1. Safety Information

! A ttention
B efore install the prod uct, p lease read the
u ser m an ual.

☞ Make sure there is no physical damage or missing part before


install PROMET5300.

☞ Make sure control power, electric current and voltage are


turned off before connecting or disconnecting PROMET5300.

☞ High voltage and high electric currents are circulating in the


terminals of PROMET5300. Direct contact might lead to a fatal
injury.

☞ You must set up PROMET5300 in accordance with its system


composition. Any non-compliant setup may cause PROMET5300
to display wrong information or to malfunction.

☞ Please connect voltage/electric current to backside terminals


according to their relevant terminal numbers.

☞ Please keep it away from flammable or hazardous materials.


1. Safety Information
2. Introduction ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 1
2.1. Introduction of PROMET5300 ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 1
2.2. Characteristics and major functions ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 1
3. Technical Data ·
··
··
··
··
··
··
·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 3
3.1. Electric Rating ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 3
3.2. Communication & Type-Tests Environment ·
··
··
··
··
··
··
··
··
··
··
·· 4
3.3. Mechanical performance & dimensional ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 5
4. Installation Instructions ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 8
4.1. Front panel Layout ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 8
4.2. Terminal View ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 9
5. Operating Instructions ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 11
5.1. Function ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 11
5.1.1. Operation display Function ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 11
5.1.2. Recording Function ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 27
5.2. Operation and Setting function ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 28
5.2.1. Operation status LED ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 28
5.2.2. CB status LED ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 29
5.2.3. Menu key operation ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 30
5.2.4. CB key operation ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 31
5.2.5. Fault Clear key operation ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 34
5.2.6. UI menu structure map ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 36
5.2.7. Start-up Screen ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 37
5.2.8. Measures ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 37
5.2.9. Relay setting ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 41
5.2.10. Records information ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 60
5.2.11. Monitoring information ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 66
5.2.12. Device setting ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 71
6. Installation & Operation ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
·· 77
7. Product connection wiring ·
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
··
· 78
2. Introduction
2.1. Synopsis
PROMET5300 is digital protection relay as the ultra-reliable ability to
perform precise instrumentation with protection factor more than 12 type,
and various interfaces with the central monitoring system through
supervisory and control capabilities to remote, which provides a
full-featured electronic switchboards solution IED (Intelligent Electronic
Device). Especially, this product is possible to provide
IEC61850(International Standard Protocol), so it could be linked to the
central monitoring system to facilitate the remote of real-time
supervisory and control at the digital substation, power station and
plant.

2.2. Characteristics and major functions

◆ Compact of Facilities
Switchboards used to relay multiple existing analog to digital one relay to
implement the Compact and to install and configure the electronic switchboards
operation convenience.

◆ Providing of various communication interfaces


It provides communication interface applicable to any environment through
accommodation of IEC61850 and various standard protocols. Therefore, user
does not need to mount separate protocol converter, and can establish
monitoring and control system rapidly and conveniently.

◆ Providing of various Graphic screen to adopted color Graphic LCD


Color Graphic LCD to the adoption of high-resolution 800X480
Mimic-Board, Vector-Diagram and provides the same screen Harmonic
Spectrum Analysis Graph provides a variety of information to users.
PROMET5300 is offered color screen so, you can easily recognize figure
and measurement value on the screen.

◆ Providing of various event information


Operation Event
It stores and manages events such as control event (on, off, trip) and
diagnosis event occurring during various operations in the order of
occurring time up to 4096 pieces.

1
Fault Event
It stores and manages various fault information (occurring time, kind of
fault, operation relay element and etc.) upon line accident in the order of
occurring time up to 1024 pieces.

◆ Fault Wave storage function


It stores and manages sample data of 320 cycle up to 4 pieces for faults
occurred recently. User can use the stored fault wave and can utilize it as
cause analysis data for faults.

◆ Providing of convenient user interface


Various set-up and instrumentation control can be input and installed
conveniently in PC through USB communication port mounted in the side
face of main body. (Software to be provided by our company is used.)

◆ Various control power


Free Voltage Type (AC / DC 110 ~ 220 [V]) controlled the various control power
supply available.

◆ Self-diagnostic diagnosis and Backup power outage


PROMET5300 the CPU Check, Memory Diagnostic and above, I/O diagnosis,
diagnosis and control, such as the power to perform regular self-diagnosis
of the bad occurred, and warned that output by storing and diagnostic
Event allows the user to take rapid countermeasures.

◆ Logic Function
PROMET5300 can be output LOGIC(= AND, OR, Latch etc.) with DO or
communication after it is received download with back and side port
information of the internal IED.

2
3. Technical Data

3.1. Electric Rating


◆ Control power

Voltage input Power dissipation


AC/DC 110~220V(Free Voltage)
Within 20W
AC/DC 20~60V(option)
◆ Current input
Connection
Input ratings Input burden
type
Current 5A / I0 : 1.5mA
3Phase 3Wire
Voltage 110V / V0 : 190/110V Below 1VA
3Phase 4Wire
Frequency 50/60Hz
◆ Input Contacts

Input type Port Input Rating Input mode

Configurable AC110V/DC125V Photo-isolated


24 Port
User Input DC48/24V Input

◆ Output Contacts
- Type 1 (A Contacts)

TRIP Contacts / ON / OFF Alarm Contacts (A Contacts)


30A/250VAC 5A/250VAC
8EA 4EA

- Type 2 (A/B Contacts)

TRIP Contacts / ON / OFF Alarm Contacts (A / B Contacts)


30A/250VAC 10A/250VAC
2EA 5EA

3
3.2. Communication & Type-Tests Environment
◆ Communication
Classification Specifications
CH1 : Optical Communication(Optic Fiber )
100M Ethernet LC type
Type
CH2 : Optical Communication(Optic Fiber )
100M Ethernet LC type
Baud Rate 100M bps
PROTOCOL IEC61850, MODBUS-TCP
CH3 : RS485 Two-wire, Half duplex, isolated
Type
Side Communication Port : USB Port Serial
Baud Rate 1200/2400/4800/9600/19200/38400/57600/115200 bps
PROTOCOL MODBUS-RTU, DNP3.0, IEC60870-5

◆ Type-Tests Environment

Items Specifications
Operating
-20 ~ 60C
Temperature
Temperature
Storage
-25 ~ 70C
Temperature
Humidity Daily average 30 ~ 80%
Insulation
> 10MΩ
Resistance
AC Voltage Tests AC 60Hz 2000V/1min

Surge Impluse 1.2/50uS 5kV +/- 3 times


Current: 1.15 times rated 3hours, 20 times 2sec
Overload Voltage: 1.15 times rated for 3hours
Power: 1.3 times rated for 3hours
1MHz Oscillatory
IEC60255-22-1 2.5kV
Transient

Type-Tests EFT/Burst IEC60255-22-4 Class A : 4kV

RFI Susceptibility IEC60255-22-6

Radiated -electro IEC60255-22-4


magnetic field
Surge IEC60255-22-5 : 4kV

ESD 60255-22-2: Contact(6kV), Air(8kV)

EMI IEC 60255-25

4
3.3. Mechanical performance and size
◆ Weight : 8.8kg
◆ Front view

◆ Side view

5
◆ Upper side view

◆ Back side view

6
◆ Cutting Size

7
4. Installation Instructions
4.1. Front panel Layout

Display panel
Power LED ㆍColor Graphic LCD
Relay Operation
RUN LED ㆍ800 × 480 Resolution
Sign LED
SYS Fail LED

Fault RESET
Key

Local/Remote
(On:Local)
LED/Button

CB2 OFF Sign CB1 OFF Sign


LED/Button LED/Button

CB1 ON Sign
LED/Button

CB2 ON Sign
LED/Button

Menu Key Terminal Port


Function Key
■ Measurement Display for PC Interface
ㆍUp key
■ Relay Parameter Setting (USB)
ㆍDown key
■ Comm. Parameter Setting ㆍEnter key
■ Event View ㆍEsc key
■ System Operation Sett

8
4.2. Terminal view
4.2.1. PROMET5300 Terminal View (Rear View)

E D C B A

4.2.2. Terminal Composition


A Terminal Composition
A1 A3 A5 A7 A9 A11 A13 A15 A17
- - - - - - - - -
A2 A4 A6 A8 A10 A12 A14 A16 A18
- - - - - - L+ N- FG

B Terminal Composition
B1 B3 B5 B7 B9 B11 B13 B15 B17
IA+ IB+ IC+ IN+ VA+ VB+ VC+ VN+ Vbus
+
B2 B4 B6 B8 B10 B12 B14 B16 B18
IA- IB- IC- IN+ VA- VB+ VC+ VN+ Vbus
-

C Terminal Composition
- Type 1 (Trip, Alarm Contacts / A Contacts) : DO 12EA

C1 C3 C5 C7 C9 C11 C13 C15 C17


CB CB SW 1 SW 2 SW 2 SW 3 ALM1/2
ALM1 ALM2
OFF COM ON OFF COM ON COM1
C2 C4 C6 C8 C10 C12 C14 C16 C18
CB SW 1 SW 1 SW 2 SW 3 SW 3 ALM3/4
ALM3 ALM4
ON OFF COM ON OFF COM COM

9
- Type 2 (Trip, Warning Contacts A/B Contacts) : DO 7EA
C1 C3 C5 C7 C9 C11 C13 C15 C17
DO1+ DO2+ DO3 DO3 DO4 DO5 DO5 DO6 DO7
CBOFF CBON A COM A A COM A A
C2 C4 C6 C8 C10 C12 C14 C16 C18
DO1+ DO2- DO3 DO4 DO4 DO5 DO6 DO6 DO7
CBOFF CBON B COM B B COM B COM

D Terminal Composition
D1 D3 D5 D7 D9 D11 D13 D15 D17
DI2 DI4 DI6 DI8 DI DI10 DI12 DI14 DI16
COM2
D2 D4 D6 D8 D10 D12 D14 D16 D18
DI1 DI3 DI5 DI7 DI DI9 DI11 DI13 DI15
COM1

E Terminal Composition
- Type 1 : Apply the DI24 module
E1 E3 E5 E7 E9 E11 E13 E15 E17
DI18 DI20 DI22 DI24 DI DO AI1 - -
COM3 Alm
B
E2 E4 E6 E8 E10 E12 E14 E16 E18
DI17 DI19 DI21 DI23 DO DO AI2 AI -
Alm Alm COM
Com A

- Type 2 : Apply the DI32 module


E1 E3 E5 E7 E9 E11 E13 E15 E17
DI18 DI20 DI22 DI24 DI DI26 DI28 DI30 DI32
COM4
E2 E4 E6 E8 E10 E12 E14 E16 E18
DI17 DI19 DI21 DI23 DI DI25 DI27 DI29 DI31
COM3

F Terminal Composition
F1 F3 F5 F7 F9 F11 F13 F15 F17
- - - - - - - - -
F2 F4 F6 F8 F10 F12 F14 F16 F18
- - - - - - - - -

ETH0, ETH1 (Optical Communication Terminal)

10
5. Operating Instructions
5.1. Function
5.1.1. Protective Relay Function
1) Protective operating characteristics for over current
◆ Normal Inverse curve

æ 0.14 ö Tm
Toperate = çç 0.02
÷´
÷ 10
è ( I / I s ) - 1 ø

11
◆ Very Inverse curve

æ 13.5 ö Tm
Toperate = çç ÷´
÷ 10
è ( I / I s ) - 1 ø

12
◆ Extremely Inverse curve


 

 
   

×


13
◆ KEPCO Normal Inverse curve

æ 0.11 ö T
Toperate = çç 0.02
+ 0.42 ÷÷ ´ m
è (I / I s ) - 1 ø 10

14
◆ KEPCO Very Inverse curve

 
  

   
  

 × 


15
◆ IEEE EI curve

æ 28.2 ö Tm
Toperate = çç 2.0
+ 0 . 1217 ÷´
÷ 10
è ( I / I s ) - 1 ø

16
◆ Long Inverse curve

æ 120 ö Tm
Toperate = çç ÷´
÷
( )1
è I / I s - 1 ø 10

17
2) Protective operating characteristics for over current for OVGR
◆ OVGR for TRIP(59GT) KEPCO Very Inverse Curve

æ 12.15 ö T
Toperate = çç + 0.35 ÷÷ ´ m
è (V / Vs ) - 1
2
ø 10

18
◆ OVGR for ALARM(59GT) KEPCO Very Inverse Curve

æ 24.75 ö T
Toperate = çç + 4.15 ÷÷ ´ m
è (V / Vs ) - 1
2.23
ø 10

19
3) Protective operating characteristics for UVR
◆ 27 KEPCO Normal Inverse curve

æ 8.0 ö Tm
Toperate = çç ÷´
2.2 ÷
è 1 - (V / Vs ) ø 10

20
4) Protective operating characteristics for THR
◆ Thermal protective(Cold Curve)

2
I2 -Ip
T = t × log 2
I 2 × (k × I b )

T=Operating Time,Ip=Load current before fault,Ib=Rating load current,


I=Fault current,k=Over load constant,τ= thermal time constant
(τ= 0.5~60/min, Ip = 0 , k = 1, Ib = 1)

21
◆ Thermal curve(Hot)

2
I2 -Ip
T = t × log 2
I 2 × (k × I b )

T=Operating Time,Ip=Load current before fault,Ib=Rating load current,


I=Fault current,k=Over load constant,τ= thermal time constant
(τ= 0.5~60/min, Ip2=0.5,k=1,Ib=1)

22
Setting range and characteristic of relay protection functions.
◆ OCR Relay

Type Setting Range & Step & Characteristic

Pickup Set Block, 1.0 ~ 80.0[A] in steps of 1[A]


Instant
Time>>> Operation
0.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.2 ~ 80.0[A] in steps of 0.1[A]
Instant
Time>> Operation
0.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.5 ~ 16.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI
Curve KEPCO Normal Inverse(KNI), KEPCO Very
Delay
Inverse(KVI), Long Inverse(LI)
Time>
Definite Time(DT)
0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Operation
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

◆ OCGR Relay
1) Residual Circuit and usual ZCT input

Type Setting Range & Step & Characteristic

Pickup Set Block, 0.5 ~ 40.0[A] in steps of 0.1[A]


Instant
Time>>> Operation
0.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.5 ~ 40.0[A] in steps of 0.1[A]
Instant
Time>> Operation
0.04 ~ 100.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.1 ~ 10.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI
Delay Curve KEPCO Normal Inverse(KNI), KEPCO Very
Time> Inverse(KVI), Long Inverse(LI)
Definite Time(DT)
0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Operation
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

23
2) Low Current ZCT Input(ex : GS-5)

Type Setting Range & Step & Characteristic

Pickup Set Block, 20 ~ 1000[mA] in steps of 1[mA]


Instant
Time>>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 20 ~ 1000[mA] in steps of 1[mA]
Instant
Time>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 20 ~ 500[mA] in steps of 10[mA]
Normal Inverse(NI), Very Inverse(VI), Extremely
Inverse(EI), IEEE EI, KEPCO Normal Inverse
Delay Curve
(KNI), KEPCO Very Inverse(KVI), Long
Time> Inverse (LI), Definite Time(DT)
0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Operation
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

◆ UVR Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]

Delay Curve KEPCO Normal Inverse(KNI), Definite Time(DT)


Time 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)
Operation
Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

◆ UVR Alarm Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]
KEPCO Normal Inverse(KNI), Definite
Delay Curve
Time(DT)
Time
Operation 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)
Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

◆ UVR Sync Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]
KEPCO Normal Inverse(KNI), Definite
Delay Curve
Time(DT)
Time
Operation 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)
Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

24
◆ OVGR Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 50 ~ 180[V] in steps of 1[V]
Instant
Time Operation
0.03 ~ 60.0[Sec in steps of 0.01[Sec
Time Set
Pickup Set Block, 8 ~ 140[V] in steps of 1[V]

Delay Curve KEPCO Very Inverse(KVI), Definite Time(DT)


Time 0.03~60.0[Sec] in steps of 0.01[Sec] (DT)
Operation
Time Set 0.03~60.0[Tm] in steps of 0.01[Tm]

Pickup Set Block, 8 ~ 140[V] in steps of 1[V]


Curve KEPCO Very Inverse(KNI), Definite Time(DT)
Alarm
Operation 0.03~60.0[Sec] in steps of 0.01[Sec] (DT)
Time Set 0.03~60.0[Tm] in steps of 0.01[Tm]

◆ OVR Relay

Type Setting Range & Step & Characteristic

Pickup Set Block, 50 ~ 180[V] in steps of 1[V]

Curve Very Inverse(VI), Definite Time(DT)


Delay
Time
0.03~60.0[Sec] in steps of 0.01[Sec] (DT)
Operation
Time Set
0.03~60.0Tm in steps of 0.01Tm (NI)

◆ POR Relay

Type Setting Range & Step & Characteristic

Pickup Set Block, 10 ~ 140[V] in steps of 1[V]


Delay
Time
Operation
0.1~50.0[Sec] in steps of 0.1[Sec]
Time Set

◆ SYNCH25 Relay

Type Setting Range & Step & Characteristic


Voltage difference Block, 2.0 ~ 90.0[V] in steps of 0.5[V]
Phase difference Block, 2~60[°] in steps of 1[°]
Frequency difference Block, 0.1~0.5[Hz] in steps of 0.1[Hz]
Operation Time Set 0.05~10.0[Sec in steps of 0.01[Sec

25
◆ THR Relay

Type Setting Range & Step & Characteristic

Pickup Set Block, 0.5 ~ 12[A] in steps of 0.1[A]

Curve Thermal Curve


Delay
Time 0.5~60[min] in steps of 0.5[min] (Thermal
Operation time constant)
Time Set 0.5~60[min] in steps of 0.5[min] (Cooling
time constant)

◆ 51LR Relay

Type Setting Range & Step & Characteristic

Pickup Set Block, 1 ~ 50[A] in steps of 0.2[A]

Curve Normal Inverse(NI), Definite Time(DT)


Delay
Operation 0.1 ~ 50.0[Sec in steps of 0.1[Sec (DT)
Time
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]
Starting
0 ~ 300[Sec in steps of 1[Sec
Delay time

◆ 48ST Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 1 ~ 80[A] in steps of 0.5[A]
Delay Starting
1.0 ~ 10.0[PU] in steps of 0.1[PU]
Time Current
Operation
0.1 ~ 50.0[Tm] in steps of 0.1[Tm]
Time Set

◆ NSOCR Relay

Type Setting Range & Step & Characteristic


Pickup Set Block, 0.5 ~ 12.0[A] in steps of 0.1[A]
Instant
Time Operation
40 ~ 100[ms] in steps of 10[ms]
Time Set
Pickup Set Block, 0.4 ~ 5.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI), Extremely
Delay Curve Inverse(EI), IEEE EI, KEPCO Normal Inverse(KNI),
Time KEPCO Very Inverse(KVI), Definite Time(DT)

Operation 0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)


Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

26
5.1.2. Recording Function
1) Operating Record
PROMET5300 stores information related to the IED operation up to maximum 4094
pieces in the Nonvolatile memory(FRAM). Since it stores data by the occurrence
time(SOE: Sequence Of Event) in the resolution of 1mSec, it is possible to trace
event. Item and content to be stored in the operation record is as follows.

Saved items Saved contents


CB Operations(ON,OFF,Trip)
Alarm Control Event Event Occurrence Time
Digital Input Event (Year/Month/Day/Hour/Min/Sec/mS)
Local/Remote Event
Event ID
Fault Occurrence Event
Event Name
Diagnostic Event
System Parameter Event Event Source(Local/Remote)
Diagnostic Occurense Event
Saved Information Delete Event

2) Fault Event Recording Function


PROMET5300 performs line protection with protection relay function for faults
occurring during line operation, and at the same time, stores information for those
faults up to maximum 1024 pieces in the Nonvolatile memory(FRAM). Contents of
the stored trouble information are as follows.

Contents of the stored


Fault occurrence time(year/month/day/hour/min/sec/mS)
Fault ID
Fault occurring phase (A/B/C/N)
Operation relay factor
Size and phase angle of the fault current by each phase

3) Fault waveform Record


PROMET5300 was recently saved sample waveform and status information
4 faults. About before and after the fault 320Cycles’s current and voltage.
There waveforms can be utilized as data for the waveform analysis and
cause analysis of fault. Contents of the stored disturbance waveform are as
follow.

Contents of the stored

Fault occurrence time


Operation relay factor and Fault occurring phase
Size and phase angle of the fault current by each phase
Size and phase angle of the fault voltage by each phase
Operation Status(DI,DO) information

27
5.2. Operation and Setting function
5.2.1. Operation status LED
The operation status of the relays, as shown below, an LED display visible
actions LED, Power LED, Pickup LED, Alarm and Trip LED 6 EA. Each
configuration is as follows.

◆ Power LED
This LED display power status of PROMET5300. When PROMET5300’s power
status is normal, Power LED will turn on green.

◆ RUN LED
This LED display operation status of PROMET5300. When PROMET5300
self-diagnosis status is normal, RUN LED will turn on green.

◆ SYS_FAIL LED
Off during normal behavior and, if diagnostic devices, at least judging by Fail
when the yellow light, and LED, LED diagnostic information to determine what items
can be diagnosed through the menu.

◆ FAULT LED
Setting-value over the current behavior of the fault is maintained. Trip time
when action is set in the output contacts, and the Fault LED will turn on red.
Fault to return the user to turn off the LED Fault Reset key is pressed.

◆ Alarm LED
Over the alarm setting Current is approved the alarm is maintained. When
become set operating time, the alarm contact output. Fault LED will turn on
red. After returning the alarm. If user push the Fault Reset key, LED will turn
off.

◆ PICK-UP LED
The behavior over setting-value relays the signal is when the yellow Pickup LED
blinks. Current-Value and Voltage-Value are setting-value LED turn off down below.

28
5.2.2. CB status LED
LED(CB OPEN LED, CB ON LED, Local LED etc,. 5EA) for the status of CB as
follows. Each configuration is as follows.

◆ LOCAL LED
This have button which CB in Control on LED-communication at local or
remote. If LOCAL have control, LED turn on. If remote have control,LED turn off.
◆ CB1_ON LED
CB1_ON LED of PROMET5300 is button which CB1 is close or open. The red
LED will light when close .

◆ CB1_OPEN LED
CB1_Open LED of PROMET5300 is button which CB1 is close or open. The
green LED will light when open.

◆ CB2_ON LED
CB2_ON LED of PROMET5300 is button which CB2 is close or open. The red
LED will light when close .

◆ CB2_OPEN LED
CB2_Open LED of PROMET5300 is button which CB2 is close or open. The
green LED will light when open.

29
5.2.3 Menu key operation
MENU-MOVE and CONTROL of PROMET5300 operate as shown below. Button of
display bottom(5ea) and right(4ea) push, hardware operate displayed-contents.

Bu
tt
on
6

Bu
tt
on
7

Bu
tt
on
8

Bu
tt
on
9

Button 1 Button 2 Button 3 Button 4 Button 5

● MENU MOVE
Button(5ea) of display bottom use when Menu move. Button 4ea from left use
menu selection and moving, and fifth right button use when next-menu move.

30
● Control Key
Right-side of LED screen will show four cells. This cells shows control-menu
SELECT, CANCEL, SAVE. etc.

5.2.4 Local / CB key operation


① Local/ Remote
If you want Local or Remote, button use as shown below.

Local/Remote

31
At first, LOCAL-key push. Right buttons use second[◀], third[▶], and Yes or
or NO select. If you want when another mode change, LOCAL-key push. and
next-flow is same.

[ Remote situation change ]

[ Local situation change ]

32
② CB1,2 Open/Close
If you want CB1,CB2, button use as shown below.

CB1 OPEN
CB2 OPEN

CB1 CLOSE
CB2 CLOSE

Remote is situation, display represent as shown below. if you want to control


CB1 or CB2, you must be changed local-situation. so then, right OK-button
push, LOCAL-key push. Right buttons use second[◀], third[▶], and Yes select.

33
Local is situation, display represent as shown below. Right buttons use
second[◀], third[▶], and Yes or or NO select.

5.2.5 Fault Clear Key operation


Fault Reset key will clear Error-status of PROMET5300.

Fault Clear

34
When Fault occurred, upper of display change [Nomal status] to [FAULT
OCCURED].

At this moment, Fault Clear key is pressed the screen will change as follows.

35
5.2.6. UI menu structure map
Menu hava main-menu and sub-menu.

main
Menu sub-menu content
start-up single line diagram single line diagram situation
General General Measurement display
Vector DIG Voltage,Current for using Vector
Measures Quality THD, TDD, Thermal
V/I Details information of Voltage/Current
Sync Information between Bus-Line
OCR
OCGR
UVR
UVR_ALARM
OVR
OVGR
Relay
POR Relay setting and check
Setting
NSOCR
THR
51LR
48STALL
SYNCH25
UVR_SYNC
operation information operation of CB operation etc,
Fault information Fault Record of Fault-operation etc.
action Counter counter of WatchDog Reset etc.
Load Profile Profile information
Present month Max Measurement Value etc. of
Records Max Measurement Present month
Present month Min Measurement Value etc. of
Min Measurement Present month
Last month Max Measurement Value etc. of
Max Measurement Last month
Last month Min Measurement Value etc. of
Min Measurement Last month
DI status Input status of 32ea
DO status Output status of 16ea
Monitoring
Monitoring status Error of IED
Device status Version of H/W, S/W
System CT ratio, PT ratio, wiring etc.
Protection Active/Deactive of Protection element
Time Time of System
Device Goose Goose Message Enable
Network IP of IED
Setting
RS485 communication of RS485
MISC Use A, count board of DI etc.
Erase record wh, event, fault
contact DI contact assignment

36
5.2.7. Start-up Screen
This is Start-up Screen, and this is represented single line diagram situation , line
voltage, line current.

5.2.8. Measures
First Button of bottom push [Measures]. If you want previous display, Right
first buttons [UP].

37
sub-menu of [Measures] is [General],[Vector DIG],[Quality],[V/I],[Sync]
as shown below.

38
① [General]
At first, you can select [General] at sub-menu of [Measures]. This menu
represent Line Voltage, Phase voltage, Frequence, Factor, Active/Reactive
Power, Active/Reactive Energy. If you want previous display, Right first buttons [UP].

② Vector DIG
You can select [Vector DIG] at sub-menu of [Measures]. This menu represent
Voltage, current, magnitude, phase of each phase, and Vector Diagram.
In especially Vector Diagram can be checked wiring of voltage, current. If you
want previous display, Right first buttons [UP].

39
③ Quality
You can select [Quality] at sub-menu of [Measures]. This menu represent
THD, TDD, Motor Thermal and find out quality of system. If you want previous
display, Right first buttons [UP].

④ V / I
You can select [ V / I ] at sub-menu of [Measures]. This menu represent
value, phase, positive/negative/zero-phase-sequence of voltage, current. If you
want previous display, Right first buttons [UP].

40
⑤ Sync
You can select [ Sync ] at sub-menu of [Measures]. This menu represent
voltage/ Frequence / phase of SYNC-LINE. If you want previous display, Right
first buttons [UP].

5.2.9. Relay setting

Second Button of bottom push [Relay Setting]. If you want previous display,
Right first buttons [UP] as belows.

41
sub-menu of [Relay Setting] is as shown below.

◈ Password must be inputted for relaying Setting. password is 2/2/2/2/.

42
If system have occurred as shown below after activation for relay setting,
if you want to hide alarm screen, push anything among Buttons and Keys
except [FAULT RESET] Key. but, if you want to clear Trip, [FAULT RESET] Key
must be to push.

① Set OCR
Setting Range & Step & characteristic of OCR is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 1.0 ~ 80.0[A] in steps of 1[A]
Instant
Operation
Time>>> 0.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.2 ~ 80.0[A] in steps of 0.1[A]
Instant
Time>> Operation
0.04 ~ 10[Sec in steps of 10[ms]
Time Set
Pickup Set Block, 0.5 ~ 16.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI
Delay Curve KEPCO Normal Inverse(KNI), KEPCO Very
Time> Inverse(KVI),
Definite Time(DT)
Operation 0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

Select [OCR] menu on the detail menu screen.

43
If you push right forth button [SET] for relay setting, password represent to
input in the screen. If you want previous display, Right first button [UP] push.

You can be located to 2 for right second or third button [◀], [▶]. You push
4times to right forth button [SEL] as below follows. If you want last inputted
number, use <- to right second or third button. If you want previous display,
Right first button [EXIT] push.

44
You can be located to change for right second or third button [▲], [▼].And
you push to right forth button [SEL], will change setting-value to [INC],[DEC].
you push to right forth button [OK] after changing setting-value. and push
first button [SAVE]. If you want to change another setting-value, push [SEL].
The method is same. If you want previous display, Right first button [EXIT] push.

The next flow is as below flows.

45
46
② Set OCGR
Setting Range & Step & characteristic of OCGR is as follows. If ZCT-input-range
is 20~2000[mA] for measurement for zero-phase-sequence current, apply a
table as below follows.

Type Setting Range & Step & characteristic

Pickup Set Block, 0.5 ~ 40.0[A] in steps of 0.1[A]


Instant
Time>>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 0.5 ~ 40.0[A] in steps of 0.1[A]
Instant
Time>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 0.1 ~ 10.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI,
Delay Curve KEPCO Normal Inverse(KNI), KEPCO Very
Time> Inverse(KVI), Long Inverse(LI),
Definite Time(DT)
0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Operation
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

If GS-5 (2000:5) of ABB apply a table as below follows.

Type Setting Range & Step & characteristic

Pickup Set Block, 20 ~ 1000[mA] in steps of 1[mA]


Instant
Time>>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 20 ~ 1000[mA] in steps of 1[mA]
Instant
Time>> Operation
0.04 ~ 10s in steps of 10ms
Time Set
Pickup Set Block, 20 ~ 500[mA] in steps of 10[mA]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI,
Delay Curve KEPCO Normal Inverse(KNI), KEPCO Very
Time> Inverse(KVI), Long Inverse(LI),
Definite Time(DT)
0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)
Operation
Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

47
Select [OCGR] menu on the detail menu screen.

[Residual Sensing]

[ZCT Sensing]

Set method is same as OCR.

48
③ Set UVR
Setting Range & Step & characteristic of UVR is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]
KEPCO Normal Inverse(KNI),
Delay Curve
Definite Time(DT)
Time
Operation 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)
Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

Select [UVR] menu on the detail menu screen.

Set method is same as OCR.

49
④ Set UVR3
Setting Range & Step & characteristic of UVR3 is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]
KEPCO Normal Inverse(KNI),
Curve
Delay time Definite Time(DT)

Operation 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)


Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

Select [UVR3] menu on the detail menu screen.

Set method is same as OCR.

50
⑤ Set UVR4
Relay of UVR4 is Voltage-terminal(Vbus 17.18) for SYNC except terminal of R,
S, T. Setting Range & Step & characteristic of UVR4 is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 10 ~ 140[V] in steps of 1[V]
KEPCO Normal Inverse(KNI),
Curve
Delay Time Definite Time(DT)

Operation 0.03~ 60.0[Sec] in steps of 0.01[Sec] (DT)


Time Set 0.03 ~ 60.0[Tm] in steps of 0.01[Tm]

Select [UVR4] menu on the detail menu screen.

Set method is same as OCR.

51
⑥ Set OVR
Setting Range & Step & characteristic of OVR is as follows.

Type Setting Range & Step & characteristic

Pickup Set Block, 50 ~ 180[V] in steps of 1[V]

Curve Very Inverse(VI), Definite Time(DT)


Delay time
0.03~60.0[Sec] in steps of 0.01[Sec] (DT)
Operation
Time Set
0.03~60.0[Tm] in steps of 0.01[Tm]

Select [OVR] menu on the detail menu screen.

Set method is same as OCR.

52
⑦ Set OVGR
Setting Range & Step & characteristic of OVGR is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 50 ~ 180[V] in steps of 1[V]
Instant
Time Operation
0.03 ~ 60.0[Sec in steps of 0.01[Sec
Time Set
Pickup Set Block, 8 ~ 140[V] in steps of 1[V]
KEPCO Very Inverse(KVI), Definite
Curve
Delay Time Time(DT)

Operation 0.03~60.0[Sec] in steps of 0.01[Sec] (DT)


Time Set 0.03~60.0[Tm] in steps of 0.01[Tm]

Pickup Set Block, 8 ~ 140[V] in steps of 1[V]


KEPCO Very Inverse(KVI),
Curve
Alarm Definite Time(DT)

Operation 0.03~60.0[Sec] in steps of 0.01[Sec] (DT)


Time Set 0.03~60.0[Tm] in steps of 0.01[Tm]

Select [OVGR] menu on the detail menu screen.

Set method is same as OCR.

53
⑧ Set POR
Setting Range & Step & characteristic of POR is ad follows.

Type Setting Range & Step & characteristic

Pickup Set Block, 10 ~ 140[V] in steps of 1[V]


Delay Time
Operation
0.1~50.0[Sec] in steps of 0.1[Sec]
Time Set

Select [POR] menu on the detail menu screen.

Set method is same as OCR.

54
⑨ Set NSOCR
Setting Range & Step & characteristic of NSOCR is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 0.5 ~ 12.0[A] in steps of 0.1[A]
Instant
Time Operation
40 ~ 100[ms] in steps of 10ms
Time Set
Pickup Set Block, 0.4 ~ 5.0[A] in steps of 0.1[A]
Normal Inverse(NI), Very Inverse(VI),
Extremely Inverse(EI), IEEE EI
Curve KEPCO Normal Inverse(KNI), KEPCO Very
Delay Time Inverse(KVI),
Definite Time(DT)

Operation 0.1 ~ 50.0[Sec] in steps of 0.1[Sec] (DT)


Time Set 0.1 ~ 50.0[Tm] in steps of 0.1[Tm]

Select [NSOCR] menu on the detail menu screen.

Set method is same as OCR.

55
⑩ Set THR
Setting Range & Step & characteristic of THR is as follows.

Type Setting Range & Step & characteristic

Pickup Set Block, 0.5 ~ 12[A] in steps of 0.1[A]

Curve Thermal Curve


Delay Time 0.5~60[min] in steps of 0.5[min] (Thermal
Operation time constant)
Time Set 0.5~60[분] in steps of 0.5[분] (Cooling time
constant)

Select [THR] menu on the detail menu screen.

Set method is same as OCR.

56
⑪ Set 51LR
Setting Range & Step & characteristic of 51LR is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 1 ~ 50[A] in steps of 0.2[A]
Curve Normal Inverse(NI), Definite Time(DT)
Delay Time
Operation 0 ~ 300[Sec] in steps of 1[Sec] (DT)
Time Set 0 ~ 300[Tm] in steps of 1[Tm]

Select [51LR] menu on the detail menu screen.

Set method is same as OCR.

57
⑫ Set 48ST
Setting Range & Step & characteristic of 48ST is as follows.

Type Setting Range & Step & characteristic


Pickup Set Block, 1 ~ 80[A] in steps of 0.5[A]
Operation
Delay Time 0.1 ~ 50.0[Sec in steps of 0.1[Sec
Time Set
Starting
1.0 ~ 10.0[PU] in steps of 0.1[PU]
Current

Select [48ST] menu on the detail menu screen.

Set method is same as OCR.

58
⑬ Set SYNCH25
Setting Range & Step & characteristic of SYNCH25 is as follows.

Type Setting Range & Step & characteristic


Voltage difference Block, 2.0 ~ 90.0[V] in steps of 0.5[V]
Phase difference Block, 2~60[°] in steps of 1[°]
Frequency difference Block, 0.1~0.5[Hz] in steps of 0.1[Hz]
Operation Time Set 0.05~10.0[Sec in steps of 0.01[Sec

Select [SYNCH25] menu on the detail menu screen.

Set method is same as OCR.

59
5.2.10. Records information
On the Main Menu screen, select the third item [Records].

If you select, represent menu of Records. If you want previous display, Right
first button [UP] push.

[ Basic screen of Records ]

60
Menu of Records is same as below follow.

① Op. Info.
You select [Op. Info] at Menu of Records. This menu represent 10ea at screen
until max 4094ea to various records of operation. Records of before and after
can be check using right second or third button [▲], [▼]. Menu of [Op. Info]
is convenient at Event Trace according to occurrence-time.

PROMET5300 record information of operation as below follows.

Saved items Saved contents


CB Operation(ON,OFF,Trip)
Alarm Control Event
Event Occurrence Time
Digital Input Event
(Year/Month/Day/Hour/Min/Sm)
Local/Remote Event
Event ID
Fault Occurrence Event
Event Name
Diagnostic Event
Event Source(Local/Remote)
System sety change Event
Diagnostic Occurrence Event
Saved Information Delete Event

And it is can be clear at [Erase record] of [Device Setting] as necessary.

61
② Fault Infomation
You select [Fault Info.] at Menu of Records. This menu represent 1ea at
screen until max 1024ea to various information of fault. Records of before and
after can be check using right second or third button [▲], [▼].

PROMET5300 record information of fault as below follows.

Saved contents
Fault occurrence time(year/month/day/hour/min/sec/mS)
Fault ID
Fault occurring phase (A/B/C/N)
Operation relay factor
Size and phase angle of the fault current by each phase

And it is can be clear at [Erase record] of [Device Setting] as necessary.

62
③ Counter Operation
Select [Device information] menu on the detail menu screen. This menu will
display number of Fault or Trip occurrence.

Information of counter is as below follows.

- Trip Count : when PROMET5300 operated, Trip-output mean count.


- CB Operation(ON) Count: when PROMET5300 operated, Count of CB-ON mean
count.
- DSP Colt Reset : ON of PROMET5300 mean count.
- DSP Warm Reset : Soft Reset of PROMET5300 mean count.

And it is can be clear at [Erase record] of [Device Setting] as necessary.

63
④ Load Profile
Select [Load Profile] menu on the detail menu screen. This menu represent
Active/Reactive & Delivered/Receive Power every 15 minutes.

⑤ This month maximum measurement


Select [This month maximum measurement] menu on the detail menu screen.
This menu will display this month maximum voltage. and current.

64
⑥ This month minimum measurement
Select [This month minimem measurement] menu on the detail menu screen.
This menu will display this month minimum voltage and current.

⑦ Last month maximum measurement


Select [Last month maximum measurement] menu on the detail menu screen.
This menu will display last month maximum voltage and current.

65
⑧ Last month minimum measurement
Select [Last month minimum measurement] menu on the detail menu screen.
This menu will display last month minimum voltage and current.

5.2.11. Monitoring information


Select forth item on the Main Menu screen [Monitoring].

66
You select [Monitoring] at Menu. This menu represent information of
monitoring. If you want previous display, Right first button [UP] push.

Information of monitoring is below figure.

67
① DI state
Select [DI State] menu on the detail menu screen. This menu displays input
contact state of 32 EA. Control menu of right side([▼], [▲]) can check input
contact state of DI1~DI16 / DI16~DI32.

68
② DO State
Select [DO State] menu on the detail menu screen. This menu displays output
contact state of TRIP, CB ON, CB OFF etc,. 16 EA.

③ Diagnostic State
Select [Diagnostic State] menu on the detail menu screen. This menu displays
problem state of current equipment(Fault Occur, Setting Fail).

69
④ Device information
Select [Device information] menu on the detail menu screen. This menu will
display hardware and software versions.

70
5.2.12. Device Setting
Select fifth item on the Main Menu screen [Device Setting]. This menu
check or change various setting-values for operation of PROMET5300.

You select [Device Setting] at Menu. This menu represent setting of device.
If you want previous display, Right first button [UP] push.

71
Setting of device is below figure.

① System Setting
Select [System Setting] menu on the detail menu screen. This menu can set
connection, CT ratio, and PT ratio, etc. Set method is same as OCR.

72
② Active relay factor
Select [Active relay factor] menu on the detail menu screen. This menu can
be set use or not activation. Set method is same as OCR.

③ Clock Set
Select [Clock Set] menu on the detail menu screen. This menu can set the
system time. Set method is same as OCR.

73
④ Network Set
Select [Network Set] menu on the detail menu screen. This menu can set IP,
Subnet Mask and SNTP IP of IED. Set method is same as OCR.

⑤ Goose Set
Select [Goose Set] menu on the detail menu screen. This menu can be set
use or not Goose Message. Set method is same as OCR.

74
⑥ RS485 Set
Select [RS485 Set] menu on the detail menu screen. This menu can set Rs485
communication protocol. Set method is same as OCR.

⑦ MISC
Select [MISC] menu on the detail menu screen. This menu can be set use or
not AI, Goose-acctvation, number of DI Board. Set method is same as OCR.

75
⑧ Delete record
Select [Delete record] menu on the detail menu screen. This menu can clear
saved Record. [Delete All] is delete all in front of record. Set method is same
as OCR.

⑨ Assign
Select [Assign] menu on the detail menu screen. This menu can be allocate

for DI at CB. Set method is same as OCR.

76
6. Installation and Operation

① It is properly check and make sure CONNECTION, and then


Control-Power turn On.

② CT/PT ratio check from System Config. Menu, and if necessary CT/PT
adjusted according to ratio.

③ After check from System Config. Menu, the necessary adjusts.

④ After check Alarm-Contact from DO Config. Menu, necessary adjusts.

⑤ After check relay-set from Relay-Setting-Menu, necessary adjusts.

⑥ After the adjustment of PROMET5300, and then return to normal.

⑦ SYS-FAIL LED turn off, periodically flashing RUN LED in the front
panel, this is NORMAL-DRIVING in the state.

77
7. Product Connection

① residual circuit type for CT-wiring

78
② ZCT circuit type for CT-wiring
③ DO Type 1 : DO 12EA
③ DO Type 2 : DO 7EA
82-
31-
427-
8300 82-
31-
427-
8302

82-
31-
427-
8300 82-
31-
427-
8302

HTTP:
//
WWW.
NEOPI
S.KR

NEOPI
S@NEOPI
S.KR