Professional Documents
Culture Documents
Report
Report
Report
INTRODUCTION
1.1 GENERAL
Ever since 1970s, new seismic design approaches have allowed architectural engineers
to design new facility with the goal of foreseeable and ductile behaviour in major earthquake,
preventing catastrophe and death. Nevertheless, some regulated damage is expected, and
excessive tremors may cause the facility to be destroyed beyond economic repair. Due to
development of technological advances and superior components, seismic protection of
structures has evolved dramatically in recent years. It was only lately recognised around the
world that it is feasible to build cost-effective buildings that can withstand severe earthquakes
with minimal or no extensive damage. Buildings can be designed in one of two ways to avoid
irreversible damage in earthquake shaking: base isolation or damage-resistant architecture.
Isolation system necessitates the separation of the structure from the floor by energy-dissipating
isolation equipment. This is tried-and-true technology that may add some to the tower's original
cost, but will save money in the long run. Damage-resistant architecture is rapidly evolving in a
range of shapes. There are a range of energy dissipation device connected to the structure in
various ways, including rocking walls or rocking frameworks with or without post-tensioning.
If it's not already the case, damage-resistant design for new construction will soon be no more
expensive than regular architecture.
A columns are vertical element that starts at the ground levels and transfers load to the
floor. A floating columns are vertical element that relies on a beam, which is a horizontal part,
at its ground position. Structures with pillars that hang or float on beams at an intermediary story
and do not reach the foundations have load transfer path irregularities.
The pressure is then transferred to additional columns underneath the beams. The load
was regarded a point load in such column. The preceding Earthquake data has provided adequate
evidence related to the behaviour of many kinds of constructions under various seismic
circumstances, and foundations issues have become a topic of interest for researchers and
technicians. This has resulted in a variety of novel ways for preserving facilities from seismic
damage. One of the most current strategies is Base Separation. The primary goal of base isolation
1
is to provide flexible and energy dispersion by integrating isolated devices known as isolators
between both the foundation and tower. Under earthquake excitations, base isolation effectively
separates the structure from the earth. Isolators systems at the base of the building will use an
elastic layer to permit related displacements between the foundations and the edifice. The
introduction of an isolation layer extends the building's basic time period.
Several designs use hovering columns, particularly just above bottom floor when
transferring girders are used, to create greater empty area on the bottom floor. Those open areas
can be needed for a venue or parking. Transferring girders must be correctly planned and
specified, particularly in seismic zone. On the beam that sustains it, the pillar is a concentrate
load. In terms of analysis, the column is generally presumed to be fixed at the base and hence
treated as a point load on the transferring beam. This type of architecture can be analysed using
STAAD Pro, ETABS, and SAP2000. Although drifting columns are capable of carrying gravity
loads, the transferring girder is of suitable size (stiffness) and have very little deformation.
2
Several images of structures built with floating pillar.
3
Fig.1.2 Palestra in London, United Kingdom
4
1.3 BASE ISOLATION CONCEPTS
The main idea behind earthquake resistance is to shield a building from the devastating
impacts of a quake by installing a necessary flexibility that isolates the building from the
earthquake motion. Between both the structure and the foundation, the base isolation introduces
a layer of low lateral stiffness. This isolation layer gives the architecture a substantially longer
natural period than its predetermined base natural period. The pseudo-acceleration, and thus the
seismically force in the building, can be reduced by extending the duration. The base isolator in
structures shields the structure against seismic force in two ways: by diverting vibration forces
and by absorbing it. The earthquake energy is dispersed by rendering the building's foundation
flexible (rather than fixed) in transverse direction, thereby lengthening the building's basic period
of time.
5
6
CHAPTER 2
REVIEW OF LITERATURE
Pratyush Malaviya, et,al (2014) [1] The major goal of this study is to a columns are vertical
element that starts at the ground levels and transfers load to the earth. A floating column is
a vertical element that relies on a beam that is a horizontally component at its level lower
(termination Level) due to architecture condition. The load is then transferred to other
columns below the beams. Many designs use drifting columns, particularly above the
ground floor when transfer girders are used, to create greater open space on the bottom floor.
These open areas can be needed for an assembly hall or storage. Transferring girders must
be correctly planned and specified, particularly in seismic zone. On the beam that supports
it, the columns is a concentrate load. In terms of analysis, the columns is generally presumed
to be pinned at the base and hence treated as a point load on the transferring beams. The
study of this type of structure can be done with STAAD Pro V8I. Although drifting columns
are capable of carrying gravity loads, the transferring girder must be of suitable size
(stiffness) and have very little deformation.
Sunil Shirol , et,al. [2015][2] In this several of the structures that are damaged by tremors
are severely damaged. As a result, it is vital to protect structures from earthquakes. Isolation
system is an example of a technique for preventing structural damage. Base isolation works
on the premise of separating substructure from superstructure. A G+6 storey model with
and without masonry infill is investigated in this study. Isolators with lead rubber bearings
and friction types were employed. A single diagonal strut was used to simulate the infill.
ETABS-2016 is used to do static and response spectrum analysis. According to the findings,
providing isolators increased the natural time period, eliminating the possibility of
recurrence. Because of the building's flexibility, the base shear and story drifts were greatly
reduced but the displacement increased. When infill activity was taken into account, the
base shear rose, whereas displacement and inter-storey drifting decreased
Jayashri Sarode, et,al (2016)[3] The major goal of the study is to metal composite beams
are widely utilised in architecture and bridge project. Beneath applied stresses, composites
beams are frequently subjected to bending and vertical shear. New models for dislocation,
storey shear, and storey drift must be created in order to design composites beams
7
uniformly. The drifting column is a vertical element that is supported by a beam and has no
foundations. The drifting column is supported by a R.C.C Beam Girder. The girder is shaped
like a beam, and the column load operates as a point load on that beam. The composites
beam is being used in the drifting column structure in this lecture presentation. So because
composites beam is exposed to a rc columns, we can take use of its strengths. Standard
structure, Floating column architecture with R.C.C Beam Girder, and Flotation column
framework with composite structures girder are the three main models compared in this
lecture. Etabs is used to carry out events that shaped.
S.B. Waykule, et,al. (2016)[4] Due to the lack of area, populace, and aesthetic and practical
needs, multi-story structures in metropolitan areas are now obliged to include column-free space.
Structures with one or more storeys are equipped with floating columns. In a structure built in a
seismic activity area, these drifting columns are extremely detrimental. The seismic forces that
emerge at various levels of a structure must be transmitted down the shortest route along the
elevation to the ground. A distortion or discontinuity in this load transfer path causes the building
to function poorly. The general shape, scale, and symmetry of a structure, as well as how seismic
forces are transported to the earth, have a significant impact on its behaviour during tremors.
During in the 2001 Bhuj earthquake in Gujarat, several buildings with an open fields story
designed for storage collapsed or were badly affected.
Isha Rohilla, et,al. [2016] [5] The purpose of this study was to investigate the due to the lack of
spaces, population, and aesthetic and practical needs, multi-story structures in metropolitan areas
are now obliged to include column-free space. Structures with one or more storeys are equipped
with floating columns. In a building constructed in a seismic activity area, these drifting columns
are extremely detrimental. The seismic forces that emerge at various levels of a structure must
be transmitted down the shortest route along the elevation to the bottom. A variation or
discontinuity in this load transfer path causes the structure to function poorly. The essential
location of floating columns in vertically irregular structures for zone II and zone V has been
studied in this study for G+5 and G+7 RC structures. The impact of the size of the beams and
columns that support the load of the floating column has also been considered. The results
generated using ETABS software were evaluated utilizing structural responses such as storey
drift, storey dislocation, and storey shear.
8
Sumana C V, et,al [2016] [6] In the present study, the structure frameworks on sloping ground
(hilly locations) are one of the elements that diminish the building's capacity because the ground
story columns are of varying heights, resulting in a combination of short and long columns.
Furthermore, if a project has an open fields story, it is frequently generated in buildings due to
client requirements or poor planning. If an earthquake hits this structure, it becomes much more
susceptible in catastrophic zones. The purpose of this comparison study was to see how
earthquake loads affected building frameworks on sloping land with fixed and isolated bases in
the hazardous zone. Conventional moment resistant frame calculation models were built in
SAP2000 as three-dimensional frames to carry out dynamically linear seismic analysis in
accordance with IS 1893 Part (I) -2002. The vertical and lateral stiffness of the lead rubber
isolator are developed for the building's maximum gravity load and design distortion, and values
were allocated for isolated models. This research could aid in determining the influence of
isolation system under earthquake excitation, as well as the effective level and stability of the
lead rubber isolator for various storey buildings with base isolation on various sloping terrain.
The results of the analysis demonstrate that the base shear and story acceleration values for the
base individual structure have decreased.
V. Harshitha, et,al. [2017][7] In recent study, much attention has been dedicated to structural
health monitoring mechanism research and innovation, with a focus on reducing wind and
seismic response of structures. Many vibration-control methods have been developed, including
passive, active, semi-active, and hybrid vibration control approaches. The tower's frequency
response is lower than both its fixed base frequency and the primary frequency of ground
movement, allowing it to stay essentially elastic during big earthquake. A passive vibration
control system is base isolation. The framework structure was subjected to free and induced
vibration analysis using the SAP 2000 v15.0.1 computer programme. The framework structure's
free vibration analysis results, such as time period, frequency, mode form, and modular mass
participation ratios, were discovered. The responsiveness of framed structures and the vibration
control effectiveness of framed structures utilising lead rubber bearings were determined using
forced vibration signals (non-linear time history analysis). In this work, isolation bearing are
used on both symmetric and asymmetric structures. Horizontal flexibility at the base aids in
proper energy dissipation at the base level, lowering the seismic demand of the edifice that must
be addressed during designing.
9
Atul N.Kolekar [2017][8] In the investigation, Prior earthquake history has shown that
constructions that are not adequately built and built with the requisite quality can cause major
harm. This fact has led to the necessity to secure the security of tall structures versus seismic
force, necessitating the use of seismic analysis to calculate earthquake responses in order to
construct seismic resistance buildings. Dynamic model of G+12 RC multi-story building frame
including Koyna and Bhuj earthquakes is performed out in the current work using reaction
spectrogram and time history assessment, and the responses of such buildings are compared
using SAP2000 program. Several appropriate criterion have been developed using two-time
histories (i.e. Koyna and Bhuj) (base shear, storey displacement, storey drift). Time history
analysis, rather than reaction spectrum analysis, is advised based on the findings since it more
precisely forecasts response of structures. For same structure, a pushover analysis is undertaken,
and the results show that the structure is seismic activity safe.
TUN MYINT AUNG, et,al [2018][9] In the investigation, evaluation, and designing of a four-
story reinforced concrete frame and its isolations in seismic zone 4, The study results will be
compared between both the fixed base condition and the isolated building condition as a
consequence of multi-direction earthquake motions such as horizontal and vertical earthquakes.
To begin, static analysis is employed to design the helical spring for a fixed base conditions due
to gravity unfactored force. Second, spectrum analysis is used only for horizontal earthquakes,
whereas time history analysis is used for both horizontal and vertical earthquakes. Furthermore,
a comparison of the analysis results at different levels of the building is shown, including forces,
deformations, drifting, accelerations, and shearing. Fixed base has a static period of 0.4 seconds.
The basis isolated period is increased to 0.8, I, and 1.2 seconds for design seismic levels,
according the base isolated idea. The outcomes, when compared to base isolated (1.2 sec) and
fixed base constructing, show that while the deformations of base isolated are greater than fixed
base, other seismographic reactions such as acceleration are substantially lower in base isolated
compared to fixed base, and base isolated has the ability to decrease member force of the
framework.
Shaikh Tabassum Sayyad [2018][10] In the investigation, the most crucial phase in seismic
design, as well as retrofitting a building, is estimating earthquake movements at the structure's
location. The movement in the foundations level of a structure is believed to be equal to ground
free field motion in traditional structural analytical techniques. This hypothesis holds true only
10
for constructions supported by rock or extremely stiff soils. Foundation movement is typically
distinct from free field motion for structures built on soft soils, and a rocking element produced
by support flexibility on horizontal foundations motion has been incorporated. The term "soil-
structure interactions" refers to the impact of the behaviour of the soil directly beneath and
surrounding the foundations on the reaction of the soil-structure under static or dynamic stresses.
A foundations is the interaction between the superstructure and the underlying soil or rock. Only
the vertical loads of the structure must be transferred to the supporting rock under static
conditions. In a seismic setting, the stresses exerted on a foundation by a structure during seismic
excitation can much surpass the stable vertical loads, causing uplift; there will also be horizontal
forces and perhaps motion at ground levels. The soil and rock at the location have unique
properties that can greatly amplify the incoming earthquake motions from of the seismic waves.
11
CHAPTER 3
OBJECTIVES
The present study is an effort towards analysis of the floating column of structure with
& without isolators. In the current study, 2 structures ranging from 10 storeys and 15 storeys are
taken. The number of bays will be kept as 5 along x direction and 5 bays along the y direction
and the bay size will be kept as 4m with the storey height being 3m by using Etabs 2016 software.
1. To achieve the most effective structure for lateral resisting we have considering the 10 and
15 storey structure which is located at the medium soil strata and determine which of the
models considered for seismic action is the most susceptible.
2. By using this research we are determining the performance of the high rise structure when
subjected to the lateral load of with and without base isolators and identifying the most
suitable location of the floating column in the structure.
3. For all geometrical configuration, the effectiveness of concrete buildings of a rc columns
with and without isolators in terms of base shear, story displacement, drift, and time period
is determined.
12
CHAPTER 4
METHODOLOGY
4.1 CONFIGURATION OF BUILDING
The present study is an effort towards analysis of the floating column of structure with
& without isolators. In the current study, 2 structures ranging from 10 storeys and 15 storeys are
taken. The number of bays will be kept as 5 along x direction and 5 bays along the y direction
and the bay size will be kept as 4m with the storey height being 3m by using Etabs 2016 software.
Three dimensional space frame analysis will be carried out for four different building
configurations for different type of bracings are used in steel structures.
SL NO. PARAMETERS
01 X-direction Bays. 5
02 Y-direction Bays. 5
03 Size of bays along x-direction 4m
04 Size of bays along y-direction 4m
05 Height of the structure 10 & 15 storied
06 Height of each story 3m
07 Software used ETABS 2016
08 Analysis Linear Static Method
09 Soil Medium Soft Soil
10 Zone for Analysis Zone V
11 Seismic Factor 0.36
12 Column Size 850mm X 1000mm
13 Slab Thickness 150mm
14 Beam C/S Dimensions 250mm X 550mm
13
4) Floating column without isolators of 15 Storied structure.
5) Floating column at corner with isolator of 10 storied structure.
6) Floating column at corner without isolator of 10 storied structure.
7) Floating column at corner with isolator of 15 storied structure.
8) Floating column at corner without isolator of 15 storied structure.
4.2 SOFTWARE
Etabs 2016 was used to create this programme. ETABS is a computer programme
designed exclusively for the construction industry. And over 35 years ago [R. W. Clough, et al.,
1963], the conception of special purpose programmes for building type structures was
established. Nevertheless, as engineers implement nonlinear static and dynamic analysis and
leverage the increased computational power currently available to generate larger, more
sophisticated analytical model, the demand for special purpose programmes like ETABS was
never higher.
ETABS allows you to create and change models, run analyses, design, and optimise
designs all from a single platform that is completely integrated into Microsoft Windows. It is
simple to create graphical representations of the findings, including real-time representations of
time-history dispersion. It's also simple to generate printed output, either to a printing or to a file,
for selected or all items. This programme represents a quantum leap ahead in the creation,
modification, analysis, and design of models.
ETABS' analytical skills are as impressive, reflecting the most recent advances in
numerical approaches and solution techniques.
4.3 MODELING
14
Fig 4.1 Units Definition
Choose the units as kilo Newton – metre before beginning to build the model (kN-m). The
number of calls in the X and Y axis should then be mentioned. In both the X and Y axis, provide
the separation.
15
4.3.2 Storey Data Definition
The Planning Grid System and Storey Definition form are used to define Storey data. To specify
the storey data, choose one of the 2 choices in the Storey Parameters Area of the form:
Basic Storey Data: To determine the amount of stories and a standard storey height used
for all storeys levels, input values in the edit boxes. The programme gives each storeys
level a default name (for example, Storey 1, Storey 2, and so on) and makes assumptions
about how similar storey levels are.
Custom Floor Information: To view the Floor Data form, select this option and click the
Modify Floor Data link. Fill in the Floor Data field in your own storey names, non-
uniform height storey levels, and customised storey similarities.
When you use the Edit menu > Edit Storey Data > Edit Storey command, the Storey Data
form also displays.
16
permutations, are among the entities accessible through the Define menu. Several of those
instances can be specified during the assignment action using the Assign menu, and others do
not require any prior identification of an object.
After creating the model, define material properties. For defining material properties
select the define menu > Material properties command and then click Add new material. In
material select property as concrete, steel, masonry or rebars based on their purpose. Also select
the grade of concrete, steel and rebar to be used
Define material parameters once the model has been created. Choose the create menu >
Material properties option, then select Add new material to specify properties of materials. Based
on the objective, choose a material such as concrete, steel, masonry, or rebars. Choose the
concrete, steel, and rebar grades as well.
17
Fig 4.5 Characteristic of Material
4.3.4 Frame properties Defininition
The attributes of beams, columns, and other line objects are covered in this section.
18
After you've defined the frames characteristics, click Add Rectangular and provide the size, type,
and columns information. The similar technique is followed for beams as well. Choose steel
angle or other steel parts as needed for bracing.
Both slab and wall components are included in the shells portion. The slabs are given
membrane-like behaviour to produce in-plane rigidity. Rigid diaphragms are used to represent
the slab portions.
19
Fig 4.8 Slab Details Defininition
The barrier portions of masonry walls have membranes behaviour, while the wall
portions of shear walls have shell behaviour.
Drawing is being used to add new things to the design or to make changes to specific
items. Beams, columns, slabs, decks, walls, and other points, line, and area elements are
examples of items. To drawing, the software must be in Draw Mode, which can be accessed
using toolbar's draw buttons or the Draw menu option. Objects like columns, beams, and floors
can also be drawn individually, as discussed in the following sections.
Ensure the Plan View is turned on. Just use Draw menu > Draw Beam/Column/Brace
Objects > Create Columns in Regions or at Clicks function, or use the Generate Columns in
Regions or at Clicks button. Left click once during the Plan View at the junction of the grid
points wherever you want the column after reviewing the parameters in the Attributes of Object
box. In the Plan View, a rectangle-shaped columns must emerge at that location. Place the
remaining columns in the same technique.
20
Fig 4.10 Columns Assigning
4.3.6.2 Draw Beams
Assure the Plan View is turned on. Use the Drawing menu > Draw Beam/Column/Brace
Components > Generate Lines in Regions or at Clicks function, or the Create Lines in Location
or at Clicks button. Left click once during the Plan View on a grid line in which a beam is to be
positioned after reviewing the settings in the Attributes of Object box. All along specified grid
line, a beam is created. Place the remaining beams in the same technique.
21
Fig 4.11 Beams Assigning
Ensure the Plan View is turned on. Choose the Drawing menu >Draw Floor/Wall Objects
> Drawing Areas command from the Sketch menu. To start the floor/area object at a columns,
left clicking on it once. Then, as you move all around circumference of the flooring object,
clicking once at each intersection of adjacent columns to draw the tower's outline. To finish the
floor, use the Enter key on your keypad.
22
Fig 4.12 Floors Assigning
The user defines a range of structural loads, such as dead, live, earthquake, and wind
loads, using the application. The loads are then distributed to multiple architectural objects in
the mode by the client.
23
4.3.8 Cases of Static Load
Dead loads, live loads, floor loads, and seismic loads are all examples of static loads.
Assuming that the building's self-weight is the dead load. The building's live load is assumed to
be 3kN/m2. The live load on the rooftop is estimated to be 1.5kN/m2.
24
Fig 4.15 Details of Load Case
Those load combinations are predicated on reliability conditions and drawn from IS
875(Part5)-1987. Because it includes all scenarios, the standard load combinations can also be
used for design purposes.
25
Fig 4.16 Load Combinations Defininition
26
Click on Define – select the section property – click on link support properties – provide all the
properties of the damper
In the plan view go to base of the structure and select the all the joints in the base and the isolator
to the joints.
27
4.5 DIFFERENT MODELS CONSIDERED ELEVATION AND 3D VIEW.
28
Fig 4.17 10 Storied Bare Frame Model
29
Fig 4.17 10 Storied Model with Floating Column at Middle.
30
Fig 4.18 10 Storied Model with Floating Column at Corner.
31
CHAPTER 5
RESULTS AND DISCUSSION
The performance of each simulation is documented in this section, and the findings are
summarised. For the corresponding static technique, the modification of systemic parameters
such as tale laterally displacement, story drift, Storey stiffness, Storey stiffness, natural time
period, and base shear has been investigated. All of the simulations' outcomes are examined,
and the most appropriate model is chosen by reviewing the outcomes of each scenario.
5.1 DISPLACEMENT OF STORY
It is the overall displacement of the ith story with regard to the floor, with a maximal
allowable limit set forth in the IS regulations for structures.
The equivalent linear method (EQS) lateral deformations for G+20 storeys tall designs
are provided in the figures below in both X and Y axis.
5.1.1 Displacement of Storey for With Isolator and Without Isolator structure along X
and Y Direction
Table 5.1 Story Displacement for 10 Storied structures along X- Direction.
X-Directions
Storey Level Without Isolators With Isolators
10 45.584 56.622
9 43.475 54.563
8 40.323 51.376
7 1.60E+02 46.163
6 1.51E+02 40.133
5 1.41E+02 34.967
4 18.99 29.492
3 13.653 23.798
2 8.299 17.906
1 3.227 11.199
0 0 0
32
Storey Displacement along X-Directons of FC at Middle
12
10
8
Storey Level
Without Isolators
6
With Isolators
4
0
0 50 100 150 200
Displacement in mm
Fig.5.1 storey vs displacement for structure along X direction.
In the above graph we can observe that the maximal displacement occurs at the floating column
position i.e 160mm which is crossing maximum limit as seismic code and minimum displacement
is occurs at the bottom floor i.e 3.22 mm.
33
Storey Displacement along Y-Directons of FC at Middle
12
10
Storey Level
8
6 Without Isolators
With Isolators
4
0
0 50 100 150 200
Displacement in mm
Fig.5.2 storey vs displacement for structure along Y direction.
In the above graph we can observe that the maximum displacement occurs at the floating column
position i.e 170mm which is crossing maximum limit as seismic code and minimum displacement
is occurs at the bottom floor i.e 5.168 mm.
X-Directons
Storey Level Without Isolators With Isolators
15 84.748 61.396
14 82.031 60.316
13 78.321 58.601
12 73.654 56.157
11 68.172 53.057
10 61.952 49.378
9 53.691 44.345
8 45.105 39.062
7 38.222 34.56
6 31.227 29.941
5 24.65 25.394
4 18.296 20.782
3 12.212 16.153
2 6.758 11.505
1 2.273 6.496
0 0 0
34
Storey Displacement along X-Directons of FC at Middle
16
14
12
Storey Level 10
Without Isolators
8
With Isolators
6
0
0 20 40 60 80 100
Displacement in mm
Fig.5.3 storey vs displacement for structure along X direction.
In the above graph we can observe that the maximal displacement occurs at the top of the building
i.e 84.78mm which is within the maximum limit as seismic code and minimum displacement is
occurs at the bottom floor i.e 2.273 mm.
35
Storey Displacement along y-Directons of FC at Middle
16
14
12
Storey Level
10
8 Without Isolators
6 With Isolators
4
2
0
0 20 40 60 80 100 120
Displacement in mm
Fig.5.4 storey vs displacement for structure along Y direction.
In the above graph we can observe that the maximum displacement occurs at the top of the
building i.e 112mm which is within the maximum limit as seismic code and minimum
displacement is occurs at the bottom floor i.e 5.41 mm.
36
Storey Displacement along X-Directons of FC at Corner
12
10
8
Storey Level
6
4 Without Isolators
With Isolators
2
0
0 10 20 30 40 50 60 70
Displacement in mm
In the above graph we can observe that the maximal displacement occurs at the top of the building
i.e 45.51mm which is within the maximum limit as seismic code and minimum displacement is
occurs at the bottom floor i.e 3.178mm. the floating column at the corner is not effecting on the
displacement.
37
Storey Displacement along Y-Directons of FC at Corner
12
10
8
Storey Level
Without Isolators
4
With Isolators
2
0
0 10 20 30 40 50 60 70 80 90
Displacement in mm
38
Storey Displacement along X-Directons of FC at Corner
16
14
12
Storey Level
10
8 Without Isolators
6
With Isolators
4
2
0
0 20 40 60 80 100
Displacement in mm
In the above graph we can observe that the maximum displacement occurs at the top of the
building i.e 84.65mm which is within the maximum limit as seismic code and minimum
displacement is occurs at the bottom floor i.e 2.265mm. the floating column at the corner is not
effecting on the displacement.
39
Storey Displacement along Y-Directons of FC at Corner
16
14
12
Storey Level
10
8 Without Isolators
6
With Isolators
4
2
0
0 20 40 60 80 100 120 140
Displacement in mm
In the above graph we can observe that the maximum displacement occurs at the top of the
building i.e 118.49mm which is within the maximum limit as seismic code and minimum
displacement is occurs at the bottom floor i.e 5.391mm. the floating column at the corner is not
effecting on the displacement.
We can notice that dislocation increases as storey height rises by reviewing Table 5.1 to
Table 5.8 and analyzing their values in fig. 5.1 to 5.8. With the use of an isolation component
for the superstructure, we can clearly see a reduction in lateral movement.
From the obtained results we can say that structure with base isolator gives better
resistance for displacement and when you compare between the storey height, the 15 storied
structure gives the higher displacement when compare to the 10 storied structure.
5.2 STORY DRIFT
40
The storey drift acquired for 10 and 15 storeid all structure models in both the X and Y
directions is presented in the tables below for both Equivalent static.
5.2.1 Storey Drift for With Isolator and Without Isolator structure along X and Y Direction
Table 5.9 Story Drift for 10 Storied structures along X- Direction.
X-Directons
Without Isolators With Isolators
10 0.000703 0.000686
9 0.001051 0.001062
8 0.001362 0.001738
7 0.001876 0.00201
6 0.002135 0.001722
5 0.001738 0.001825
4 0.001779 0.001898
3 0.001785 0.001964
2 0.001691 0.002235
1 0.001076 0.003733
0 0 0
10
8
Storey level
Without Isolators
6
With Isolators
4
0
0 0.001 0.002 0.003 0.004
Drift
41
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.003733 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.000686. at the position of floating column the drift is increased.
Y-Directons
Without Isolators With Isolators
10 0.000609 0.000642
9 0.001079 0.001187
8 0.001451 0.002565
7 0.002116 0.002987
6 0.003002 0.00215
5 0.002121 0.00228
4 0.002174 0.002375
3 0.002209 0.002427
2 0.002188 0.002656
1 0.001723 0.006959
0 0 0
10
Storey level
6 Without Isolators
With Isolators
4
0
0 0.001 0.002 0.003 0.004 0.005 0.006 0.007 0.008
Drift
42
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.006959 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.000609. at the position of floating column the drift is increased.
X-Directons
Storey Level Without Isolators With Isolators
15 0.000907 0.000361
14 0.001237 0.000572
13 0.001556 0.000815
12 0.001835 0.00104
11 0.002089 0.001252
10 0.002754 0.001668
9 0.002863 0.001761
8 0.002295 0.001501
7 0.002332 0.00154
6 0.002192 0.001518
5 0.002121 0.001537
4 0.002029 0.001543
3 0.001818 0.001551
2 0.001499 0.001674
1 0.000758 0.002165
0 0 0
14
12
Storey level
10
8
Without Isolators
6
With Isolators
4
0
0 0.0005 0.001 0.0015 0.002 0.0025 0.003 0.0035
Drift
43
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.002165 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.000907 and at the position of floating column the drift is increased.
Y-Directions
Storey Level Without Isolators With Isolators
15 0.00071 0.000188
14 0.001187 0.000371
13 0.001623 0.000555
12 0.001993 0.000717
11 0.002343 0.000984
10 0.004067 0.001891
9 0.004316 0.001976
8 0.002914 0.001198
7 0.002977 0.001157
6 0.002869 0.001155
5 0.002817 0.001163
4 0.002784 0.00116
3 0.002561 0.001102
2 0.002396 0.001212
1 0.001804 0.002419
0 0 0
10
8
Without Isolators
6 With Isolators
4
2
0
0 0.001 0.002 0.003 0.004 0.005
Drift
44
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.002419 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.000188 and at the position of floating column the drift is increased.
10
8
Storey Level
Without Isolators
6
With Isolators
4
0
0 0.0005 0.001 0.0015 0.002 0.0025 0.003 0.0035 0.004
Drift
45
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.003701 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.000699 and at the position of floating column the drift is increased.
10
8 Without Isolators
Storey Level
With Isolators
6
0
0 0.001 0.002 0.003 0.004 0.005 0.006 0.007 0.008
Drift
46
In the above graph we can observe that the storey drift occurs at the bottom of the tower i.e
0.006942 which is within the maximum limit as seismic code and minimum drift is occurs at the
top floor i.e 0.001047 and at the position of floating column the drift is increased.
14
12
Storey Level
10
6 Without Isolators
4
With Isolators
2
0
0 0.0005 0.001 0.0015 0.002 0.0025 0.003 0.0035
Drift
47
In the above graph we can observe that the storey drift occurs at the floating column of the
building i.e 0.001963 which is within the maximum limit as seismic code and minimum drift is
occurs at the top floor i.e 0.000389 and at the position of floating column the drift is increased.
15 Without Isolators
Storey Level
With Isolators
10
0
0 0.001 0.002 0.003 0.004 0.005
Drift
48
In the above graph we can observe that the storey drift occurs at the floating column of the
building i.e 0.002415 which is within the maximum limit as seismic code and minimum drift is
occurs at the top floor i.e 0.001437 and at the position of floating column the drift is increased.
49
Storey Shear along X Direction of FC at Middle
12
10
Without Isolators
Storey Level
8
With Isolators
6
0
0 500 1000 1500 2000 2500
Storey Shear
50
Storey Shear along Y Direction of FC at Middle
12
10
Storey Level
8
Without Isolators
6
With Isolators
4
0
0 500 1000 1500 2000
Storey Shear
51
Storey Shear along X Direction of FC at Middle
16
14
12
Storey Level 10
8 Without Isolators
With Isolators
6
4
2
0
0 500 1000 1500 2000 2500 3000
Storey Shear
Fig. 5.23 Storey Shear in 15 storeys along X Direction
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column with isolators i.e 2315.8152 KN and
floating column without isolators is lesser storey shear 233.8035 KN.
52
2 1197.9288 2744.7091
1 1198.9977 0
0 0 0
10 With Isolators
8
6
4
2
0
-500 0 500 1000 1500 2000 2500 3000 3500
Storey Shear
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column with isolators i.e 2744.7091 KN and
floating column without isolators is lesser storey shear 168.1695 KN.
53
Table 5.25 Storey Shear in 10 Storeys along X Direction
Floating Column at Corner along X Directons
Storey Level Without Isolators With Isolators
10 429.8784 288.2333
9 902.5841 608.3444
8 1276.0799 840.5125
7 1539.5865 1006.5246
6 1723.0416 1146.0061
5 1858.3383 1244.8059
4 1951.7123 1308.0377
3 2004.2352 1343.6056
2 2027.5786 1359.4136
1 2033.4145 1363.3735
0 0 0
10 Without Isolators
8 With Isolators
Storey Level
0
0 500 1000 1500 2000 2500
Shear in KN
Fig. 5.25 Storey Shear in 10 storeys along X Direction
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column without isolators i.e 2033.4145KN and
floating column with isolators is lesser storey shear 288.2333 KN.
54
Table 5.26 Storey Shear in 10 Storeys along Y Direction
8 Without Isolators
With Isolators
6
4
2
0
0 500 1000 1500 2000
Shear in KN
Fig. 5.26 Storey Shear in 10 storeys along Y Direction
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column without isolators i.e 1571.2868 KN and
floating column with isolators is lesser storey shear 200.7176 KN.
55
Table 5.27 Storey Shear in 15 Storeys along X Direction
Floating Column at Corner along X Directions
Storey Level Without Isolators With Isolators
15 235.1853 453.1415
14 516.0878 844.0981
13 758.2945 1184.9584
12 964.6718 1471.3757
11 1138.086 1668.2927
10 1269.6996 1813.2361
9 1369.7892 1956.2301
8 1459.9618 2069.5155
7 1530.1874 2153.1443
6 1581.9832 2211.5857
5 1618.2269 2249.05
4 1641.5136 2270.3352
3 1654.7219 2279.9559
2 1660.6646 2282.3832
1 1662.1594 2284.3895
0 0 0
14
12
Storey Level
10 Without Isolators
8 With Isolators
0
0 500 1000 1500 2000 2500 3000
Shear in KN
56
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column with isolators i.e 2284.3895 KN and
floating column without isolators is lesser storey shear 235.1853 KN.
10
8
6
4
2
0
0 500 1000 1500 2000 2500 3000 3500
Shear in KN
57
In the above graph we can observe that the storey shear is maximal for bottom storeys in both the
models and storey is maximum for the floating column with isolators i.e 2738.735 KN and floating
column without isolators is lesser storey shear 169.4776 KN.
2000
1500
1000
500
0
Without Isolators With Isolators
X Directons
58
Table 5.30 B Y Direction ase Shear in 10 Storeys
Y Directions
Without Isolators With Isolators
1542.7721 950.5924
59
Base Shear along X Direction of FC at Middle
2500
2000
Shear Force in kN
1500
1000
500
0
Without Isolators With Isolators
2500
Shear Force in kN
2000
1500
1000
500
60
In the above graph we can observe that the base shear is maximum for maximum for the floating
pillar with isolators i.e 2744.7091 KN and floating column without isolators is lesser storey shear
1198.9977 KN.
2000
1500
1000
500
In the above graph we can observe that the base shear is maximum for maximum for the floating
column without isolators i.e 2282.3832 KN and floating column with isolators is lesser storey
shear 1662.1594 KN.
61
Base Shear along Y Direction of FC at Corner
1800
1600
Shear Force in kN
1400
1200
1000
800
600
400
200
0
In the above graph we can observe that the base shear is maximal for maximum for the floating
column without isolators i.e 1571.2868 KN and floating column with isolators is lesser storey
shear 949.4154 KN.
2000
Shear Force in kN
1500
1000
500
62
In the above graph we can observe that the base shear is maximal for maximum for the floating
pillar with isolators i.e 2282.3832 KN and floating column without isolators is lesser storey shear
1662.1594 KN.
2500
Shear Force in kN
2000
Without Isolators
1500
With Isolators
1000
500
In the above graph we can observe that the base shear is maximum for maximum for the floating
pillar with isolators i.e 2735.7153 KN and floating column without isolators is lesser storey shear
1197.7735 KN.
63
CHAPTER 6
CONCLUSION AND SCOPE FOR FUTURE STUDIES
In this project, a G+9 and G+14 multi-story symmetric RC structure is investigated
utilising reaction spectrum analysis by with dampers and without dampers in the building and
evaluating numerous places inside the building. The investigation produced the following
findings.
1. We can observe that the structure with base isolator are showing the optimum results.
2. The floating column providing at the corner with isolator are giving the optimum results
among the considered.
3. The comparison between with and without isolator, the storey displacement is in the base
isolator are showing the optimum result.
4. The comparison between the with and without isolator, the storey drift is in the base
isolator are showing the lesser value and all are within the permissible limit.
5. In the natural time period the structure with base isolator are showing are higher value
than the without isolator.
6. In the storey shear the structure with base isolator are showing are higher value than the
without isolator.
7. In the base shear the structure with base isolator are showing are higher value than the
without isolator.
8. When compared to the floating column in the centre, the floating column in the corner
has a bigger displacement.
We can observed that when the storey height grows, the displacement increases as well.
The bending moment at the floating column location is high when compare to the other
location in building.
64
SCOPE FOR FUTURE WORKS
A elevated structure with multiple storeys must be investigated to find the impact of a
floating column in various earthquake regions.
The current study is grounded on the Response spectrum approach of linear dynamic
analysis. The findings must be confirmed using nonlinear dynamic modeling.
The research could be expanded to find a way to manage irregularity in such structures
by installing shear walls in strategic spots.
The investigation can be conducted out on structures with changing slopes or two-
directional slopes.
Soil structure interaction of Friction pendulum system can be taken into account.
Building and estimation are required to determine cost efficiency.
.
65
REFERENCES
1. Jayashri Sarode1 and Mr. Amol.S. Pote2.”Analysis of floating column building of
composite and r.c.c beam girder & comparison with r.c.c frame structure by using etabs
v9.7.0.” IJAR August 2016.
66
Standard Codes
1. IS-1893:2002, “Code for earthquake resistant design of structures- general provisions
for buildings, Part I, Bureau of Indian Standards”, New Delhi.
2. IS-456:2000, “Code of practice for plain and reinforced concrete code of practice”,
Bureau of Indian Standards, New Delhi, 2000.
3. IS-875:1987, “Code for Dead load design of structures- general provisions for
buildings”, Part I, Bureau of Indian Standards”, New Delhi.
4. IS-875:1987, “Code for Live load design of structures- general provisions for buildings”,
Part II, Bureau of Indian Standards”, New Delhi
67