Protection Relays

NG10
GENERATOR PROTECTION RELAY
RESTRAINED DIFFERENTIAL
FOR GENERATORS / MOTORS / SHORT LINES
APPLICATION
The relay type NG10 provides sensitive, high operating speed and selective differential protection against phase-
to-phase and phase-to-ground short circuits of motors/generators or short lines.

NG10

74CT

52
- Protective & control functions
74TCS BF

50N/51N-87NHIZ Residual overcurrent


or high impedance restricted ground fault
side H
G side L
87G-M-L 64REF Biased restricted differential ground fault
87G-M-L Double slope biased differential
for generators, motors and short lines
74CT BF Breaker Failure
74CT Side H CTs monitoring
74CT Side L CTs monitoring
50N/51N 87NHIZ 64REF 74TCS Trip circuit supervision
Nota: 50N/51N in alternativa a 87NHIZ

Id

Id1=(K2/100) ∙ IS - Q

Id>>

TRIP Id1 = (K1/100) ∙ IS

NO TRIP
Id>
α1 α2
0 Is
-Q

NG10 - Flyer - 10-2021