Analysis, Design and Simulation of RC Passive Damping Network in A Simple Distributed DC Power System Using Pspice
Analysis, Design and Simulation of RC Passive Damping Network in A Simple Distributed DC Power System Using Pspice
net/publication/26516792
CITATIONS READS
2 1,103
3 authors, including:
Awang Jusoh
Universiti Teknologi Malaysia
97 PUBLICATIONS 1,261 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
ZVS Full Bridge Series Resonant Boost Converter with Series-Connected Transformer View project
All content following this page was uploaded by Awang Jusoh on 04 January 2015.
Faculty of Electrical Engineering, Universiti Teknologi Malaysia, 81310 UTM Skudai, Johor, Malaysia.
*
Corresponding author: awang@fke.utm.my (Awang Jusoh), Tel: 607-5535787, Fax: 607-5566262
Abstract: The sub-system interaction and instability phenomena are a common problem in the Distributed Power System
(DPS). In order to regulate the output voltage or the speed, the internal control function of a converter known as constant
power load (CPL) results in the converter tends to draw a constant power. This phenomenon cause the input impedance of
CPL has negative incremental input impedance, which tends to create instability as it is connected to a system. This paper
concerns about the compensation method used to improve the stability of two or more connected subsystems, consisting of
an L-C filter and a CPL. A compensation method known as passive damping network containing only RC components is
examined purposely to eliminate and reduce the instability of the subsystem. The passive damping network was designed
and simulated using PSpice. The results show that the designed passive damping network is suitable for small-scale power
distribution system that contains constant power load with power level of 1 kW.
14
AWANG JUSOH, ZAINAL SALAM, LIM AIK JIN / ELEKTRIKA, 9(1), 2007, 14‐18
1 s 2 (LC1R L + LC 2 R L ) − sL + R L
−R =− = 3 (2)
0 K s LC1C 2 RL − s 2 LC2 + sR L C 2
V-
15
AWANG JUSOH, ZAINAL SALAM, LIM AIK JIN / ELEKTRIKA, 9(1), 2007, 14‐18
Root Locus
typical 1000 W load ) with the supply voltage of 270 V
and the C1 = 150 uF. C2 is obtained using equation
5000
4000
RL=30Ω R=∞Ω L
3000
5Ω C2 = 2 .
2000 1Ω R
1000 0.6Ω
0.3Ω R= 0Ω
Table 1. RC damping parameter with different poles
Imaginary Axis
-1000
Increasing RL placement
-2000
θ (°) R(Ω) C2(mF)
-3000
-4000
0° 0.351 1.211
-5000
-8000 -6000 -4000 -2000 0
Real Axis
2000 4000 6000 8000 10000
10° 0.357 1.177
⎛ L ⎞
⎛ C1R L + C2 (RL − R) ⎞ ⎜ C2 RR L + R [R L − R ] ⎟ 1 (4) 4. RESULTS
s + s ⎜⎜
3 2
⎟⎟ + s⎜ ⎟+ =0
⎝ C C RR ⎠ ⎜ ⎜ LC C R R ⎟ LC C R The schematic diagram for the PSpice simulation with
1 2 L 1 2 L
⎟ 1 2
⎝ ⎠
RC passive damping network is shown in Figure 7. All
LR L the component values used are shown clearly. The RC
By camparing Equation (1) and (4), an extra term s
R damping network is represented as R1 and C2. The source
has appeared. In order to validate the Equation (1), term and L-C filter components are as previous section. The
LR L damping network was chosen to place the system
C 2 RR L >> . This condition creates a condition complex poles on the 60o line in the complex plane. The
R
that is values of damping resistor R are 0.7 Ω and a blocking
capacitor C2 of 1.2 mF. The input voltage step signal is
L shown as V3. The + 50 V voltage transient is imposed at
C2 >> (5) simulation time 4 ms, and at simulation time 14 ms, the
R2 transient is removed.
The simulation results for bus voltage for both CPL
Therefore the design procedure is to choose R such that power level of 1 kW and 50 kW is shown in Figure 8.
the effective resistance in the quadratic portion of The plot shows that bus voltage experiences a single
Equation (3) provides satisfactory damping of the overshoot and then quickly settle to the new steady-state
complex poles, then C2 must be chosen to ensure that value 280 V, illustrating the effectiveness of the damping
equation 5 is satisfied. For example the design is to place network. The system is well damped at low power level
the complex system poles on the 45-degree of theta angle (1 kW) and experiences slightly oscillatory behavior as
(θ) in the s-plane, then the magnitudes of the real part and the power increased (50 kW).
the imaginary part of the quadratic characteristic equation
of Equation (3) must be equal. The damping resistor R is PARAMETERS:
given as L1 P
1 2 V2
R L LC1
R= (6) 150uH
I V+
LC1 + 2C1 R L V1 R1 G1
270 {P} W1
0.7 IN+ OUT+
Using the second order equation, the damping resistor C1 IN- OUT-
GVALUE
in term of θ angle can be presented as Equation (7) V3
300uF V(W1)/V(V2)
C2
1.2m
R L LC1
R= (7)
2CosθC1 R L + LC1 0
V-
16
AWANG JUSOH, ZAINAL SALAM, LIM AIK JIN / ELEKTRIKA, 9(1), 2007, 14‐18
360V
300V
50KW
1KW
320V
280V
280V
260V
240V
200V
0s 2ms 4ms 6ms 8ms 10ms 12ms 14ms 16ms 18ms 20ms
V(V2,0)
Time
240V
180ms 200ms 220ms 240ms 260ms 280ms 300ms 320ms
Time
Figure 8. Simulated bus voltage V2
Figure 10. Simulated bus voltage V2 without passive
The effectiveness of the passive damper can be proven damping
further. In this case, the CPL is connected to DC bus bar
through a long cabling system. Typical components
values for the cabling can be represented by the series R- 300V
simulation time.
However with the insertion of the passive damping Figure 11. Simulated bus voltage V2 with passive
network, the problem of bus interaction and instability damping
phenomena were eliminated. This is shown in the plot of
Figure 11. The plot shows that at simulation time 200 ms,
+10V voltage transient is imposed for a period of 40 ms, 5. CONCLUSION
and at simulation time of 260 ms, a –10 V voltage The analysis, theoretical design and simulation of the RC
transient is again imposed for the period of time of 50 ms. damping network were examined extensively in a simple
The plot shows that the system is well damped where the system consisting of LC filter and constant power load.
bus voltage experiences a single overshoot and then Detail analysis and design of obtaining the damper
quickly settle to the steady-state value, illustrating the components for CPL of 1 kW were given. The PSpice
effectiveness of the damping network. simulation results show the effectiveness of the designed
passive damping network that satisfactorily maintained
1
L2
2V4
R3
1
L3
2 the DC bus bar from any oscillation due to the interaction
150uH
V+
0.5 10uH of negative incremental impedance and LC filter. The
V6 R2 simulation result also proved that the designed RC
270Vdc
C3 0.7 damping network could be further implemented for
300u 5000 W3
G2 higher CPL power level of 5 kW.
C5 IN+ OUT+
C4 IN- OUT-
V7
100u GVALUE
1200u v (W3)/v (V4) REFERENCES
[1] Gua, G. C, Tabisz, W. A, Leu, C. S, Dai, N, Watson,
R. and Lee, F. C. “Development of A DC Distributed
0
V-
Power System,” IEEE Applied Power Electronics
Figure 9. Schematic diagram with R-L cabling Electronics Conference, APEC’94, pp.763-769,
connected 1994.
[2] W. A. Tabisz, Milan M. Jovanovic , F C Lee ,
“Present and Future of Distributed Power Systems,”
IEEE Applied Power Electronics Conference,
APEC’92, , pp. 11-18, Feb. 1992.
[3] Jusoh, A, “The instability Effect of Constant Power
Loads”. IEEE National Power and Energy
Conference, PECon 04, Kuala Lumpur, 175-179,
2004.
17
AWANG JUSOH, ZAINAL SALAM, LIM AIK JIN / ELEKTRIKA, 9(1), 2007, 14‐18
[4] M. Alfayyoumi, A. H. Nayfeh, and D. Borojevic, Symposium on Circuits & Systems, ISCAS’99, Vol.
“Input Filter Interactions in DC-DC Switching 5, pp. 82-85, May 1999.
Regulators,” IEEE Power Electronic Specialists [7] R. D. Middlebrook, “Input Filter Considerations in
Conference, PESC’99, Vol. 2, pp. 926-932, 1999. Design and Application of Switching Regulators,”
[5] R. B. Ridley, B. H. Cho, F. C. Lee, “Analysis and IEEE Proceeding on Industry Application Society
Interpretation of Loop Gains of Multiloop-Controlled Annual Meeting, pp. 11-14, October 1976.
Switching Regulators,” IEEE Transaction on Power [8] A. M. Cross, A. J. Forsyth, D. R. Trainer and N.
Electronics, Vol. 3, No. 4, pp.489-498, Oct. 1988. Baydar, “Simulation of Power Quality Issues in