +44 (0)1842 754545 Product Information
Telefax +44 (0)1842 763051
www.troxuk.co.uk Computer Room Floor Grille Type AFG
e-mail: trox@troxuk.co.uk PI/1/8.2/B/1

Type AFG
The very latest production procedures are used in the
manufacture of the AFG floor grille including the use of robotic
welding.

Materials
Grille face and border frame are from extruded aluminium
sections, mill finish as standard.
Optional finishes include natural anodise, black with linished face,
powder coated silver grey RAL 9006 or nylon coated black.
Rear assemblies made from formed sheet steel frame and
extruded aluminium blades, stove enamelled black (RAL 9005).
Description
The type AFG floor grille has been specifically developed for Dimensions
mounting in Raised Access Floors in such areas as Computer
Rooms, where load and damage resistance are of the utmost Nominal size A B C
importance.
Having a heavy duty construction, the AFG can replace 600mm 600 599 68.5 140 approx
square floor tiles to handle supply air or alternatively extract air.
Grille border depth can be specified to suit the type of floor
system used. A range of surface finishes is available. Can be
fitted with rear opposed blade damper assembly for air volume
flow control.

Type AFG-A / AG construction


90mm Maximum
Pedestal

A  O/A Grille
13mm Nominal Pitch 6mm
Detail
A
25

Detail A Typical Floor Plan View


X
B
C

Shims to suit
height required

Detail for variable pedestal height X Grille Replacing Floor Tile


Available X = 25 (Standard)
up to 50mm in 1mm steps
Product Information
Computer Room Floor Grille Type AFG
PI/1/8.2/B/1

Installation Technical Data


Shims are permanently fitted to the underside of the grille frame in
the area of the pedestal to provide the required depth between Table 1: Supply air
pedestal face and upper surface of flooring. These shims are
factory fitted, see detail ‘A’ for range of dimension ‘X’. V· (l/s)
Damper
110 165 220 275 330 385
Product Certification
The type AFG floor grille has been independently tested to the  ps (Pa) 1 2 3 5 7 10
performance specification:
Open veff (m/s) 1.0 1.5 2.0 2.5 3.0 3.5
PSA MOB PF2 PS/SPU March 1992, with the following results:
LpNR <15 <15 <15 <15 <15 15
Test Result
 ps (Pa) 2 3 5 8 10 15
Trimmed
Stability of deflection LpNR <20 <20 <20 <20 <20 20
(centre of grille):
Table 2: Extract air
4.5 kN static load through Deflection 23 hours after load
25mm square indentor applied - 3mm V· (l/s)
Deflection 24 hours after load Damper
applied - 3mm 220 275 330 385 440 500
0.09mm permanent
deformation  ps (Pa) 3 4 5 7 9 12
0.01mm permanent indentation Open
LpNR <20 <20 <20 <20 22 25
Impact load test:
 ps (Pa) 5 6 8 10 13 18
40 Kg Sand Bag from 1m Did not collapse Trimmed
LpNR <20 <20 <20 22 25 28
height

Dynamic rolling load test: Selection Guide


When the AFG floor grille is used in an area with high heat loads,
4.5 kN load 50 passes of wheel Did not collapse e.g. computer rooms, the grille should be located close to the
3 kN load 50 passes of wheel 0.40mm Vertical permanent heat source but away from any wall or partition.
deformation (max)
3 kN load 50 passes of wheel 0.20mm Horizontal permanent The recommended air volume per grille for a ceiling height of 3m
deformation (max) is between 140 and 220 l/s. For higher ceilings the flow can be
increased up to typically 300 l/s.
Safety load test
(centre of grille): The pressure drop across the type AFG floor grille should also be
considered in the selection process for a pressurised floor void
13.5 kN load through 25mm Did not collapse system.
square indentor
Further detailed selection can be obtained on request.

Nomenclature
V· in l/s : Volume flow rate

LpNR : NR rating assuming a room correction of 8dB


LpNR = LWNR - 8dB

LWNR : NR rating of sound power level

 ps in Pa : Static pressure drop

veff in m/s : Effective discharge velocity

2
Product Information
Computer Room Floor Grille Type AFG
PI/1/8.2/B/1

Specification Text
Heavy duty construction floor grille for supply or extract air.
Frames with welded mitred corners suitable for pedestal
mounting. Front profiled blade sections welded to frame.
Adjustable opposed blade damper fitted on request. Height
between pedestal face and face of grille to be selected with
permanently factory fitted shims as necessary.

Materials
Grille face and border frame are from extruded aluminium
sections, mill finish as standard.
Optional finishes include natural anodise, black with linished face,
powder coated silver grey RAL 9006 or nylon coated black.
Rear assemblies made from formed sheet steel frame and
extruded aluminium blades, stove enamelled black (RAL 9005).

Order Code

AFG - A / 600 x 600 / 0 / 35 / P4 / RAL 9005

Type Nominal Size Not used State Colour

Rear Assemblies
A = Face only
AG = Rear opposed blade damper Finishes
A1 = Mill Finish (standard)
A4 = Natural Anodised (25 microns)
P4 = Painted black and surface linished
P2 = Silver grey RAL 9006
N1 = Nylon coated black

Frame Depth (mm)


Design changes reserved · All rights reserved © Trox (U.K.) Limited (04/2002)

between face of grille and face of pedestal


25 standard
Optionally 26 - 50 in 1mm steps

Order Example AFG


Make: TROX
Type: AFG-AG/600 x 600/0/32/P4/RAL 9005