EMEG Annual Testing Report (Full Load Test)

THE BUILDING MAINTENANCE AND STRATA MANAGEMENT ACT (CHAPTER 30C)


BUILDING MAINTENANCE AND STRATA MANAGEMENT
(LIFT, ESCALATOR AND BUILDING MAINTENANCE)
REGULATIONS 2016 ("BMSM (LEBM) Regulations")
RECORDS OF INSPECTED ITEMS FOR FULL LOAD TEST OF LIFT
FOR APPLICATION FOR PERMIT TO OPERATE THE LIFT
Commissioner of Buildings INSTRUCTIONS:
Building and Construction Authority (1) *Delete Accordingly
52 Jurong Gateway Road (2) If "NA" is selected for any item, to indicate in the remarks column the
Website: http://www.bca.gov.sg/ reason(s) for selecting "NA" (e.g. lifts are of older design and code, etc).
(3) Status of all items should be "Ok" before submission
(4) This checklist is not exhaustive. Specialist professional engineers ("SPEs")
must exercise their due diligence and flag out any other safety-related and
other observations that may affect the operation of the lift and not listed in
this checklist

Location:________________________________________________________________________

Lift Number: __________ ("Lift") Year of Installation: ________ Type of Lift: *Home/Passenger/Cargo/Others

Number of stops: ______ Rated speed (m/sec): ______ *Machine Room / MRL Car Load:__________(kg)

Applicable code/yr.____________ Test Load: ____________(kg) Test Date: __________________

Machine room / Head room Status Remarks


1 Traction Motor Condition (coupling) *Ok/NA
2 Drive & Deflector Sheaves (groove profile/ropes condition) *Ok/NA
3 Gearbox (oil condition / backlash/ bearing) *Ok/NA
Effectiveness of Brakes (free plunger, lever movement, drum surface free from
4 *Ok/NA
oil)
5 Normal brake stopping distance (mm) __________ *Ok/NA
6 Emergency brake stopping distance (mm)__________ *Ok/NA
7 Controller and Electrical System *Ok/NA
8 Earth linkage to car top *Ok/NA
9 Governor rope Ø - Required (mm) ________ Measured(mm):___________ *Ok/NA
10 Governor pulley condition *Ok/NA
Governor tripping mechanism *Ok/NA
Overspeed switch function *Ok/NA
Flyweight move freely *Ok/NA
All linkages and moving parts free of defects *Ok/NA
Gripping jaw is able to effectively grip the rope *Ok/NA
11 Does the pull force of the governor effectively engage the
*Ok/NA
safety gear against the guide rails
Safety gear switch function *Ok/NA
For testing of the safety gear, after the safety gear is engaged, does the machine
*Ok/NA
run until the suspension rope slips or slacks?
Safety Gear stopping distance (mm):_______________ *Ok/NA
Ascending Car Over speed Protection:
12 Detection means used _______________________ *Ok/NA
Stopping means used _____________________

Unintended Car Movement Prevention


13 Car stopping distance in up direction_______________mm *Ok/NA
Car stopping distance in down direction _____________mm
14 Does the terminal speed reduction system function as intended *Ok/NA
15 Manual rescue means (electrical / mechanical) *Ok/NA
16 EBOPS function & Battery condition *Ok/NA
17 ARD function & Battery condition *Ok/NA
18 Load balance point range (%)___________ (Every 5 year) *Ok/NA
EMEG Annual Testing Report (Full Load Test)

Hoist way Status Remarks


Suspension Rope Condition
19 *Ok/NA
(broken wires, strand, rouging, rust )
20 Suspension rope diameter *Ok/NA
Required Ø (mm) ____________
Fill in the measured Ø of each rope (mm) in the table below:
Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope Rope
21 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Top /Bottom floor landings door lock/switches


22 All other landing doors/ emergency access door switches / Car emergency exit *Ok/NA
switch
23 Terminal stopping switches *Ok/NA
24 Car door switch *Ok/NA
Lift Car and Pit Status Remarks
25 25mm Car Door Gap Test on the doorway *Ok/NA
26 Car door mechanical lock function *Ok/NA
27 10mm Car & Landing Door Gap with door frame *Ok/NA
28 Function of door protection devices *Ok/NA
29 Door Linkages and associated Fastenings *Ok/NA
30 Door closing force measured__________KN *Ok/NA
31 Function of over-load weighing device, its alarm and indicator *Ok/NA
32 Car bottom clearance (mm)_____________ *Ok/NA
33 Max. allowable cwt runby signage / cwt runby *Ok/NA
Buffer Condition (proper fixing, oil level, oil leak, disintegrated )
34 *Ok/NA
Buffer type ____________________________
35 Buffer Switches *Ok/NA
36 All E-Stop switches - Machine / Pulley room, Hoistway, Car and Lift Pit *Ok/NA
37 Governor Rope Tension Pulley condition *Ok/NA
38 Pit Ladder (accessibility, condition) *Ok/NA
39 Pit cleanliness *Ok/NA
Ventilation / Illumination requirements
40 *Ok/NA
(Machinery space / Car top / Lift pit)
41 Proper safety signage are affixed *Ok/NA
EMEG Annual Testing Report (Full Load Test)

Any Other Observation


Observations:

42

Declaration for Lift Testing Contractor:

I, on behalf of the lift service contractor engaged by the owner of the lift to examine, inspect and test the Lift in accordance with
Regulation 7(1) of the BMSM (LEBM) Regulations ("lift testing contractor"), declare that:
(1) The measurements, observations and information as stated above are true and accurate as at the date of this submission.
(2) The lift testing contractor has carried out the examination, inspection and testing of the Lift, in the presence of the supervising SPE.
(3) The supervising SPE is not a partner, associate, director, officer or employee of the lift testing contractor carrying out the examination,
inspection and testing of the Lift.

Lift Testing Contractor:

Name of Representative:

Designation of Representative:

Date of Submission:
Declaration for Supervising SPE:

I, as the supervising SPE, declare that:


(1) I have checked and verified the measurements, observations and information, and I confirm that the measurements, observations and
information as stated above are true and accurate as at the date of this submission.
(2) I have witnessed the lift testing contractor carrying out the examination, inspection and testing of the Lift, and I confirm that the lift
testing contractor carried out the examination, inspection and testing of the Lift in my presence.
(3) I am of the opinion that the Lift is fit and safe for operation and use.
(4) I am not a partner, associate, director, officer or employee of the owner of the Lift or the lift testing contractor carrying out the
examination, inspection and testing of the Lift.

Name of Supervising SPE:

Date of Submission: