Professional Documents
Culture Documents
Raft 2
Raft 2
POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFT 2 REF
CODES BS 8007 / BS 8110 DESIGNED BY KUSHAN CHECKED BY MAHESH 10/08/2017
Reference Calculations Output
DESIGN INFORMATION
BS8110:1985 Material Properties
Characteristic strength of concrete, fcu = 35 N/mm2
Table 3.1 Characteristic strength of steel, fy = 460 N/mm2
Fig. 2.1 Young's modulus of concrete (Short term), Ec = 2.7E+04 N/mm2
Fig. 2.2 Young's modulus of steel (Short term), Es = 2.0E+05 N/mm2
Density of concrete, ρct = 24 kN/m3
Durability Requirement
Exposure condition = Severe
BS8007:1987
Clear cover to top r/f, = 50 mm
Clause 2.7.6
Clear cover to bottom r/f, = 75 mm
Thermal Requirement
BS8007:1987 Fall in temperature between the hydration peak and ambient,
T1 = 42 °C
Fall in temperature due to seasonal variations, T2 = 11 °C
Coefficient of thermal expansion of mature concrete, α = 1.0E‐05 oC‐1
A.5 & Fig A.3 Restraint factor, R = 0.5
Clause 2.2.3.3 Allowable crack width, cw = 0.2 mm
Critical steel ratio, ρ crit = 0.0035
Table A.1 Ratio of tensile strength to average bond strength
fct/fb = 0.67
between concrete and steel,
Base Slab Section Properties
Thickness of slab h = 700 mm
Length of slab ly = 3290 mm
Width of slab lx = 5500 mm
Reinforcement Properties
Reinforcement design width, bt = 1000 mm
T1 ‐ Span shortway top r/f ØT1 = T 16 bars
R/F spacing of T1 = 125 mm
B1 ‐ Support shortway bottom r/f ØB1 = T 16 bars
R/F spacing of B1 = 125 mm
T2 ‐ Span longway top r/f ØT2 = T 16 bars
R/F spacing of T2 = 125 mm
B2 ‐ Support longway bottom r/f ØB2 = T 16 bars
R/F spacing of B2 = 125 mm
DESIGN FORCES
Load Case : SUB_02_ULS_TANKFULL
BM, M [kNm/m] SF, V
DT, Ft [kN/m]
Direction Span Support [kN/m]
SLS ULS SLS ULS SLS ULS ULS
Reinforcement to Carry Bending Moment and Direct Tension at SLS
Bending moment in SLS, Ms = 20.00 kNm/m width
Direct tension in SLS, Fs,t = 200.00 kN/m width
(20 x 10^6)
Ms/Fth =
(200 x 10^3 x 700)
= 0.14
Distance to centre of reinforcements, a = Top cover + ØT1/2
= 50 + 16/2
= 58 mm
a1 = a/h
= 58/700
= 0.08
0.5(1‐2a1)2 = 0.5 x (1‐2 x 0.08)^2
= 0.3528
Ms/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
For Crack Width
Steel ratio, ρ1&2 = As/[bd]
= 1608/(1000 x 642)
= 0.00250
Ms Fts
Maximum steel stress, fs1 = +
2bthρ1[0.5h ‐ a] 2bthρ1
20 x 10^6 200 x 10^3
= +
2x1000x700x0.0025(0.5x700 ‐ 58) 2x1000x700x0.0025
= 76.57 N/mm2
1 Fts
Minimum steel stress, fs2 = ‐ ρ1fs1
ρ2 bth
1 200x10^3
= ‐ 0.0025 x 76.57
0.00250 1000 x 700
= 37.50 N/mm2
Distance from the compression face to crack width calculation point,
a' = Thickness of Element
= 700 mm
Strain due to stiffening effect between 2bth
ε2 =
cracks for 0.2mm crack width, 3EsAs
2 x 1000 x 700
=
3 x 200000 x 1608
= 1.5E‐03
Average strain, εm = ε1‐ε2
= 0.0E+00
Cmin = cover only
= 50 mm
acr = √[(125/2)^2+(700‐642)^2] ‐ 16/2
= 77 mm
Crack width, w = 3acrεm
= 3 x 77 x 0
= 0.00 mm w = 0 mm
Allowable crack width, Cw = 0.2 mm
Crack width due to direct tension is satisfactory Ok
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFT 2 REF
CODES BS 8007 / BS 8110 DESIGNED BY KUSHAN CHECKED BY MAHESH 10/08/2017
Reference Calculations Output
Reinforcement to Carry Bending Moment and Direct Tension at ULS
Bending moment in ULS, Mu = 30.00 kNm/m width
Direct tension in ULS, Fu,t = 267.00 kN/m width
(30 x 10^6)
Mu/Fth =
(267 x 10^3 x 700)
= 0.16
Distance to centre of reinforcements, a = Top cover + ØT1/2
= 50 + 16/2
= 58 mm
a1 = a/h
= 58/700
= 0.08
2
0.5(1‐2a1) = 0.5 x (1‐2 x 0.08)^2
= 0.3528
Mu/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
Reinforcement to Carry Bending Moment and Direct Tension at SLS
Bending moment in SLS, Ms = 23.00 kNm/m width
Direct tension in SLS, Fs,t = 200.00 kN/m width
Ms/Fth = (23 x 10^6)/(200 x 10^3 x 700)
= 0.16429
Distance to centre of reinforcements, a = Bottom cover + ØB1/2
= 75 + 16/2
= 83 mm
a1 = a/h
= 83/700
= 0.12
0.5(1‐2a1)2 = 0.5 x (1‐2 x 0.12)^2
= 0.2888
Ms/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
For Crack Width
Steel ratio, ρ1&2 = As/[bd]
= 1608/(1000 x 617)
= 0.00261
Ms Fts
Maximum steel stress, fs1 = +
2bthρ1[0.5h ‐ a] 2bthρ1
23 x 10^6 200 x 10^3
= +
2x1000x700x0.00261(0.5x700 ‐ 83) 2x1000x700x0.00261
= 78.42 N/mm2
1 Fts
Minimum steel stress, fs2 = ‐ ρ1fs1
ρ2 bth
1 200x10^3
= ‐ 0.00261 x 78.42
0.00261 1000 x 700
= 31.21 N/mm2
Distance from the compression face to crack width calculation point,
a' = Thickness of Element
= 700 mm
Crack width, w = 3acrεm
BS8007:1987
= 3 x 95 x 0
Clause B.5
= 0.00 mm
Mu/Fth = (33 x 10^6)/(267 x 10^3 x 1000)
= 0.1236
Distance to centre of reinforcements, a = Bottom cover + ØB1/2
= 75 + 16/2
= 83 mm
a1 = a/h
= 83/700
= 0.12
0.5(1‐2a1)2 = 0.5 x (1‐2 x 0.12)^2
= 0.2888
Mu/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
Shear stress, v = Vu/bvd
BS8110:1985
= (60x10^3)/(1000x617)
Clause 2.5.5.2
= 0.1 N/mm2
100As/bd = (100x1608)/(1000x617)
= 0.26062 < 3
BS8110:1985
→ Ok
Table 3.9
Conditions to
400/d = 400/617
Satisfy
= 0.6483 < 1
→ Not Ok use value 1
Design shear stress, vc = 0.79[100As/bd]1/3[400/d]1/4[fcu/25]1/3/γm
BS8110:1985
= {0.79[0.26]^(1/3)x[1]^(1/4)x[35/25]^(1/3)}/1.25
Table 3.9
= 0.45 N/mm2
Shear enhancement factor for a section at a distance d from support,
BS8110:1985
= 2d/av
Clause 3.4.5.10
= 2
Enhanced design shear vc = 0.45 x 2
stress, = 0.90321 N/mm2
Shear stress at support is satisfactory Ok
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFT 2 REF
CODES BS 8007 / BS 8110 DESIGNED BY KUSHAN CHECKED BY MAHESH 10/08/2017
Reference Calculations Output
Span in longway ‐ Top Face
Assume T16 @ 125 C/C reinforcement provided in span longway
Effective depth, d = h ‐ top cover ‐ ØT1 ‐ ØT2/2
= 700 ‐ 50 ‐ 16 ‐ 16/2
= 626 mm
Reinforcement to Carry Bending Moment and Direct Tension at SLS
Bending moment in SLS, Ms = 30.00 kNm/m width
Direct tension in SLS, Fs,t = 322.00 kN/m width
(30 x 10^6)
Ms/Fth =
(322 x 10^3 x 700)
= 0.13
Distance to centre of reinforcements, a = Top cover + ØT1 + ØT2/2
= 50 + 16 + 16/2
= 74 mm
a1 = a/h
= 74/700
= 0.11
2
0.5(1‐2a1) = 0.5 x (1‐2 x 0.11)^2
= 0.3042
Ms/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
For Crack Width
Steel ratio, ρ1&2 = As/[bd]
= 1608/(1000 x 626)
= 0.00257
Ms Fts
Maximum steel stress, fs1 = +
2bthρ1[0.5h ‐ a] 2bthρ1
30 x 10^6 322 x 10^3
= +
2x1000x700x0.00257(0.5x700 ‐ 74) 2x1000x700x0.00257
= 119.77 N/mm2
1 Fts
Minimum steel stress, fs2 = ‐ ρ1fs1
ρ2 bth
1 322x10^3
= ‐ 0.00257 x 119.77
0.00257 1000 x 700
= 59.31 N/mm2
Distance from the compression face to crack width calculation point,
a' = Thickness of Element
= 700 mm
Strain due to stiffening effect between 2bth
ε2 =
cracks for 0.2mm crack width, 3EsAs
2 x 1000 x 700
=
3 x 200000 x 1608
= 1.5E‐03
Average strain, εm = ε1‐ε2
= 0.0E+00
Cmin = Top cover only
= 50 mm
acr = √[(125/2)^2+(700‐626)^2] ‐ 16/2
= 88 mm
Crack width, w = 3acrεm
= 3 x 88 x 0
= 0.00 mm w = 0 mm
Allowable crack width, Cw = 0.2 mm
Crack width due to direct tension is satisfactory Ok
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFT 2 REF
CODES BS 8007 / BS 8110 DESIGNED BY KUSHAN CHECKED BY MAHESH 10/08/2017
Reference Calculations Output
Reinforcement to Carry Bending Moment and Direct Tension at ULS
Bending moment in ULS, Mu = 42.00 kNm/m width
Direct tension in ULS, Fu,t = 452.00 kN/m width
(42 x 10^6)
Mu/Fth =
(452 x 10^3 x 700)
= 0.13
Distance to centre of reinforcements, a = Top cover + ØT1 + ØT2/2
= 50 + 16 + 16/2
= 74 mm
a1 = a/h
= 74/700
= 0.11
2
0.5(1‐2a1) = 0.5 x (1‐2 x 0.11)^2
= 0.3042
Mu/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
Reinforcement to Carry Bending Moment and Direct Tension at SLS
Bending moment in SLS, Ms = 6.00 kNm/m width
Direct tension in SLS, Fs,t = 322.00 kN/m width
Ms/Fth = (6 x 10^6)/(322 x 10^3 x 700)
= 0.02662
Distance to centre of reinforcements, a = Bottom cover + ØB1 + ØB2/2
= 75 + 16 + 16/2
= 99 mm
a1 = a/h
= 99/700
= 0.14
0.5(1‐2a1)2 = 0.5 x (1‐2 x 0.14)^2
= 0.2592
Ms/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
For Crack Width
Steel ratio, ρ1&2 = As/[bd]
= 1608/(1000 x 601)
= 0.00268
Ms Fts
Maximum steel stress, fs1 = +
2bthρ1[0.5h ‐ a] 2bthρ1
6 x 10^6 322 x 10^3
= +
2x1000x700x0.00268(0.5x700 ‐ 99) 2x1000x700x0.00268
= 92.35 N/mm2
1 Fts
Minimum steel stress, fs2 = ‐ ρ1fs1
ρ2 bth
1 322x10^3
= ‐ 0.00268 x 92.35
0.00268 1000 x 700
= 79.58 N/mm2
Distance from the compression face to crack width calculation point,
a' = Thickness of Element
= 700 mm
Crack width, w = 3acrεm
BS8007:1987
= 3 x 109 x 0
Clause B.5
= 0.00 mm
Mu/Fth = (9 x 10^6)/(452 x 10^3 x 700)
= 0.02845
Distance to centre of reinforcements, a = Bottom cover + ØB1 + ØB2/2
= 75 + 16 + 16/2
= 99 mm
a1 = a/h
= 99/700
= 0.14
0.5(1‐2a1)2 = 0.5 x (1‐2 x 0.14)^2
= 0.2592
Mu/Fth < 0.5(1‐2a1)2 Therefore the section has Tension only
Shear stress, v = Vu/bvd
BS8110:1985
= (85x10^3)/(1000x601)
Clause 2.5.5.2
= 0.14 N/mm2
100As/bd = (100x1608)/(1000x601)
= 0.26755 < 3
BS8110:1985
→ Ok
Table 3.9
Conditions to
400/d = 400/601
Satisfy
= 0.66556 < 1
→ Not Ok use value 1
Design shear stress, vc = 0.79[100As/bd]1/3[400/d]1/4[fcu/25]1/3/γm
BS8110:1985
={0.79[0.27]^(1/3)x[1]^(1/4)x[35/25]^(1/3)}/1.25
Table 3.9
= 0.46 N/mm2
Shear enhancement factor for a section at a distance d from support,
BS8110:1985
= 2d/av
Clause 3.4.5.10
= 2
Enhanced design shear vc = 0.46 x 2
stress, = 0.91116 N/mm2
Shear stress at support is satisfactory Ok
PROJECT POLGAHAWELA, POTHUHERA AND ALAWWA INTEGRATED WATER SUPPLY PROJECT
STRUCTURE INTAKE PUMP STATION ELEMENT RAFT 2 REF
CODES BS 8007 / BS 8110 DESIGNED BY KUSHAN CHECKED BY MAHESH 10/08/2017
Reference Calculations Output
Reinforcement to Resist Shrinkage and Thermal Movement in Immature Concrete
BS8007:1987 Assume continuous constructions without movement joints [Option ‐1]
Table 5.1
BS8007:1987 Critical steel ratio, ρcrit = 0.0035
Table A.1
BS8007:1987 Ratio of tensile strength to average
fct/fb = 0.67
Table A.1 bond strength between concrete and
steel,
BS8007:1987 Restraint factor, R = 0.5
Clause A.5
BS8007:1987 Maximum crack spacing, smax = [fct/fb][Ф/2ρ]
Clause A.3 Maximum crack width, wmax = smaxRα[T1+T2]
BS8007:1987 Maximum allowable crack width, wmax = 0.2 mm
Clause 2.2.3.3
Required steel ratio based on the [fct/fb]Rα[T1+T2]Ф
ρ =
areas of surface zone, 2wmax
[0.67]x0.5x1.0E‐05[42+11]Ф
=
2x0.2
= 0.00040 Ф
For shortway Direction (span) ρ1 = 0.0004x16
= 0.0064 > ρcrit → Ok
For shortway Direction (support) ρ2 = 0.0004x16
= 0.0064 > ρcrit → Ok
For longway Direction (span) ρ3 = 0.0004x16
= 0.0064 > ρcrit → Ok
For longway Direction (support) ρ4 = 0.0004x16
= 0.0064 > ρcrit → Ok
Therefore Required minimum steel area
As,req = 0.0064x250x1000
of surface zone in shortway support
= 1600 mm2/m width
Therefore Required minimum steel area
As,req = 0.0064x250x1000
of surface zone in longway support
= 1600 mm2/m width