Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

OIL AND NATURAL

Client: GAS CORPORATION


ADDITIONAL PROCESS LIMITED
UNITS
L&T, E&C
DIVISION

Contractor : Larsen & Toubro Limited, Doc. No. : 5015-LT-00-EL-04-CA-0003


E&C DIVISION, Mumbai Rev. : 00

CAPACITOR SIZING CALCULATION

OWNER : OIL AND NATURAL GAS CORPORATION LIMITED, URAN

UNIT : ADDITIONAL PROCESS UNITS

L&T JOB NO. : 5015

DOC. CATEGORY: A R I REVIEW CODE

1 REVIEWED, NO COMMENTS.WORK TO PROCEED.


DOCUMENT STATUS
1st 2nd 3rd
REVIEWED AS COMMENTED. WORK SHALL
□ FINAL FOR CODE – 1 □ AS BUILT 2 PROCEED WITH FABRICATION / MANUFACTURING
TAKING CARE AND INCORPORATING OWNER /PMC
COMMENTS.
COMMENTS (IF ANY):
MAJOR NON CONFORMANCE AND DEVIATIONS TO
3 CONTRACT SPECIFICATIONS. RESUBMIT FOR REVIEW
AFTER INCORPORATING COMMENTS.

I RETAINED FORINFORMATION / RECORDS.

ONGC/PMC

DATE REVIEWED BY

00 24.11.10 Issued for Review SA RH


HOD PEM
PREPARED CHECKED
REV. DATE DESCRIPTION APPROVED
BY BY
BY
LARSEN & TOUBRO LIMITED DOCUMENT NO.
E&C DIVISION
5015-LT-00-EL-04-CA-0003
CAPACITOR SIZING
CALCULATION REVISION : 00
PROJECT : Additional Process Units

CUSTOMER : ONGC, URAN PAGE : 2 OF 4

CONTENTS

SECTION PAGE

1. Scope...........................................................................................................................3

2. Reference Documents................................................................................................. 3

3. Capacitor sizing calculation.........................................................................................3

4. Conclusion....................................................................................................................4
LARSEN & TOUBRO LIMITED DOCUMENT NO.
E&C DIVISION
5015-LT-00-EL-04-CA-0003
CAPACITOR SIZING
CALCULATION REVISION : 00
PROJECT : Additional Process Units

CUSTOMER : ONGC, URAN PAGE : 3 OF 4

1. SCOPE
The scope of this document covers capacitor sizing calculation to be installed in APU Substation for Uran APU
project.

2. REFERENCE DOCUMENTS

Engineering Design Basis Electrical : V002-00-50-50-DB-001, Rev 1

Design Philosophy for Electrical Facilities : 6-51-0099 Rev 04

Job Specification Electrical : V002-00-50-50-SP-02-0

Overall Electrical Load Analysis : 5015-LT-00-EL-03-CA-0001 Rev 0

Overall key single line Diagram : 5015-LT-00-EL-00-SL-0002 Rev 0

3. CAPACITOR SIZING CALCULATION

The kW and kVA loading on the HV switchboards HT-201 under normal running load as per overall electrical
load analysis are as follows

NORMAL RUNNING LOAD/ MAXIMUM DEMAND LOAD


KW KVAR KVA P.F.
21244.6 11378.7 24100 0.881

The present power factor of 6.6kV bus is calculated as cos Ø1 = (kW/kVA) = 21244.6/24100=0.881
The required Power Factor as per ITB is 0.9. Hence cos Ø 2 = 0.9
Total MW considering 15% future load growth = 21.2446* 1.15 = 24.43 MW

Capacitive MVAR = MW * (tan (cos-1(cos Ø1))-tan (cos-1(cos Ø 2)))


= 24.43 * (tan (cos-1(0.881))-tan (cos-1(0.9)))
= 24.43 * (0.537-0.484)
= 1.295 MVAr
LARSEN & TOUBRO LIMITED DOCUMENT NO.
E&C DIVISION
5015-LT-00-EL-04-CA-0003
CAPACITOR SIZING
CALCULATION REVISION : 00
PROJECT : Additional Process Units

CUSTOMER : ONGC, URAN PAGE : 4 OF 4

4. CONCLUSION

The total capacitor bank rating shall be 1.295 MVAR. The capacitor bank on each bus section of HT -201 shall
be selected as 650 KVAr.