Professional Documents
Culture Documents
ANNEXURE 1.1-Soft Copy-30 Deg Dev Loading Calculation FINAL
ANNEXURE 1.1-Soft Copy-30 Deg Dev Loading Calculation FINAL
: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001
DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 30.0 0
TOTAL 266
ULT 399 3912
TOTAL 63 10
ULT 94 15 919
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 1299 12739
(Due to Plan/Elevation Deviation)
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 30.0 X ### 0
TOTAL 1012
ULT. 1518 14891
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 X 2 2598 25478
(Due to Plan/Elevation Deviation)
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001
147
12739
14891
1471
25478
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001
DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 433
TOTAL 699
ULT 1048 10282
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 1299 12739
(Due to Plan/Elevation Deviation)
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 X ### 866
TOTAL 1878
ULT. 2818 27631
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 X 2 2598 25478
(Due to Plan/Elevation Deviation)
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001
-7208
12739
27631
-13239
25478
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001
DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 433
TOTAL 699
ULT 769 7540
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 953 9342
(Due to Plan/Elevation Deviation)
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 30.0 X COS 30.0 X ### 1042
TOTAL 2054
ULT. 2260 22162
3. LONGITUDINAL LOAD: 1.0 X 1203 X Cos 30.0 X Cos 0.0 X 2 2293 22484
(Due to Plan/Elevation Deviation)
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001
-5286
9342
22162
-11903
22484
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001
DESIGN DATA NC 30
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 1149 11267
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X ### 1000
TOTAL 2012
ULT. 3018 29601
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001
DESIGN DATA NC 30
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 843 8263
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 30.0 X ### 1203
TOTAL 2216
ULT. 2437 23902
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001
DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 0
TOTAL 266
ULT 399 3912
TOTAL 63 10
ULT 94 15 919 147
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 1500 14710
(Due to Plan/Elevation Deviation)
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 X ### 0
TOTAL 1012
ULT. 1518 14891
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 X 2 3000 29420
(Due to Plan/Elevation Deviation)
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001
DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 0
TOTAL 266
ULT 293 2869
TOTAL 63 10
ULT 69 11 674 108
3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 1100 10787
(Due to Plan/Elevation Deviation)
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 0.0 X COS 0.0 X ### 0
TOTAL 1012
ULT. 1114 10920
3. LONGITUDINAL LOAD: 1.0 X 1203 X Cos 0.0 X Cos 0.0 X 2 2647 25963
(Due to Plan/Elevation Deviation)
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0002
DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( JACK BUS )
WIND SPAN 45 m (0 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 45 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 45 100
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 0
TOTAL 100
ULT 150 1467
TOTAL 26 10
ULT 39 15 379 147
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 45 X 4 651
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X ### 0
TOTAL 795
ULT. 1193 11701
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) SHEET NO: 08 OF 71
MUMBAI 225 kV OHTL DES NO.: G-414/DES-10
DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( 30 Deg Dev Angle of Entry )
WIND SPAN 120 m
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 1149
TOTAL 58 0
ULT 86 0
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON SUSP. INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO DEVIATION 1 X 1000 X SIN 30.0 X 2 1000
TOTAL 2012
ULT. 3018
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
ASSOCIATED TRANSRAIL SHEET NO: 06 OF 30
T.T. "DA"
STRUCTURES LTD, BARODA. DRG NO: AT-92/DES-2
DESIGN DATA
DEVIATION ANGLE 2 deg
WIND SPAN 400 240 m
WEIGHT SPAN ( MAX ) 600 360 m
WEIGHT SPAN ( MIN ) 200 100 m
CASE DESCRIPTION : ANTI-CASCADING CONDITION
A ) GROUND WIRE
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0
b) DUE TO DEVIATION 2 X 2599 X SIN 1.0 91
c) WIND ON TOWER
TOTAL 91
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON PILOT INSULATOR
b) WIND ON INSULATOR 0
c) WIND ON WIRE 0
d) DUE TO DEVIATION 2 X 6303 X SIN 1.0 X 2 440
e) WIND ON TOWER
TOTAL 440
FACTOR OF SAFETY
a) FOR TOWER 1.15
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) SHEET NO: 02 OF 08
MUMBAI #REF! DES NO.: G-414/DES-1
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 0 X 120 0
b) DUE TO DEVIATION 2 X 1810 X SIN 15.0 937
TOTAL 937
TOTAL 58 5
3. LONGITUDINAL LOAD: 0
B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON SUSP. INSULATOR 2.200 X 0.280 X 0.5 X 0 X 2 X 1 0
b) WIND ON WIRE 0.02288 X 0.0 X 120 X 1 0
c) DUE TO DEVIATION 2 X 1280 X SIN 15.0 X 1 663
TOTAL 663
TOTAL 299 75
3. LONGITUDINAL LOAD: 0
FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.02
ALL ABOVE LOADS ARE IN KGS