(8 - BUILDINGS) PRIVATE PALACE

Contract No: Project Name: SHEET Location Test Date :

Ect-13-575-R (8 - BUILDINGS) PRIVATE PALACE 1 OF 1 Al Wajba 14-Sep-21

GENERAL DATA
Equipment: FCU - 02 - 01
Equipment Location : Loundry BS - 07 Fan Model : HFCF14

Area Served : Loundry BS - 07 Serial Number : N/A

Equipment Manufacturer : Trane Tag No : FCU - 02

Fan Specified Actual %


SPEED
LOW

Total air flow rate CFM - Outlet OK


MEDIUM
SPEED

Total air flow rate CFM - Outlet 1,008 709 70%


SPEED
HIGH

Total air flow rate CFM - Outlet OK

Motor Data Design Actual

Motor Manufacturer N/A

Motor kW 0.23

Phase / Hz 1/50

Average Voltage (L1-L2/L2-L3/L1-L3) 240 236

Average Amperage (L1/L2/L3) 1.07 1.05

REMARKS :-

Testing & Balancing Mep Contractor Main Contractor Client Consultant


Jumbo Electromech SHK/Khaled Bin Abdul
CSI Engineering Services Al Bandary Engineering James Cubitt & Partners
Engineering Rahman Al Thani

Name : Jovel Ortiz

Signature :

Date: 23-Nov-2022
AIR DISTRIBUTION TERMINAL SHEET

(8 - Buildings) Private Palace

S/N System No. Location Area Served Terminal Size Design CFM Actual CFM % Remarks
FCU - 02 - 01
1 FCU - 02 - 01 Loundry BS - 07 Loundry BS - 07 375x375 504 357
2 FCU - 02 - 01 Loundry BS - 07 Loundry BS - 07 375x375 504 352
1,008 709 70%

10
(8 - BUILDINGS) PRIVATE PALACE

Contract No: Project Name: SHEET Location Test Date :

Ect-13-575-R (8 - BUILDINGS) PRIVATE PALACE 1 OF 1 Al Wajba 14-Sep-21

GENERAL DATA
Equipment: FCU - 02 - 02
Equipment Location : Toilet - BS - 20 Fan Model : HFCF14

Area Served : Storage - BS 20 Serial Number : N/A

Equipment Manufacturer : Trane Tag No : FCU - 02

Fan Specified Actual %


SPEED
LOW

Total air flow rate CFM - Outlet OK


MEDIUM
SPEED

Total air flow rate CFM - Outlet 1,008 717 71%


SPEED
HIGH

Total air flow rate CFM - Outlet OK

Motor Data Design Actual

Motor Manufacturer N/A

Motor kW 0.23

Phase / Hz 1/50

Average Voltage (L1-L2/L2-L3/L1-L3) 240 237

Average Amperage (L1/L2/L3) 1.07 0.89

REMARKS :-

Testing & Balancing Mep Contractor Main Contractor Client Consultant


Jumbo Electromech SHK/Khaled Bin Abdul
CSI Engineering Services Al Bandary Engineering James Cubitt & Partners
Engineering Rahman Al Thani

Name : Jovel Ortiz

Signature :

Date: 23-Nov-2022