Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 14

TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.

: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001

DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 30.0 0
TOTAL 266
ULT 399 3912

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN 0 0 0
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 0 0 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 63 10
ULT 94 15 919

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 1299 12739
(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 30.0 X ### 0
TOTAL 1012
ULT. 1518 14891

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1000 X SIN 0 X 2 0 0
d) WIRE ELE.DEVIATION DOWNWARD 1000 X SIN 0 X 2 0 0
TOTAL 349 100
ULT. 524 150 5136

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 X 2 2598 25478
(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001

27⁰C & High Wind - Reliability condition

147

12739

14891

1471

25478
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001

DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 433
TOTAL 699
ULT 1048 10282

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN -30 0 -500
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 30 500 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 563 -490


ULT 844 -735 8274

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 1299 12739
(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 X ### 866
TOTAL 1878
ULT. 2818 27631

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1000 X SIN -30 X 2 0 -1000
d) WIRE ELE.DEVIATION DOWNWARD 1000 X SIN 30 X 2 1000 0
TOTAL 1349 -900
ULT. 2024 -1350 19846

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 X 2 2598 25478
(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001

27⁰C & High Wind - Reliability condition

-7208

12739

27631

-13239

25478
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-
MUMBAI 225 kV OHTL GCC-CHA-TAB-0001

DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X COS 30.0 433
TOTAL 699
ULT 769 7540

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN -30 0 -500
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 30 500 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 563 -490


ULT 619 -539 6068

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X Cos 0.0 953 9342
(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 30.0 X COS 30.0 X ### 1042
TOTAL 2054
ULT. 2260 22162

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1203 X SIN -30 X 2 0 -1203
d) WIRE ELE.DEVIATION DOWNWARD 1203 X SIN 30 X 2 1203 0
TOTAL 1553 -1103
ULT. 1708 -1214 16748

3. LONGITUDINAL LOAD: 1.0 X 1203 X Cos 30.0 X Cos 0.0 X 2 2293 22484
(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
Doc No.: MNT_II-EXE-TLL-EXT-
GCC-CHA-TAB-0001

27⁰C & High Wind - Reliability condition

-5286

9342

22162

-11903

22484
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001

DESIGN DATA NC 30
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 1149 11267

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN -30 0 -500
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 30 500 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 563 -490


ULT 844 -735 8274 -7208

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 1500 14710


(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 X ### 1000
TOTAL 2012
ULT. 3018 29601

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1000 X SIN -30 X 2 0 -1000
d) WIRE ELE.DEVIATION DOWNWARD 1000 X SIN 30 X 2 1000 0
TOTAL 1349 -900
ULT. 2024 -1350 19846 -13239

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X 2 3000 29420


(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001

DESIGN DATA NC 30
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 843 8263

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN -30 0 -500
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 30 500 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 563 -490


ULT 619 -539 6068 -5286

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 1100 10787


(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 30.0 X ### 1203
TOTAL 2216
ULT. 2437 23902

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1203 X SIN -30 X 2 0 -1203
d) WIRE ELE.DEVIATION DOWNWARD 1203 X SIN 30 X 2 1203 0
TOTAL 1553 -1103
ULT. 1708 -1214 16748 -11903

3. LONGITUDINAL LOAD: 1.0 X 1203 X Cos 0.0 X 2 2647 25963


(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001

DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 0
TOTAL 266
ULT 399 3912

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN 0 0 0
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 0 0 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 63 10
ULT 94 15 919 147

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 1500 14710
(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 X ### 0
TOTAL 1012
ULT. 1518 14891

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1000 X SIN 0 X 2 0 0
d) WIRE ELE.DEVIATION DOWNWARD 1000 X SIN 0 X 2 0 0
TOTAL 349 100
ULT. 524 150 5136 1471

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 X 2 3000 29420
(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0001

DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( Dead End/Angle of Entry )
WIND SPAN 120 m (30 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X COS 0.0 0
TOTAL 266
ULT 293 2869

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN 0 0 0
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 0 0 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 63 10
ULT 69 11 674 108

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X Cos 0.0 1100 10787
(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO PLAN DEVIATION 1 X 1203 X SIN 0.0 X COS 0.0 X ### 0
TOTAL 1012
ULT. 1114 10920

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1203 X SIN 0 X 2 0 0
d) WIRE ELE.DEVIATION DOWNWARD 1203 X SIN 0 X 2 0 0
TOTAL 349 100
ULT. 384 110 3766 1079

3. LONGITUDINAL LOAD: 1.0 X 1203 X Cos 0.0 X Cos 0.0 X 2 2647 25963
(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.10
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) Doc No.: MNT_II-EXE-TLL-EXT-GCC-
MUMBAI 225 kV OHTL CHA-TAB-0002

DESIGN DATA NC 0
DEVIATION ANGLE 0 deg ( JACK BUS )
WIND SPAN 45 m (0 Deg in Plan & Elevation)
WEIGHT SPAN ( MAX ) 45 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 45 100
b) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 0
TOTAL 100
ULT 150 1467

2. VERTICAL LOAD : MIN


a) WEIGHT OF WIRE 0.35 X 45 16 0
b) WIRE ELE.DEVIATION UPWARD 1 X 1000 X SIN 0 0 0
c) WIRE ELE.DEVIATION DOWNWARD 1 X 1000 X SIN 0 0 0
d) WEIGHT OF G.W CLAMP 10 10 10

TOTAL 26 10
ULT 39 15 379 147

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 1500 14710


(Due to Plan/Elevation Deviation)

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 45 X 4 651
c) DUE TO PLAN DEVIATION 1 X 1000 X SIN 0.0 X ### 0
TOTAL 795
ULT. 1193 11701

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 45 X 4 179 0
b) WEIGHT OF INSULATOR & HARDWARE 2 X 100 200 100
c) WIRE ELE.DEVIATION UPWARD 1000 X SIN 0 X 4 0 0
d) WIRE ELE.DEVIATION DOWNWARD 1000 X SIN 0 X 4 0 0
TOTAL 379 100
ULT. 568 150 5574 1471

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 0.0 X 4 6000 58840


(Due to Plan/Elevation Deviation)

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) SHEET NO: 08 OF 71
MUMBAI 225 kV OHTL DES NO.: G-414/DES-10

DESIGN DATA NC 30
DEVIATION ANGLE 30 deg ( 30 Deg Dev Angle of Entry )
WIND SPAN 120 m
WEIGHT SPAN ( MAX ) 150 m
WEIGHT SPAN ( MIN ) 0 m
CASE DESCRIPTION : 27⁰C & High Wind - Reliability condition

A ) GROUND WIRE (AACSR) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 197 X 120 266
b) DUE TO DEVIATION 1 X 1000 X SIN 30.0 500
TOTAL 766
ULT 1149

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WEIGHT OF G.W CLAMP 5 5 0

TOTAL 58 0
ULT 86 0

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 1299

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON SUSP. INSULATOR 2.706 X 0.280 X 0.5 X 191.0 X 2 X 1 145
b) WIND ON WIRE 0.02288 X 158 X 120 X 2 868
c) DUE TO DEVIATION 1 X 1000 X SIN 30.0 X 2 1000
TOTAL 2012
ULT. 3018

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDW 2 X 100 200 100

TOTAL 349 100


ULT. 524 150

3. LONGITUDINAL LOAD: 1.0 X 1000 X Cos 30.0 X 2 2598

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.50
ALL ABOVE LOADS ARE IN KGS
ASSOCIATED TRANSRAIL SHEET NO: 06 OF 30
T.T. "DA"
STRUCTURES LTD, BARODA. DRG NO: AT-92/DES-2

DESIGN DATA
DEVIATION ANGLE 2 deg
WIND SPAN 400 240 m
WEIGHT SPAN ( MAX ) 600 360 m
WEIGHT SPAN ( MIN ) 200 100 m
CASE DESCRIPTION : ANTI-CASCADING CONDITION

A ) GROUND WIRE
1. TRANSVERSE LOAD :
a) WIND ON WIRE 0
b) DUE TO DEVIATION 2 X 2599 X SIN 1.0 91
c) WIND ON TOWER
TOTAL 91

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.583 X 600 350 117
b) WEIGHT OF G.W CLAMP 5 5 5
c) WEIGHT OF MAN WITH TOOLS
TOTAL 355 122

3. LONGITUDINAL LOAD: 2599 X COS 0.0 2599

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON PILOT INSULATOR
b) WIND ON INSULATOR 0
c) WIND ON WIRE 0
d) DUE TO DEVIATION 2 X 6303 X SIN 1.0 X 2 440
e) WIND ON TOWER
TOTAL 440

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 2.004 X 600 X 2 2405 802
b) WEIGHT OF INSULATOR 1 X 161 161 161
c) WEIGHT OF MAN WITH TOOLS
d) WEIGHT OF PILOT INSULATOR
e) ERECTION LOADS
TOTAL 2566 963

3. LONGITUDINAL LOAD: 6303 X COS 0.0 X 1 X 2 6303

FACTOR OF SAFETY
a) FOR TOWER 1.15
ALL ABOVE LOADS ARE IN KGS
TRANSRAIL LIGHTING LTD Loading Calculation for Gantry (0-20 deg.) SHEET NO: 02 OF 08
MUMBAI #REF! DES NO.: G-414/DES-1

DESIGN DATA NC 30 BWC


DEVIATION ANGLE 30 deg
WIND SPAN 120 0 m
WEIGHT SPAN ( MAX ) 150 0 m
WEIGHT SPAN ( MIN ) 0 0 m
CASE DESCRIPTION : 12⁰C (Minimum Temperature) & Wind - Reliability condition

A ) GROUND WIRE (OPGW) NC

1. TRANSVERSE LOAD :
a) WIND ON WIRE 0.01125 X 0 X 120 0
b) DUE TO DEVIATION 2 X 1810 X SIN 15.0 937
TOTAL 937

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.35 X 150 53 0
b) WEIGHT OF G.W CLAMP 5 5 5

TOTAL 58 5

3. LONGITUDINAL LOAD: 0

B ) CONDUCTOR
1. TRANSVERSE LOAD :
a) WIND ON SUSP. INSULATOR 2.200 X 0.280 X 0.5 X 0 X 2 X 1 0
b) WIND ON WIRE 0.02288 X 0.0 X 120 X 1 0
c) DUE TO DEVIATION 2 X 1280 X SIN 15.0 X 1 663
TOTAL 663

2. VERTICAL LOAD : MAX MIN


a) WEIGHT OF WIRE 0.9942 X 150 X 1 149 0
b) WEIGHT OF INSULATOR & HARDW 2 X 75 150 75

TOTAL 299 75

3. LONGITUDINAL LOAD: 0

FACTOR OF SAFETY
a) FOR TOWER (Quality) 1.02
ALL ABOVE LOADS ARE IN KGS

You might also like