Professional Documents
Culture Documents
Week 8 Ground Anchor Fall 2016
Week 8 Ground Anchor Fall 2016
Week 8 Ground Anchor Fall 2016
Bar tendons are commonly available in 26 mm, 32 mm, 36 mm, 45 mm, and 64
mm diameters
Anchor transmit the tensile force from the main structure to the
surrounding soil, and thus becomes a sub-structure in itself.
Different Uses
Typically installed in rock and very stiff to hard cohesive soil deposits using either
rotary drilling or hollow-stem auger methods.
Tremie (gravity displacement) methods are used to grout the anchor in a straight
shaft borehole. The borehole may be cased or uncased depending on the stability
of the borehole.
Most suitable for coarse granular soils and weak fissured rock. This anchor type is
also used in fine grained cohesionless soils. With this type of anchor, grout is
injected into the bond zone under pressures greater than 0.35 MPa.
The borehole is typically drilled using a hollow stem auger or using rotary
techniques with drill casings. As the auger or casing is withdrawn, the grout is
injected into the hole under pressure until the entire anchor bond length is
grouted.
This grouting procedure increases resistance to pullout relative to tremie grouting
methods by:
(1) increasing the normal stress (i.e., confining pressure) on the grout bulb resulting
from compaction of the surrounding material locally around the grout bulb; and
Post-grouted ground anchors use delayed multiple grout injections to enlarge the
grout body of straight shafted gravity grouted ground anchors. Each injection is
separated by one or two days.
Post-grouting is accomplished through a sealed grout tube installed with the tendon.
The tube is equipped with check valves in the bond zone. The check valves allow
additional grout to be injected under high pressure into the initial grout which has
set.
The high pressure grout fractures the initial grout and wedges it outward into the soil
enlarging the grout body.
Type D: Under-reamed Anchors
This type of anchor may be used in firm to hard cohesive deposits. In addition to
resistance through side shear, as is the principal load transfer mechanism for other
anchors, resistance may also be mobilized through end bearing.
Vertical and horizontal spacing requirements for ground anchors
The horizontal and vertical spacing of the ground anchors will vary depending on project specific
requirements and constraints, which may include:
(1) Necessity for a very stiff system (i.e., closely spaced anchors) to control lateral wall movements;
(2) Existing underground structures that may affect the positioning and inclination of the anchors; and
(3) Type of vertical wall elements selected for the design.
Contribution of ground anchors to wall stability
The main anchor length divided into two parts:
(i) Fixed length and
(ii) Free length
Inclined Anchor
The top or upper portion over which no
tension force is transmitted to the
surrounding ground is known as the free
length or stressing length.
Vertical Anchor
The bottom or lower length of the anchor over which the tensile force is transmitted
to the surrounding ground is known as fixed length or bond length.
The fixed length of the tendon is surrounded by main thick grout, known
as primary grouting or anchor grout;
The minimum unbonded length for rock and soil ground anchors is 4.5 m for strand
tendons and 3 m for bar tendons. These minimum values are intended to prevent
significant reductions in load resulting from seating losses during transfer of load to the
structure following anchor load testing.
(1) locate the bond length a minimum distance behind the critical potential failure surface;
(2) locate the anchor bond zone in appropriate ground for anchoring;
(3) ensure overall stability of the anchored system; and
(4) accommodate long term movements.
In general, the unbonded length is extended a minimum distance of H/5 or 1.5 m behind
the critical potential failure surface to accommodate minor load transfer to the grout
column above the top of the anchor bond zone.
Installation of Ground Anchors
STEP 1
Holes of required size are drilled into the ground by a drill rig up to a desired
depth at the location chosen for installation of anchors.
STEP 2
The anchor tendon is inserted centrally into the hole.
STEP 3
A grout, usually cement, is pumped into the space left between the tendon and the
hole, at predetermined grouting pressure.
The pressures vary for the primary grouting and the secondary grouting.
Usually, a sheath is provided around the tendon in the secondary grout area to
protect it from corrosion.
If a casing pipe is used in drilling the hole, it will be withdrawn during grouting.
The grout is finally allowed to cure.
STEP 4
A reaction (jacking) and locking system called anchor head is installed on the
anchor at the ground surface or on a structural surface.
STEP 5
A tensile stress is applied to the anchor by a hydraulic jack to a value somewhat
greater than tie design load of the anchor.
This value usually varies from 1.25 to 2 times the design load.
STEP 6
When the load is applied to the anchor, the lock-off system is engaged, and the
applied tension from the jack is released.
Design of Soil Anchors
Qu
F .S.
Pu
= (L0 tan ) . b. P0
Qu
4
. D d
2 2
N c . cu D . l . cu
Where,
Qu = estimated ultimate load carrying capacity of a belled anchor
of given size (kN/m2)
D = under-ream diameter (m)
d = shaft diameter (m)
l = distance between adjacent under-reams (m)
cu = undrained shear strength of clay soil
Nc = bearing capacity factor = 9
2. Straight circular anchors
Qu ( .d . L0 ) . Sb
where,
d = diameter of the primary grout bulb (m)
L0 = fixed anchor length (m)
Sb, = soil to grout bond strength (kN/m2)
Table 1 Types of Soil Anchors and Suitable Soils for their Anchorage
Note:
* Friction from compacted zone having locked in stress. Mass penetration of grout in
highly pervious sand/gravel forms ‘bulb’ anchor.
** Local penetration grout will form bulbs, which act in bearing or increase
effective diameter.
Table 1 Soil to Grout Bond Strength Soil Anchors in Cohesive Soils