BUILDING ENVELOPE
Walls 8” Concrete Blocks, three oval care
½” Cement Plaster
2” Sand Aggregate
Light Color (Dirty White)
Glass No Shade
Ordinary Glass
White Powder Coated
Ceiling 8” Concrete Block (Sand Aggregate)
5/8” Gypsum Plaster (Sand Aggregate)
Floor 8” Sand and Gravel Aggregate
5/8” Plaster Cement (Sand Aggregate)
Door Aluminum Framed Swing Glass Door
White Powder Coated
INTERNAL LOADS
Lighting 56 Fluorescent bulb (12W)
Occupants 58 people
Use of Space Multi-Purpose Building (Office)
EXTERNAL DIMENSIONS
No. of floors 2
Ceiling Height 13’
N & S walls 39.36’
W & E walls 59.04’
Door Area South 6.56’ x 8.036’
Ceiling Area 59.04 x 39.36
Floor Area 59.04 x 39.36
SURVEY ESTIMATE
LIGHTINGS
LIGHTING 1ST Floor
Room No. of Types of Wattage Sensible Total Heat Load
Lights Bulbs Factor (BTU/hr)
Office 1 4 Fluorescent 12W 4.25 204
Office 2 4 Fluorescent 12W 4.25 204
Office 3 4 Fluorescent 12W 4.25 204
Office 4 4 Fluorescent 12W 4.25 204
Lobby 2 Fluorescent 12W 4.25 102
Hallway 5 Fluorescent 12W 4.25 255
Women’s 2 Fluorescent 12W 4.25 102
Room
Men’s Room 3 Fluorescent 12W 4.25 153
Stairs 1 Fluorescent 12W 4.25 51
Total 29 1479