Overall Heat Transfer

Coefficient
Heat Exchangers
Numerical 1
Calculate the overall heat transfer coefficient of heat
transfer between water and oil if the water flows through a
copper tube of 180 mm inside diameter and 15 mm thick
while the oil flows through the annulus formed by this pipe
and an outer concentric pipe. The thermal conductivity of
the tube wall is 349 W/mK and the fouling factors on the
oil and water side are 0.00086 and 0.000344 respectively.
The oil and water side heat transfer coefficients can be
taken as 1280 and 4650 W/m2K respectively.

16-08-2022 Dr MMJ Kumar 2


Numerical 2
A horizontal steel pipe of 5.25 cm I.D and 6.03 cm O.D is
exposed to atmospheric air at 20oC. Hot water at 98oC
flows through this pipe with a velocity of 15 m per minute.
Taking the following data, calculate the overall heat
transfer coefficient, based on outer area of the pipe.
k for steel = 54 W/mK.
hi = 1961 W/m2K.
ho = 7.91 W/m2K

16-08-2022 Dr MMJ Kumar 3


Numerical 3
Calculate the overall heat transfer coefficient based on the
outer area of the pipe in Problem 2, if it is now exposed to
steam at 1 atm and 100oC with
ho = 32790 W/m2K

16-08-2022 Dr MMJ Kumar 4


Numerical 4
Determine the overall heat transfer coefficient based on the
outer area of a 3.81 cm O.D and 3.175 cm I.D. brass tube
(k = 103.8 W/mK) if the heat transfer coefficients for flow
inside and outside the tube are 2270 and 2840 W/m2K,
respectively, and the unit fouling resistances at inside and
outside surfaces are Rfi = Rfo = 8.8 x 10-3 m2K/W.

16-08-2022 Dr MMJ Kumar 5


Numerical 5

16-08-2022 Dr MMJ Kumar 6


Numerical 6

16-08-2022 Dr MMJ Kumar 7


Numerical 7

Saturated steam at 1200C is condensing on the outer surface of a single


pass heat exchanger. The heat transfer coefficient is U0 = 1800 W/m2K.
Determine the surface area of heat exchanger capable of heating 1000
kg/h of water from 200C to 900C. Also compute the rate of
condensation of steam. Take hfg =2200 kJ/kg.

16-08-2022 Dr MMJ Kumar 8


Numerical 8

A double-pipe counter flow heat exchanger transfers heat between two


water streams. If 19 kg/s of water is heated in the tubes from 10 to 400 C
with 25 kg/s of inlet water on the shell side at 460 C, then what are the
effectiveness and LMTD of the heat exchanger? The specific heat of
water is 4.18 kJ/kg K.

16-08-2022 Dr MMJ Kumar 9


Numerical 9

In a double pipe counter flow Heat Exchanger. 10000 kg/h of an oil


having a specific heat of 2095 J/kg.K is cooled from 800C to 500C by
8000 Kg/h of water entering at 250C .Determine the heat exchanger area
for an overall heat transfer coefficient of 300 W/m2.K. Take Cp for
water as 4180 J/kg.K.

16-08-2022 Dr MMJ Kumar 10


Thank You

Dr. M. Mohan Jagadeesh Kumar

16-08-2022 Dr MMJ Kumar 11