Professional Documents
Culture Documents
Ansiariashraeiso13256 2 1998
Ansiariashraeiso13256 2 1998
ASHRAE STANDARD
Approved by ARI on August 10, 2001; by the ASHRAE Standards Committee on March 20, 2002; by the ASHRAE
Board of Directors on July 3, 2003; and by the American National Standards Institute on August 15, 2003.
ASHRAE Standards are scheduled to be updated on a five-year cycle; the date following the standard number is
the year of ASHRAE Board of Directors approval. The latest copies may be purchased from ASHRAE Customer
Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: orders@ashrae.org. Fax: 404-321-5478. Tele-
phone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in U.S. and Canada).
When addenda or interpretations to this standard have been approved, they can be downloaded free of charge
from the ASHRAE Web site at http://www.ashrae.org/template/TechnologyLinkLanding/category/1631 or
http://www.ashrae.org/template/TechnologyLinkLanding/category/1686.
ARI uses its best efforsts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not
certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk.
ASHRAE DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information
and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any
products, components, or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any
tests conducted under its Standards or Guidelines will be nonhazardous or free from risk.
1.3 This part of ISO 13256 does not apply to the testing and 1. The heat exchange loop may be placed in horizontal
rating of individual assemblies for separate use or to units trenches or vertical bores, or be submerged in a body of
having two or more indoor sections connected to a single out- surface water.
door section. It does not apply to heat pumps covered in ISO 2. The temperature of the brine is related to the climatic condi-
5151, ISO 13253, or ISO 13256-1. tions and may vary from –5°C to 40°C.
5. Performance requirements 5.2.2.2 The 110 % voltage test shall be conducted prior
to the 90 % voltage test.
5.1 General
5.2.2.3 All power to the equipment shall be cut off for 3
5.1.1 To comply with this part of ISO 13256, water-to-
min at the conclusion of the one hour test at 90 % voltage level
water and brine-to-water heat pumps shall be designed and
and then restored for one hour.
produced such that any production unit will meet the applica-
ble requirements of this part of ISO 13256. 5.2.3 Test requirements
5.1.2 For heat pumps with capacity control, the perfor- Heat pumps shall meet the following requirements when
mance requirement tests shall be conducted at maximum operating at the conditions specified in Tables 3 and 4.
capacity. (a) During the entire test, the equipment shall operate with-
out any indication of damage.
5.2 Maximum operating conditions test
(b) During the test period specified in 5.2.2.1, the equipment
5.2.1 Test conditions shall operate continuously without tripping any motor
The maximum operating conditions test shall be overload or other protective devices.
conducted for cooling and heating at the test conditions estab- (c) During the test period specified in 5.2.2.3, the motor over-
lished for the specific applications (see 4.2.3) specified in load protective device may trip only during the first 5 min
Tables 3 and 4. Heat pumps intended for use in two or more of operation after the shutdown period of 3 min. During
applications shall be tested at the most stringent set of condi- the remainder of the test period, no motor overload pro-
tions specified in Tables 3 and 4. tective device shall trip. For those models so designed
5.2.2 Test procedures that resumption of operation does not occur within the
5.2.2.1 The equipment shall be operated continuously first 5 min after initial trip, the equipment may remain out
for one hour after the specified temperatures have been estab- of operation for not longer than 30 min. It shall then
lished at each specified voltage level. operate continuously for the remainder of the test period.
5.3 Minimum operating conditions test more applications shall be tested at the most stringent set of
5.3.1 Test conditions conditions.
Heat pumps shall be tested at the minimum operating test 5.4.2 Test procedures
conditions for cooling and heating at the test conditions estab- After establishment of the specified temperature condi-
lished for the specific application (see 4.2.3) specified in tions, the heat pump shall be operated continuously for a
Tables 5 and 6. Heat pumps intended for use in two or more period of four hours.
applications shall be tested at the most stringent set of condi-
5.4.3 Test requirements
tions specified in Tables 5 and 6.
No condensed water shall drip or run off the equipment’s
5.3.2 Test procedures casing during the test.
For the minimum operating cooling test, the heat pump
shall be operated continuously for a period of not less than 30
6. Test methods
min after the specified temperature conditions have been
established. For the minimum operation heating test, the heat 6.1 General
pump shall soak for 10 min with liquid at the specified temper- The standard capacity ratings shall be determined by the
ature circulating through the coil. The equipment shall then be test methods and procedures established in this clause and
started and operated continuously for 30 min. Annex A. The total cooling and heating capacities shall be the
5.3.3 Test requirements average of the results obtained for the indoor and outdoor sides
No protective device shall trip during these tests and no using the liquid enthalpy test method in Annex B. The results
damage shall occur to the equipment. obtained by these two methods must agree within 5 % in order
for a particular test to be valid. Measurements should be made
5.4 Enclosure sweat test
in accordance with the provisions of Annex C.
5.4.1 Test conditions
The enclosure sweat test shall be conducted in the cooling 6.2 Uncertainties of measurement
mode at the test conditions established for the specific appli- The uncertainties of measurement shall not exceed the
cations specified in Table 7. Heat pumps intended for two or values specified in Table 8.
Uncertainty of measurementa
Measured quantity Unit of indicated values
Water
- temperature °C ±0.1°C
- temperature difference °C ±0.1°C
- volume flow l/s ±1%
- static pressure difference Pa ±5 Pa (p ≤ 100 Pa)
±5 % (p >100 Pa)
Electrical inputs ±0.5%
Time ±0.2%
Mass ±1.0%
aUncertainty of measurement: an estimate characterizing the range of values within which the true value of a measurand lies (measurand: a quantity subject to measurement).
NOTE: Uncertainty of measurement comprises, in general, many components. Some of these components may be estimated on the basis of the statistical distribution of the results
of series of measurements and can be characterized by experimental standard deviations. Estimates of other components can be based on experience or other information.
Liquid temperature
- inlet ±0.5°C ±0.2°C
Temperature of liquid entering indoor-side, in degrees (g) net cooling capacity (see 3.3), in watts
Celsius (h) net heating capacity (see 3.5), in watts
Temperature of liquid entering outdoor-side, in degrees (i) energy efficiency ratio (see 3.8), in watts per watt
Celsius (j) coefficient of performance (see 3.9), in watts per watt
Temperature of liquid leaving indoor-side, in degrees
Celsius 7. Marking provisions
Temperature of liquid leaving outdoor-side, in degrees 7.1 Nameplate requirement
Celsius Each water-to-water and brine-to-water heat pump,
Liquid flow rate, indoor-side, in litres per second whether composed of a single package or separate assemblies,
Liquid flow rate, outdoor-side, in litres per second shall have a durable nameplate, firmly attached to each sepa-
rate assembly in a location accessible for reading.
6.4 Test tolerances
7.2 Nameplate information
6.4.1 The maximum permissible variation of any observa-
The nameplate shall provide the following minimum
tion during the capacity test is listed in the first column of
information in addition to the information required in interna-
Table 9. The maximum permissible variation of any observa-
tional safety standards.
tion during the performance tests is listed in Table 10.
6.4.2 The maximum permissible variations of the average (a) Manufacturer’s name or trademark1.
of the test observations from the standard or desired test con- (b) Distinctive type or model designation and serial number.
ditions are shown in Table 9, second column. (c) Full-load capacity rating (see 7.3). Equipment rated for
more than one application shall state capacity ratings for
6.5 Test results
both heating and cooling, as appropriate for each applica-
The results of a capacity test shall express quantitatively
tion.
the effects produced upon the indoor-side liquid by the equip-
(d) Rated voltage(s).
ment tested. For given test conditions, the capacity test results
(e) Rated frequency(ies).
shall include such of the following quantities as are applicable:
(f) Refrigerant designation and refrigerant mass charge.
(a) cooling capacity (see 6.1), in watts The information required in 7.2 a, b, d, e and the refrig-
erant designation shall be placed on each element (matched
(b) heating capacity (see 6.1), in watts
assembly) of the system.
(c) measured power input to equipment, in watts
(d) liquid pump power adjustment, indoor-side (see 4.1.2), in 7.3 Designation of capacity ratings
watts The designation of capacity rating shall be established in
(e) liquid pump power adjustment, outdoor-side (see 4.1.3), such a way that the heat transfer media are indicated (IW =
in watts
(f) effective power input to equipment or power inputs to all 1
The manufacturer is considered to be the firm identified on the
equipment components (see 3.10), in watts nameplate.
B3.3 Line loss corrections C2.3 In no case should the smallest scale division of the
If line loss corrections are to be made, they shall be pressure measuring instrument exceed 2.5 times the specified
included in the capacity calculations. accuracy.
C3 Electrical measurements
Annex C (informative)
Instrumentation and measurements C3.1 Electrical measurements should be made with either
indicating or integrating instruments.
C1 Temperature
C3.2 Instruments used for measuring the electrical input to
C1.1 Temperatures should be measured using liquid-in- heaters or other apparatus furnishing heat loads should be
glass thermometers, thermocouples, or electric resistance accurate to ±1.0% of the quantity measured. Instruments used
thermometers, including thermistors. The instrument charac- for measuring electrical input to fan motors, compressor
teristics of Table C-1 should be met. motors, or other electrical accessories should be accurate to
±1.0% of the indicated value.
C1.2 Air velocities over the wet-bulb temperature measur-
ing instruments should be approximately 5 m/s. C3.3 Voltages should be measured at the equipment termi-
nals.
C1.3 In no case should the smallest scale division of the
temperature measuring instrument exceed twice the specified C4 Liquid flow measurement
accuracy. For example, for the specified accuracy of ±0.05°C, C4.1 Water and brine flow rates should be measured with a
the smallest scale division should not exceed 0.1°C. liquid flow meter or quantity meter having an accuracy of
C1.4 Where an instrument accuracy of ±0.05°C is speci- ±1.0% of the indicated value.
fied, the instrument should be calibrated by comparison with C4.2 Condensate collection rates should be measured with
a thermometer certified by a recognized authority, such as a a liquid quantity meter measuring either mass or volume and
national standards laboratory. having an accuracy of ±1.0% of the indicated value.
C1.5 Temperature measuring instruments used to measure C5 Time, mass and speed measurements
the change in temperature should be arranged so that they can
be readily interchanged between inlet and outlet positions to C5.1 Time measurements should be made with instruments
improve accuracy. having an accuracy of ±0.20%.
C5.2 Mass measurements should be made with apparatus
C1.6 Temperature of liquids within conduits should be
having an accuracy of ±0.2%.
measured by inserting the temperature measuring instrument
directly within the liquid, or within a well inserted into the liq- C5.3 Speed measurements should be made with a revolu-
uid. If a glass thermometer is to be inserted directly into the tion counter, tachometer, stroboscope or oscilloscope having
liquid, it should be calibrated for the effect of pressure. an accuracy of ±1.0 %.
ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment. ASHRAE’s
members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and
components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted
standards and the practical state of the art.
ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the indoor and
outdoor environment to a greater extent than specified by the standards and guidelines as established by itself and other
responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive technical committee structure,
continue to generate up-to-date standards and guidelines where appropriate and adopt, recommend, and promote those new
and revised standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date standards and design considerations as the material is
systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek
out and disseminate information from other responsible organizations that is pertinent, as guides to updating standards and
guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the system’s
intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope
operates. However, energy source selection and the possible environmental impact due to the energy source and energy
transportation will be considered where possible. Recommendations concerning energy source selection should be made by
its members.
86703
PC 2/05