EXTERNAL STATIC PRESSURE CALCULATIONS

Specia Duct Equiv. Velocity Duct Press. Fitting Total Press.


Description Air Flow Rectangular Duct Size (mmxmm) Duct Fitting Loss Velocity Head Loss Friction Reynold
Sr.No Floor equip. Loss Length Diameter Pressure (in Loss (in Press. Loss Loss (in
(CFM) Length (m) Coeff. (fpm) per 100' Factor Number
(in w.g.) (ft) Dh (in) w.g.) w.g.) (in w.g.) w.g.)

1 Supply Duct 4,250 800 x 500 2.13 0.08 7.0 27.0 1066.2 0.071 0.056 0.01757 250,205 0.003899 0.00567 0.010
2 Supply Transition 4,250 800 x 500 0.40 0.47 1.3 27.0 1066.2 0.071 0.056 0.01757 250,205 0.000732 0.03331 0.034
3 Supply Duct 4,250 600 x 450 3.03 0.08 10.0 22.3 1566.1 0.153 0.141 0.01703 303,245 0.014077 0.012233 0.026
4 Supply Transition 3,450 600 x 450 0.40 0.31 1.3 22.3 1271.3 0.101 0.097 0.01766 246,163 0.001269 0.031238 0.033
5 Supply Duct 3,080 500 x 400 7.24 0.08 23.8 19.2 1529.1 0.146 0.162 0.01759 255,080 0.038424 0.011662 0.050
6 Supply VD 2,760 500 x 400 0.30 9.00 1.0 19.2 1370.2 0.117 0.132 0.01794 228,578 0.001303 1.053483 1.055
7 Supply Duct 2,760 400 x 300 3.79 0.08 12.4 14.9 2288.4 0.326 0.459 0.01725 295,396 0.056975 0.026119 0.083
13 Supply Transition 2,760 400 300 0.37 0.26 1.2 14.9 2288.4 0.326 0.459 0.01725 295,396 0.0056 0.084886 0.090
14 Supply Duct 2,760 350 x 250 1.71 0.08 5.6 12.7 3144.3 0.616 0.994 0.01688 346,259 0.055586 0.04931 0.105
16 Supply Damper 2,500 350 x 250 0.20 8.00 0.7 12.7 2848.1 0.506 0.828 0.01715 313,640 0.005436 4.045763 4.051
17 Supply Duct 2,500 300 x 250 8.75 0.08 28.7 11.8 3306.3 0.682 1.191 0.01699 337,930 0.341997 0.054523 0.397
Supply 5.933
TOTAL 0.00 TOTAL 5.933
Total External Static Pressure (in w.g.) = 5.933
ESP with 10% safety factor (in w.g.) = 6.526 1625.049
Total External Static Pressure (Pa) = 1625
Abbreviations:-
1) CFM :Cubic Feet Per Minute 2)FPM: Feet Per Minute 3)in WC: Inches Water Column 4)Pv = Velocity pressure in inches of water column

Notes:-
1) Friction Coefficient for Duct fittings is as per (ASHRAE Handbook 2009, SMACNA Fourth Edition)
2) Pressure loss through Volume Control Damper and Exhaust Air Louver is calculated by using the Pressure Drop Detail Catalogue.
4) Pressure loss through Duct is Verefied and Calculated through "McQuay"Design Tools Duct Sizer .
5) Friction Factor through Duct is Verefied and Calculated through "McQuay"Design Tools Duct Sizer .