Professional Documents
Culture Documents
Exercicis GEO
Exercicis GEO
GENERAL CONCEPTS
EJEMPLO 1
2 2
A=ᴨ· r =ᴨ· 65 =13273,22 mB) Total wind turbine height
C) Tip speed
2ᴨ m
v=ω·r =14 · · 65=95,29
60 s
EJEMPLO 2
2 2
A=ᴨ· r =ᴨ· 65 =13273,22 m2) Tip speed
2ᴨ m
v=ω·r =14 · · 65=95,29
60 s
4) Rated power
1 1
P=C p · · ρ·A· V 3=0,4 · · 1· 13273· 113=3,53 MW
2 2
5) Power with a wind speed 5, 7, 9 and 13 m/s (Cp = 0.4)
1 3
P=C p · · ρ·A· V
2
1
P=0,4 · · 1· 13273 ·53 =0,33 MW
2
1 3
P=0,4 · · 1· 13273 ·7 =0,91 MW
2
1 3
P=0,4 · · 1· 13273 ·9 =1,93 MW
2
1
P=0,4 · · 1· 13273 ·133 =5,83 MW
2
5
Power [MW]
0
4 5 6 7 8 9 10 11 12 13 14
Wind speed [m/s]
EJEMPLO 3
Calculate rotor speed (low speed) at 0%, 25%, 50%, 75% and 100% of rated power.
- Constant speed WT (Eco62) P=1300 kW
- Generator 2P / 50 Hz ωs = 1500 rpm
- Gearbox ratio: 81,05
Slip
−0,009 · P [KW ]
Slip [ % ] =
100
−0,009 · 0
Slip [ % ] = =0 %
100
−0,009 ·325
Slip [ % ] = =−0,2925 %
100
−0,009 ·650
Slip [ % ] = =−0,585 %
100
−0,009 · 975
Slip [ % ] = =−0,8775 %
100
−0,009 ·1300
Slip [ % ] = =−1,17 %
100
Generator speed
ω=Slip·ω s +ω s
Rotor speed
ω
ω r=
Gr
1500
ω r= =18,51 rpm
81,05
1938,75
ω r= =23,92 rpm
81,05
2377,5
ω r= =29,33 rpm
81,05
2816,25
ω r= =34,75 rpm
81,05
3255
ω r= =40,16 rpm
81,05
Tabla de resultados:
Power [KW] Slip [%] Generator speed [rpm] Rotor speed [rpm]
0 0 1500 18,51
325 -0,2925 1938,75 23,95
650 -0,585 2377,5 29,33
975 -0,8775 2816,25 34,75
1300 -1,17 3255 40,16
EJEMPLO 1
( ) ( )( hz ) ( 0,03 )
100
ln ln
m
V ( h )=V ( href )· =10· =13,96
ln ( ) ln ( )
h ref 10 s
z 0,03
(
( )
0,25 )
100
ln
m
V ( h )=10 · =16,24
ln ( )
10 s
0,25
3) Roughness length = 1 m
( ) ( 1001 ) =20 m
ln
V ( h )=10 ·
ln ( )
10 s
1
EJEMPLO 2
Determine
(Uc ) (89 )
k 2
− −
Q { U ≥U 1 } =e =e =0,45 %
2) The probability of the wind speed between >= 3 m/ and < 25 m/s.
( 39 )
2
−
Q { 3 ≥U 1 } =e =0,89 %
( )
2
25
−
Q { 25 ≥U 1 } =e
9
=0,0004456 %
Q { 25 ≥3 }=0,89−0,0004456=0,89 %
( 69 )
2
−
Q { 6 ≥ U 1 }=e =0,6411 %
( )
2
10
−
Q { 10 ≥U 1 } =e
9
=0,29 %
h any=24 ·365=8760 h
m
Numero de horas a 6 =0,6411 · 8760=5616,74 h
s
m
Numero de horas a 10 =0,29 · 8760=2548,81 h
s
EJEMPLO 1
Determine the curve Cp versus tip speed ratio (0 to 16), and with T = 0, 3, 6, 10, 15 & 24º
1 1 0,035
= − =0,805.
β 1+0,08 ·3 1+33
(
C p ( 1,3 ) =0,6 · 128 ·0,805−0,6 · ( 0,805
1
) · 3−0−8)· e
−20 ·0,805
=5,6 · 10−6 ≅ 0
·
Todos los resultados más la gráfica representando el valor de Cp para cada grado:
CP(0º)
Cp(3º)
Cp(6º)
Cp(10º)
Cp(15º)
Cp(24º)
0.000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
EJEMPLO 2
- 3.2 MW WT
- Rotor D = 100 m
- Ngb = 80 based on an induction generator
- 960 V; 50 Hz (2 pair of poles)
- p= 1,225 kg/m3.
Neglecting slip (assuming s = 0). Calculate the mechanical power generated for wind speeds of
5, 8, 11 and 14 m/s
60 · f 60 · 50
n= = =1500 rpm
p 2
2ᴨ 2ᴨ rad
ω=n· =1500 · =157,08
60 60 s
ω·R
λ=
Vw
157,07 · 50
λ 1= =19,63
5 · 80
157,07· 50
λ= =12,27
8· 80
157,07· 50
λ= =8,92
11· 80
157,07· 50
λ= =7,01
14 · 80
C p=0,0045 · ( 100−( λ−10 )2 )
1 3
Pw = · ρ·A· V w ·C p
2
1 2 3
Pw 1= · 1,225· ᴨ· 50 · 5 ·0,036=19603 W
2
1
Pw 2= · 1,225· ᴨ· 502 · 83 · 0,43=1051148 W
2
1
Pw 3= · 1,225· ᴨ· 502 · 113 · 0,44=2847989 W
2
1 2 3
Pw 4 = ·1,225 · ᴨ·50 · 14 ·0,41=5409916W
2
EJEMPLO 3
- P = 6000 kW
- n = 11,5 rpm
GFC WT:
F= 50 kN/m2
Rgear= 34,78
R=0,5 m
V? Y L?
2ᴨ rad
ω g=399,97· =41,88
60 s
P 6000· 103
V g= = =1,43 m3
2· ω g · F 2 · 41,88 ·50000
Vg 1,432
Lg = 2
= 2
=1,823 m
ᴨ·r g ᴨ·0,5
DD WT:
F= 50 kN/m2
Rgear= 1
R=3,5 m
V? Y L?
2ᴨ rad
ω g=399,97· =1,2
60 s
P 6000 · 103 3
V g= = =49,82 m
2· ω g · F 2 ·1,2 · 50000
Vg 49,82
Lg = 2
= 2
=1,294 m
ᴨ·r g ᴨ·3,5
2.3 MW, 690 V, 50 Hz squirrel cage induction generator (SCIG) is used in a fixed-speed wind
energy system. The SCIG is directly connected to the grid of 690 V 50Hz. The generator
parameters are given in Table B. At a given wind speed, the SCIG operates at the rated speed
of 1512 rpm. Using the induction generator equivalent circuit, determine the following:
rad
w s=2 · ᴨ·f =2 · ᴨ·50=314,16
s
2ᴨ 2ᴨ rad
w m=n m · =1512 · =158,33
60 60 s
n s−n m 1500−1512
s= ·100= · 100=−0,8 %
ns 1500
rad
w r= (1−s ) · w s= ( 1−(−0,008 ) ) · 314,16=316,67
s
B)
2 1−d
Pm=3· Rr · I r ·
d
√ √
3
Pm 2334 · 10
I r= = =2030,92 j A
1−d −3 1− ( −0,008 )
3· Rr · 3· 1,497 · 10 ·
d −0,008
C)
Pm 2334 · 103
T m= = =14,74 kNm
wm 158,33
D)
2 2 −3
Pcu , r=3· I r · R r=3 · 2030,92 · 1,497 ·10 =18523 W
E)
P 2,3 M
η= ·100= · 100=98,54 %
Pm 2,334 M
F)
Resultados en la tabla.
- a) The rotor mechanical and electrical speeds, and load impedance value.
- b) The dq-axis and rms stator currents.
- c) The dq-axis and rms stator voltages.
- d) The mechanical power and torque.
- e) The stator winding loss and power factor.
- f) The stator active and reactive powers, and generator efficiency.
A)
60· f 60 · 11,25
n m= = =22,5 rpm
p 30
2ᴨ rad
w m=22,5 · =2,356
60 s
rad
w r=wm · p=2,356 ·30=70,68
s
−3
Z L =RL + j X L=0,19125+ j 70,68· 1,3104 · 10 =0,2125∠25,84 º Ω
B)
−3
V ds =R L · i ds−w r · L L · i qs=0,19125 · 1448−70,68 ·1,3104 · 10 · 1087=176,4 V
V s =Z L ·i s =0,2125 ·1242,9=264,7 V
D)
2 −3 2
Pcu, s=3 · Rs · I s ·cos ( φ )=3 · 0,73051· 10 ·1288 · cos ( 0,8967 ) =3,635 kW
F)
Ps 884,4 · 103
η= ·100= · 100=95,19 %
Pm 929,07· 10
3
EJEMPLO 1
V rect =V n− j·ω·L· I s−R· I s
rad
ω=2 ᴨ·f =2 ᴨ· 50=314,16
s
Fase a:
−3
V rect ( a )=400 ∠ 0 º− j·314,16 · 0,1· 10 ·50 ∠25 º−2 ·50 ∠25 º=313,1 ∠−8 º V
Fase b:
V rect ( b )=400 ∠−120º − j· 314,16 · 0,1 ·10−3 · 50 ∠−95º −2· 50 ∠−95º =313,1∠−128 º V
Fase c:
−3
V rect ( c )=400 ∠120º − j· 314,16 · 0,1· 10 · 50∠ 145 º−2 · 50∠ 145 º=313,1∠−112º V
EJEMPLO 2
Dos a nivel de VSC con SVPWM
Considere un inversor de fuente de tensión de dos niveles. El inversor está conectado a una
carga RL trifásica equilibrada, y su tensión de CC es 1,220 V. El inversor está modulada por
SVPWM. La frecuencia de conmutación del convertidor es 720 Hz. En una instancia de tiempo
dado, la referencia de tres voltajes de fase V * a, v * b y v * c se encuentran para ser 398,37 V,
145,81 V, y -544,18 V, respectivamente. Determinar lo siguiente:
a) Los componentes α-beta de las tensiones de referencia de tres fases.
b) El ángulo del vector de voltaje de referencia y el número de sector.
c) El vector de voltaje de referencia y el índice de modulación.
d) los tiempos de permanencia.
e) Tres vectores espaciales fijas que se utilizan para sintetizar el vector de voltaje de referencia.
a)
V α =398,37 V
V β=398,37 V
b)
Phi:
phi=tan
−1
( )
Vβ
Vα
=tan (
−1 398,37
398,37 )
=45 º
Sector: 1
c)
V ref =V α +V β j=398,37+398,37 j=563,37∠ 45 º
Índice de modulación:
√ 3 ·V ref √ 3· 563,38
m a= = =0,8
V dc 1220
d)
·sin ( )=785,67 µs
1 ᴨ
d =m · T · sin ( θ )=0,8 ·
2 a s
720 4
1
d 0 =T s−d 1−d 2 = −287,57 µ−785,67 µ=315,64 µs
720
e)
2 −j0 2 −j0
V 1= · V dc · e = ·1220 · e =813,33V
3 3
ᴨ ᴨ
2 j 2 j
V 2= · V dc · e 3 = · 1220 ·e 3 =813,33∠ 60º
3 3
V 0=0
EJEMPLO 3
Consider a grid-connected two-level VSC with voltage-oriented control (VOC). The inverter is
connected to the grid of 690V 50Hz and delivers 2.3 MW to the grid with unity power factor
operation. The inverter is modulated by an SVM scheme with modulation index of 0.8 and
operates under steady-state conditions. The line inductance Lg is 0.1098 mH. To simplify the
analysis, all the harmonics produced by the inverter are neglected. When the grid voltage
vector angle θgis -45ºC, determine the following:
1) The instantaneous three-phase grid voltage and currents.
2) The grid voltage angle.
3) The dq-axis grid voltages and currents.
4) The active and reactive powers delivered to the grid (using dq-axis grid voltages and
currents).
5) The dc-link voltage and corrent
1)
V 690
V g= · √2= · √ 2=563,38 V ( peak )
√3 √3
2 · P g 2· 2,3 ·106
ig = = =2721,6 A (peak )
3 · v g 3· 563,38
φ g=180 º
( −ᴨ4 )=398,37V
v ag =v g · cos ( ωg · t ) =v g · cos ( θ g ) =563,38· cos
( −ᴨ4 −ᴨ)=−1924,5 A
i ag=i g · cos ( ω g ·t−φg ) =i g · cos ( θ g−φ g )=563,38 · cos
(
i cg =i g · cos ω g ·t−φg +
2ᴨ
3) (
=i g · cos θg −φ g +
2ᴨ
3
=563,38 ·cos )
−ᴨ
4
−ᴨ+ (
2ᴨ
3 )
=−704,42 A
2)
v α =v ag=398,37V
√3 √3
v β = · ( v ag+ 2· v bg ) = · ( 398,37+2 ·−544,19 )=−398,37 V
3 3
3)
2 2
v dg = ·¿¿ · ¿
3 3
−2
v qg= ·¿
3
−2
·¿
3
2 2
i dg= · ¿¿ · ¿
3 3
−2
i qg= ·¿
3
−2
·¿
3
4)
3 3 6
Pg = · ( v dg i dg+ v qg i qg ) = · ( 563,38 ·−2721,6+ 0 )=−2,3 · 10 W
2 2
3 3
Q g= · ( v qg i qg + v dg i dg ) = · ( 0−0 ) =0 VAR
2 2
5)
V dc = √
2 · V √ 2 ·690
= =1220V
ma 0,8
Pg −2,3· 106
I dc = = =−1855,6 A
V dc 1220