Promet5300 Eng V1 1
Promet5300 Eng V1 1
NEOPI
S.KR
1. Safety Information
! A ttention
B efore install the prod uct, p lease read the
u ser m an ual.
◆ Compact of Facilities
Switchboards used to relay multiple existing analog to digital one relay to
implement the Compact and to install and configure the electronic switchboards
operation convenience.
1
Fault Event
It stores and manages various fault information (occurring time, kind of
fault, operation relay element and etc.) upon line accident in the order of
occurring time up to 1024 pieces.
◆ Logic Function
PROMET5300 can be output LOGIC(= AND, OR, Latch etc.) with DO or
communication after it is received download with back and side port
information of the internal IED.
2
3. Technical Data
◆ Output Contacts
- Type 1 (A Contacts)
3
3.2. Communication & Type-Tests Environment
◆ Communication
Classification Specifications
CH1 : Optical Communication(Optic Fiber )
100M Ethernet LC type
Type
CH2 : Optical Communication(Optic Fiber )
100M Ethernet LC type
Baud Rate 100M bps
PROTOCOL IEC61850, MODBUS-TCP
CH3 : RS485 Two-wire, Half duplex, isolated
Type
Side Communication Port : USB Port Serial
Baud Rate 1200/2400/4800/9600/19200/38400/57600/115200 bps
PROTOCOL MODBUS-RTU, DNP3.0, IEC60870-5
◆ Type-Tests Environment
Items Specifications
Operating
-20 ~ 60C
Temperature
Temperature
Storage
-25 ~ 70C
Temperature
Humidity Daily average 30 ~ 80%
Insulation
> 10MΩ
Resistance
AC Voltage Tests AC 60Hz 2000V/1min
4
3.3. Mechanical performance and size
◆ Weight : 8.8kg
◆ Front view
◆ Side view
5
◆ Upper side view
6
◆ Cutting Size
7
4. Installation Instructions
4.1. Front panel Layout
Display panel
Power LED ㆍColor Graphic LCD
Relay Operation
RUN LED ㆍ800 × 480 Resolution
Sign LED
SYS Fail LED
Fault RESET
Key
Local/Remote
(On:Local)
LED/Button
CB1 ON Sign
LED/Button
CB2 ON Sign
LED/Button
8
4.2. Terminal view
4.2.1. PROMET5300 Terminal View (Rear View)
E D C B A
B Terminal Composition
B1 B3 B5 B7 B9 B11 B13 B15 B17
IA+ IB+ IC+ IN+ VA+ VB+ VC+ VN+ Vbus
+
B2 B4 B6 B8 B10 B12 B14 B16 B18
IA- IB- IC- IN+ VA- VB+ VC+ VN+ Vbus
-
C Terminal Composition
- Type 1 (Trip, Alarm Contacts / A Contacts) : DO 12EA
9
- Type 2 (Trip, Warning Contacts A/B Contacts) : DO 7EA
C1 C3 C5 C7 C9 C11 C13 C15 C17
DO1+ DO2+ DO3 DO3 DO4 DO5 DO5 DO6 DO7
CBOFF CBON A COM A A COM A A
C2 C4 C6 C8 C10 C12 C14 C16 C18
DO1+ DO2- DO3 DO4 DO4 DO5 DO6 DO6 DO7
CBOFF CBON B COM B B COM B COM
D Terminal Composition
D1 D3 D5 D7 D9 D11 D13 D15 D17
DI2 DI4 DI6 DI8 DI DI10 DI12 DI14 DI16
COM2
D2 D4 D6 D8 D10 D12 D14 D16 D18
DI1 DI3 DI5 DI7 DI DI9 DI11 DI13 DI15
COM1
E Terminal Composition
- Type 1 : Apply the DI24 module
E1 E3 E5 E7 E9 E11 E13 E15 E17
DI18 DI20 DI22 DI24 DI DO AI1 - -
COM3 Alm
B
E2 E4 E6 E8 E10 E12 E14 E16 E18
DI17 DI19 DI21 DI23 DO DO AI2 AI -
Alm Alm COM
Com A
F Terminal Composition
F1 F3 F5 F7 F9 F11 F13 F15 F17
- - - - - - - - -
F2 F4 F6 F8 F10 F12 F14 F16 F18
- - - - - - - - -
10
5. Operating Instructions
5.1. Function
5.1.1. Protective Relay Function
1) Protective operating characteristics for over current
◆ Normal Inverse curve
æ 0.14 ö Tm
Toperate = çç 0.02
÷´
÷ 10
è ( I / I s ) - 1 ø
11
◆ Very Inverse curve
æ 13.5 ö Tm
Toperate = çç ÷´
÷ 10
è ( I / I s ) - 1 ø
12
◆ Extremely Inverse curve
×
13
◆ KEPCO Normal Inverse curve
æ 0.11 ö T
Toperate = çç 0.02
+ 0.42 ÷÷ ´ m
è (I / I s ) - 1 ø 10
14
◆ KEPCO Very Inverse curve
×
15
◆ IEEE EI curve
æ 28.2 ö Tm
Toperate = çç 2.0
+ 0 . 1217 ÷´
÷ 10
è ( I / I s ) - 1 ø
16
◆ Long Inverse curve
æ 120 ö Tm
Toperate = çç ÷´
÷
( )1
è I / I s - 1 ø 10
17
2) Protective operating characteristics for over current for OVGR
◆ OVGR for TRIP(59GT) KEPCO Very Inverse Curve
æ 12.15 ö T
Toperate = çç + 0.35 ÷÷ ´ m
è (V / Vs ) - 1
2
ø 10
18
◆ OVGR for ALARM(59GT) KEPCO Very Inverse Curve
æ 24.75 ö T
Toperate = çç + 4.15 ÷÷ ´ m
è (V / Vs ) - 1
2.23
ø 10
19
3) Protective operating characteristics for UVR
◆ 27 KEPCO Normal Inverse curve
æ 8.0 ö Tm
Toperate = çç ÷´
2.2 ÷
è 1 - (V / Vs ) ø 10
20
4) Protective operating characteristics for THR
◆ Thermal protective(Cold Curve)
2
I2 -Ip
T = t × log 2
I 2 × (k × I b )
21
◆ Thermal curve(Hot)
2
I2 -Ip
T = t × log 2
I 2 × (k × I b )
22
Setting range and characteristic of relay protection functions.
◆ OCR Relay
◆ OCGR Relay
1) Residual Circuit and usual ZCT input
23
2) Low Current ZCT Input(ex : GS-5)
◆ UVR Relay
24
◆ OVGR Relay
◆ OVR Relay
◆ POR Relay
◆ SYNCH25 Relay
25
◆ THR Relay
◆ 51LR Relay
◆ 48ST Relay
◆ NSOCR Relay
26
5.1.2. Recording Function
1) Operating Record
PROMET5300 stores information related to the IED operation up to maximum 4094
pieces in the Nonvolatile memory(FRAM). Since it stores data by the occurrence
time(SOE: Sequence Of Event) in the resolution of 1mSec, it is possible to trace
event. Item and content to be stored in the operation record is as follows.
27
5.2. Operation and Setting function
5.2.1. Operation status LED
The operation status of the relays, as shown below, an LED display visible
actions LED, Power LED, Pickup LED, Alarm and Trip LED 6 EA. Each
configuration is as follows.
◆ Power LED
This LED display power status of PROMET5300. When PROMET5300’s power
status is normal, Power LED will turn on green.
◆ RUN LED
This LED display operation status of PROMET5300. When PROMET5300
self-diagnosis status is normal, RUN LED will turn on green.
◆ SYS_FAIL LED
Off during normal behavior and, if diagnostic devices, at least judging by Fail
when the yellow light, and LED, LED diagnostic information to determine what items
can be diagnosed through the menu.
◆ FAULT LED
Setting-value over the current behavior of the fault is maintained. Trip time
when action is set in the output contacts, and the Fault LED will turn on red.
Fault to return the user to turn off the LED Fault Reset key is pressed.
◆ Alarm LED
Over the alarm setting Current is approved the alarm is maintained. When
become set operating time, the alarm contact output. Fault LED will turn on
red. After returning the alarm. If user push the Fault Reset key, LED will turn
off.
◆ PICK-UP LED
The behavior over setting-value relays the signal is when the yellow Pickup LED
blinks. Current-Value and Voltage-Value are setting-value LED turn off down below.
28
5.2.2. CB status LED
LED(CB OPEN LED, CB ON LED, Local LED etc,. 5EA) for the status of CB as
follows. Each configuration is as follows.
◆ LOCAL LED
This have button which CB in Control on LED-communication at local or
remote. If LOCAL have control, LED turn on. If remote have control,LED turn off.
◆ CB1_ON LED
CB1_ON LED of PROMET5300 is button which CB1 is close or open. The red
LED will light when close .
◆ CB1_OPEN LED
CB1_Open LED of PROMET5300 is button which CB1 is close or open. The
green LED will light when open.
◆ CB2_ON LED
CB2_ON LED of PROMET5300 is button which CB2 is close or open. The red
LED will light when close .
◆ CB2_OPEN LED
CB2_Open LED of PROMET5300 is button which CB2 is close or open. The
green LED will light when open.
29
5.2.3 Menu key operation
MENU-MOVE and CONTROL of PROMET5300 operate as shown below. Button of
display bottom(5ea) and right(4ea) push, hardware operate displayed-contents.
Bu
tt
on
6
Bu
tt
on
7
Bu
tt
on
8
Bu
tt
on
9
● MENU MOVE
Button(5ea) of display bottom use when Menu move. Button 4ea from left use
menu selection and moving, and fifth right button use when next-menu move.
30
● Control Key
Right-side of LED screen will show four cells. This cells shows control-menu
SELECT, CANCEL, SAVE. etc.
Local/Remote
31
At first, LOCAL-key push. Right buttons use second[◀], third[▶], and Yes or
or NO select. If you want when another mode change, LOCAL-key push. and
next-flow is same.
32
② CB1,2 Open/Close
If you want CB1,CB2, button use as shown below.
CB1 OPEN
CB2 OPEN
CB1 CLOSE
CB2 CLOSE
33
Local is situation, display represent as shown below. Right buttons use
second[◀], third[▶], and Yes or or NO select.
Fault Clear
34
When Fault occurred, upper of display change [Nomal status] to [FAULT
OCCURED].
At this moment, Fault Clear key is pressed the screen will change as follows.
35
5.2.6. UI menu structure map
Menu hava main-menu and sub-menu.
main
Menu sub-menu content
start-up single line diagram single line diagram situation
General General Measurement display
Vector DIG Voltage,Current for using Vector
Measures Quality THD, TDD, Thermal
V/I Details information of Voltage/Current
Sync Information between Bus-Line
OCR
OCGR
UVR
UVR_ALARM
OVR
OVGR
Relay
POR Relay setting and check
Setting
NSOCR
THR
51LR
48STALL
SYNCH25
UVR_SYNC
operation information operation of CB operation etc,
Fault information Fault Record of Fault-operation etc.
action Counter counter of WatchDog Reset etc.
Load Profile Profile information
Present month Max Measurement Value etc. of
Records Max Measurement Present month
Present month Min Measurement Value etc. of
Min Measurement Present month
Last month Max Measurement Value etc. of
Max Measurement Last month
Last month Min Measurement Value etc. of
Min Measurement Last month
DI status Input status of 32ea
DO status Output status of 16ea
Monitoring
Monitoring status Error of IED
Device status Version of H/W, S/W
System CT ratio, PT ratio, wiring etc.
Protection Active/Deactive of Protection element
Time Time of System
Device Goose Goose Message Enable
Network IP of IED
Setting
RS485 communication of RS485
MISC Use A, count board of DI etc.
Erase record wh, event, fault
contact DI contact assignment
36
5.2.7. Start-up Screen
This is Start-up Screen, and this is represented single line diagram situation , line
voltage, line current.
5.2.8. Measures
First Button of bottom push [Measures]. If you want previous display, Right
first buttons [UP].
37
sub-menu of [Measures] is [General],[Vector DIG],[Quality],[V/I],[Sync]
as shown below.
38
① [General]
At first, you can select [General] at sub-menu of [Measures]. This menu
represent Line Voltage, Phase voltage, Frequence, Factor, Active/Reactive
Power, Active/Reactive Energy. If you want previous display, Right first buttons [UP].
② Vector DIG
You can select [Vector DIG] at sub-menu of [Measures]. This menu represent
Voltage, current, magnitude, phase of each phase, and Vector Diagram.
In especially Vector Diagram can be checked wiring of voltage, current. If you
want previous display, Right first buttons [UP].
39
③ Quality
You can select [Quality] at sub-menu of [Measures]. This menu represent
THD, TDD, Motor Thermal and find out quality of system. If you want previous
display, Right first buttons [UP].
④ V / I
You can select [ V / I ] at sub-menu of [Measures]. This menu represent
value, phase, positive/negative/zero-phase-sequence of voltage, current. If you
want previous display, Right first buttons [UP].
40
⑤ Sync
You can select [ Sync ] at sub-menu of [Measures]. This menu represent
voltage/ Frequence / phase of SYNC-LINE. If you want previous display, Right
first buttons [UP].
Second Button of bottom push [Relay Setting]. If you want previous display,
Right first buttons [UP] as belows.
41
sub-menu of [Relay Setting] is as shown below.
42
If system have occurred as shown below after activation for relay setting,
if you want to hide alarm screen, push anything among Buttons and Keys
except [FAULT RESET] Key. but, if you want to clear Trip, [FAULT RESET] Key
must be to push.
① Set OCR
Setting Range & Step & characteristic of OCR is as follows.
43
If you push right forth button [SET] for relay setting, password represent to
input in the screen. If you want previous display, Right first button [UP] push.
You can be located to 2 for right second or third button [◀], [▶]. You push
4times to right forth button [SEL] as below follows. If you want last inputted
number, use <- to right second or third button. If you want previous display,
Right first button [EXIT] push.
44
You can be located to change for right second or third button [▲], [▼].And
you push to right forth button [SEL], will change setting-value to [INC],[DEC].
you push to right forth button [OK] after changing setting-value. and push
first button [SAVE]. If you want to change another setting-value, push [SEL].
The method is same. If you want previous display, Right first button [EXIT] push.
45
46
② Set OCGR
Setting Range & Step & characteristic of OCGR is as follows. If ZCT-input-range
is 20~2000[mA] for measurement for zero-phase-sequence current, apply a
table as below follows.
47
Select [OCGR] menu on the detail menu screen.
[Residual Sensing]
[ZCT Sensing]
48
③ Set UVR
Setting Range & Step & characteristic of UVR is as follows.
49
④ Set UVR3
Setting Range & Step & characteristic of UVR3 is as follows.
50
⑤ Set UVR4
Relay of UVR4 is Voltage-terminal(Vbus 17.18) for SYNC except terminal of R,
S, T. Setting Range & Step & characteristic of UVR4 is as follows.
51
⑥ Set OVR
Setting Range & Step & characteristic of OVR is as follows.
52
⑦ Set OVGR
Setting Range & Step & characteristic of OVGR is as follows.
53
⑧ Set POR
Setting Range & Step & characteristic of POR is ad follows.
54
⑨ Set NSOCR
Setting Range & Step & characteristic of NSOCR is as follows.
55
⑩ Set THR
Setting Range & Step & characteristic of THR is as follows.
56
⑪ Set 51LR
Setting Range & Step & characteristic of 51LR is as follows.
57
⑫ Set 48ST
Setting Range & Step & characteristic of 48ST is as follows.
58
⑬ Set SYNCH25
Setting Range & Step & characteristic of SYNCH25 is as follows.
59
5.2.10. Records information
On the Main Menu screen, select the third item [Records].
If you select, represent menu of Records. If you want previous display, Right
first button [UP] push.
60
Menu of Records is same as below follow.
① Op. Info.
You select [Op. Info] at Menu of Records. This menu represent 10ea at screen
until max 4094ea to various records of operation. Records of before and after
can be check using right second or third button [▲], [▼]. Menu of [Op. Info]
is convenient at Event Trace according to occurrence-time.
61
② Fault Infomation
You select [Fault Info.] at Menu of Records. This menu represent 1ea at
screen until max 1024ea to various information of fault. Records of before and
after can be check using right second or third button [▲], [▼].
Saved contents
Fault occurrence time(year/month/day/hour/min/sec/mS)
Fault ID
Fault occurring phase (A/B/C/N)
Operation relay factor
Size and phase angle of the fault current by each phase
62
③ Counter Operation
Select [Device information] menu on the detail menu screen. This menu will
display number of Fault or Trip occurrence.
63
④ Load Profile
Select [Load Profile] menu on the detail menu screen. This menu represent
Active/Reactive & Delivered/Receive Power every 15 minutes.
64
⑥ This month minimum measurement
Select [This month minimem measurement] menu on the detail menu screen.
This menu will display this month minimum voltage and current.
65
⑧ Last month minimum measurement
Select [Last month minimum measurement] menu on the detail menu screen.
This menu will display last month minimum voltage and current.
66
You select [Monitoring] at Menu. This menu represent information of
monitoring. If you want previous display, Right first button [UP] push.
67
① DI state
Select [DI State] menu on the detail menu screen. This menu displays input
contact state of 32 EA. Control menu of right side([▼], [▲]) can check input
contact state of DI1~DI16 / DI16~DI32.
68
② DO State
Select [DO State] menu on the detail menu screen. This menu displays output
contact state of TRIP, CB ON, CB OFF etc,. 16 EA.
③ Diagnostic State
Select [Diagnostic State] menu on the detail menu screen. This menu displays
problem state of current equipment(Fault Occur, Setting Fail).
69
④ Device information
Select [Device information] menu on the detail menu screen. This menu will
display hardware and software versions.
70
5.2.12. Device Setting
Select fifth item on the Main Menu screen [Device Setting]. This menu
check or change various setting-values for operation of PROMET5300.
You select [Device Setting] at Menu. This menu represent setting of device.
If you want previous display, Right first button [UP] push.
71
Setting of device is below figure.
① System Setting
Select [System Setting] menu on the detail menu screen. This menu can set
connection, CT ratio, and PT ratio, etc. Set method is same as OCR.
72
② Active relay factor
Select [Active relay factor] menu on the detail menu screen. This menu can
be set use or not activation. Set method is same as OCR.
③ Clock Set
Select [Clock Set] menu on the detail menu screen. This menu can set the
system time. Set method is same as OCR.
73
④ Network Set
Select [Network Set] menu on the detail menu screen. This menu can set IP,
Subnet Mask and SNTP IP of IED. Set method is same as OCR.
⑤ Goose Set
Select [Goose Set] menu on the detail menu screen. This menu can be set
use or not Goose Message. Set method is same as OCR.
74
⑥ RS485 Set
Select [RS485 Set] menu on the detail menu screen. This menu can set Rs485
communication protocol. Set method is same as OCR.
⑦ MISC
Select [MISC] menu on the detail menu screen. This menu can be set use or
not AI, Goose-acctvation, number of DI Board. Set method is same as OCR.
75
⑧ Delete record
Select [Delete record] menu on the detail menu screen. This menu can clear
saved Record. [Delete All] is delete all in front of record. Set method is same
as OCR.
⑨ Assign
Select [Assign] menu on the detail menu screen. This menu can be allocate
76
6. Installation and Operation
② CT/PT ratio check from System Config. Menu, and if necessary CT/PT
adjusted according to ratio.
⑦ SYS-FAIL LED turn off, periodically flashing RUN LED in the front
panel, this is NORMAL-DRIVING in the state.
77
7. Product Connection
78
② ZCT circuit type for CT-wiring
③ DO Type 1 : DO 12EA
③ DO Type 2 : DO 7EA
82-
31-
427-
8300 82-
31-
427-
8302
82-
31-
427-
8300 82-
31-
427-
8302