Professional Documents
Culture Documents
Ducting Design
Ducting Design
Duct Design
The chapter presents the ducting calculations for sizing the appropriate duct
needed for the system. Standard values are needed to be used as basis for design
parameters. The sizing of ducts and pressure drops are obtained through calculations
using table and charts. The blue lines represent the supply ducts while the red lines
represent the return ducts
3.2 Zoning
Figure 3.1 below shows the zoning layout of zone 1 that will be used for the initial
computation.
Supply
Return
Where:
Qtotal= cooling load of room/zone, kW
Mair= mass flow rate of air, kg/s
Vair= specific volume of air, m3/kg
hinside= specific enthalpy of room/zone, kJ/kg
hsupply= specific enthalpy of coil, kJ/kg
hsupply=36.719 kJ/kg
FOR ZONE 1:
This section shows the computation for the mass flow rate of air, the total volume
of supply air and the duct diameter for the main duct to be used in zone 1. The equation
for mass flow rate is shown below.
Qtotal= Mair(hinside-hsupply)
( )
1 kJ
s
106928.46 W = M air (73.77−36.719) kJ /kg
1000 W
M air=2.89 kg/ s
The computed mass flow rate of air for zone 1 is 2.89 kg/s. The equation and
computation for CFM is shown below where the acquired mass flow rate is used.
CFM =(M air)(V air)
Where:
Mair= 2.89kg/s
Mair= V at 13°C= 0.8225 m3/kg
3 3
CFM =(2.89 kg / s)(0.8225m /kg) ( 3.28 ft / m ) (60 s / min)
3
CFM =5032.76 f t /min
The computation for mass flow rate of air, the total volume of supply air and the duct
diameter for the main duct will be the same to all zone.
Since zone 2&3 have the same rooms and cooling load computation, the amount
of air supplied for both of the zones are equal.
Qtotal= Mair(hinside-hsupply)
1 kJ /s
97390.81 W ( )=M air (73.77−36.719)kJ /kg
1000W
M air=2.63 kg/ s
The computed mass flow rate of air for zone 2&3 is 2.63 kg/s. The equation and
computation for CFM is shown below where the acquired mass flow rate is used.
CFM =(M air)(V air)
Where:
Mair= 2.63 kg/s
Mair= V at 13°C= 0.8225 m3/kg
3 3
CFM =(2.63 kg / s)(0.8225m /kg) ( 3.28 ft / m ) (60 s / min)
3
CFM =4579.99 f t /min
FOR ZONE 4:
Qtotal= Mair(hinside-hsupply)
1 kJ /s
94785.87 W ( )=M air (73.77−36.719)kJ /kg
1000 W
M air=2.56 kg /s
The computed mass flow rate of air for zone 4 is 2.56 kg/s. The equation and
computation for CFM is shown below where the acquired mass flow rate is used.
CFM =(M air)(V air)
Where: Mair= 2.56 kg/s
Mair= V at 13°C= 0.8225 m3/kg
3 3
CFM =(2.56 kg /s)(0.8225 m /kg) ( 3.28 ft /m ) (60 s/min)
3
CFM =4458.09 f t /min
Rair= 0.5Sair
Where:
Sair=supply air, ft3/min
Rair=return air, ft3/min
FOR ZONE 1:
Rair =0.5(S air )
Rair =0.5(5032.76)
3
Rair =2516.38 f t /min
The return air needed for zone 1 is 2516.38 ft 3/min .it is calculated by multiplying
the supply air by 50 %. The computations are shown above
The computation for return will be the same to all zone.
Rair =0.5(4579.99)
FOR ZONE 4:
Rair =0.5(S air )
Rair =0.5(4458.09)
3
Rair =2229.05 f t /min
Return Air
FOR ZONE 1:
5032.76 CFM
No . of diffusers for supply=
200 CFM
No . of diffusers for supply =25.16
No . of diffusers for supply =26 diffusers
2516.38CFM
No . of diffusers for return=
200CFM
No . of diffusers for return=12.58
No . of diffusers for return=13 diffusers
2290.00CFM
No . of diffusers for return=
200CFM
No . of diffusers for return=11.45
No . of diffusers for return=12 diffusers
FOR ZONE 4:
4458.09 CFM
No . of diffusers for supply=
200 CFM
No . of diffusers for supply =22.29
No . of diffusers for supply=23 diffusers
22929.05CFM
No . of diffusers for return=
200CFM
No . of diffusers for return=11.15
No . of diffusers for return=12 diffusers
Table 3.4 Summary of no. of Diffuser per zone
D=
√ 4 V air
vπ
Where: D= diameter of duct (fy or mm)
Vair= volume flow rate of air in duct or diffuser (cfm)
v= velocity of air (fpm)
The recommended main duct velocity is 2000 fpm and branch duct velocity is 1600 fpm
(Carrier, 2014).
ZONE 1
Using the formula above, and the computed CFM, the acquired diameter is rounded
down in order to achieve the minimum acceptable air velocity. The result is tabulated
below:
ZONE 2&3
ADJUST
ED
SECTI ADJUST DIAMET DIAMET
ON ED CFM ER (in.) ER (in.)
A1 200 4.28 4
A2 400 6.06 6
A3 600 7.42 7
A4 800 8.56 8.5
A5 1000 9.57 9.5
A6 1200 10.49 10
A7 200 4.28 4
B1 1400 11.33 11
B2 1600 12.11 12
B3 1800 12.85 12.5
B4 2000 13.54 13.5
B5 2200 14.2 14
B6 2400 14.83 14.5
B7 200 4.28 4
C1 200 4.28 4
C2 400 6.06 6
C3 600 7.42 7
C4 800 8.56 8.5
C5 1000 9.57 9.5
C6 1200 10.49 10
C7 1400 11.33 11
C8 1600 12.11 12
C9 1800 12.85 12.5
C10 2000 13.54 13.5
m1 2600 15.44 15
m2 4600 20.54 20.5
ZONE 4
ADJUST
ED
SECTI ADJUST DIAMET DIAMET
ON ED CFM ER (in.) ER (in.)
A1 200 4.28 4
A2 400 6.06 6
A3 200 4.28 4
A4 600 7.42 7
A5 800 8.56 8.5
m1 1000 9.57 9.5
B1 200 4.28 4
B2 400 6.06 6
B3 600 7.42 7
B4 800 8.56 8.5
B5 1000 9.57 9.5
B6 1200 10.49 10
B7 200 4.28 4
B8 200 4.28 11
B9 400 6.06 6
B10 1800 12.85 12.5
B11 2000 13.54 13.5
B12 2200 14.2 14
B13 2400 14.83 14.5
B14 200 4.28 4
m2 3600 18.17 18
C1 200 4.28 4
C2 400 6.06 6
C3 600 7.42 7
C4 800 8.56 8.5
m3 4400 20.08 20
Return
Zone 1- 3
ADJUSTE
SECTI ADJUST DIAMET D
ON ED CFM ER (in.) DIAMETE
R (in.)
1 100 3.03 3
2 100 3.03 3
r-a 200 4.28 4
3 100 3.03 3
r-b 300 5.24 5
4 100 3.03 3
r-c 400 6.06 6
5 100 3.03 3
r-d 500 6.77 6.5
6 100 3.03 3
r-e 600 7.42 7
7 100 3.03 3
r-f 700 8.01 8
r-g 700 8.01 8
8 100 3.03 3
r-h 800 8.56 8.5
9 100 3.03 3
r-i 900 9.08 9
10 100 3.03 3
r-j 1000 9.57 9.5
11 100 3.03 3
r-k 1100 10.04 10
12 100 3.03 3
r-l 1200 10.49 10
Zone 4
ADJUSTE
SECTIO ADJUSTE DIAMETE D
N D CFM R (in.) DIAMETE
R (in.)
1 100 3.03 3
2 100 3.03 3
r-a 200 4.28 4
3 100 3.03 3
r-b 300 5.24 5
4 100 3.03 3
5 100 3.03 3
r-c 500 6.77 6.5
6 100 3.03 3
r-d 600 7.42 7
7 100 3.03 3
r-e 700 8.01 8
8 100 3.03 3
9 100 3.03 3
r-f 900 9.08 9
10 100 3.03 3
r-g 1000 9.57 9.5
11 100 3.03 3
12 100 3.03 3
r-h 1200 10.49 10
r-i 1200 10.49 10
Zone 1
Zone 1 is the ground floor of the school building. The total supply air needed for this
zone is 5200 ft3/min. The static pressure in the supply duct system is 3.3 in WC. The
return air system is 2400 ft 3/min. The static pressure in the return duct system is 2.8 in
WC. below shows the supply and return layout for zone 1.
Supply
Supply
Supply
AHU Selection 4
Supply Duct Return Duct
Supply Air Static Pressure Return Air Static Pressure
Cfm in WC CFM in WC
4600 3.26 2400 2.53