Engineering Report Structural

PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Beam Design
Beam Mark Label B -1

Design Parameters
F'c = 21 MPa
Fy = 235 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3

Beam Width = 0.25 m


Beam Depth = 0.4 m
Tributary Width = 1 m
Thickness of Slab = 0.1 m
Clear Span Length = 5.75 m

Service Dead Load = 6.728 kPa x 1m =


CHB/Wall Load = 8.94 kN/m

Service Live Load = 1.9 1.9kPa x 1m =

Wu 24.9752 kN/m
Max. Moment 103.218 kN-m

Effective Width of Slab for T Beams


A. 16tf +bw 1.850 m
B. Center to Center Space of Beam 1.000 m
C. L/4 + bw 1.688 m
Effective Width for L Beams
A. 6tf +bw 0.850 m
B. Center to Center Space of Beam/2 1.000 m
C. L/12 + bw 0.729 m
Governing Effective Width 0.729 m

Assuming a < thickness of Slab


a= 100 mm
Solving Area of Steel =
Assume # of Layers = 2 layer of rebars
d = 321.5 mm
As = 1797.52 mm2
Number of Bars = 9.000 pcs 16 mm rebar
Actual As = 1809.56

Solving for Actual a = 32.672 < 100 - - - - - - - assumption is correct


Solving for Actual Mu = 116.793 kN-m
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Checking For Shear Capacity


Actual Ultimate Shear Vu = 71.8037 kN
Vud (Shear @ dist. d) = 71.8037 kN

If Vud > ØVc/2, stirrups is needed


ØVc = 1/6*(f'c)^0.5*b*d = 46.0406 kN
ØVc/2 = 23.0203 kN < 71.8037 kN - - - - - Stirrups is Needed

Vud < Ø(Vc + Vs)


S = Avfyd/Vs = 333.73 mm

Check Limitations for Vs, it must be less than Ø(2/3) (f'c^0.5)bd


Ø(2/3) (f'c^0.5)bd = 184.162 kN
Vs = (Vud - ØVc)/Ø = 34.3508 kN < 184.162 kN - - - - - Vs Limits is Okay

Max Spacing of Shear Reinforcement


if Vs < 0.33(f'c)bd max spacing is 160.75 mm or 600mm =
if Vs > 0.33(f'c)bd max spacing is 80.375 mm or 300mm

0.33 (f'c)^0.5bd = 122.775 kN


Vs = (Vud - ØVc)/Ø = 34.3508 kN < 122.775 kN 160.8

There fore, use 2 legs of 10 mm rebar @ 160.75 mm O.C.

Checking For Ductility


Cb = 231.018 mm
ab = 196.365 mm
Acb = 97008 mm2
Ccb (Capacity of Conc.)= 1298.69 kN (Capacity of Concrete at Balance Condition)
Actual Tension Force (Tf) = 425.246 kN
If Tf < Ccb , Pass Ductility 425.246 kN < 974.021 kN Beam Pass For Ductillity Requirem
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Beam Type

T-Beams
L-Beams

6.728 kN/m

1.9 kN/m

2 layers brad

1 layer' 0.058
2 layer d' 0.0785

umption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

- Stirrups is Needed

- Vs Limits is Okay

160.75
80.375

mm spacig O.C. 0.333333333333333 201.0619


4.47213595499958 fc'^0.5
200 b
326 d
97194.4214219909

157.07963267949 Av
227 fy
ance Condition) 321.5 d
34.3508464196541 Vs
ass For Ductillity Requirement 333.725404978855 spacing
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Beam Design
Beam Mark Label B -2

Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3

Beam Width = 0.225 m


Beam Depth = 0.35 m
Tributary Width = 2.5 m
Thickness of Slab = 0.1 m
Clear Span Length = 4.05 m

Service Dead Load = 4.57 kPa x 2.5 m =


CHB/Wall Load = 8.96 kN/m

Service Live Load = 1.9 1.9kPa x 2.5 m =

Wu 31.579 kN/m
Max. Moment 64.7468 kN-m

Effective Width of Slab for T Beams


A. 16tf +bw 1.825 m
B. Center to Center Space of Beam 2.500 m
C. L/4 + bw 1.238 m
Effective Width for L Beams
A. 6tf +bw 0.825 m
B. Center to Center Space of Beam/2 2.500 m
C. L/12 + bw 0.563 m
Governing Effective Width 0.563 m

Assuming a < thickness of Slab


a= 100 mm
Solving Area of Steel =
Assume # of Layers = 2 layer of rebars
d = 271.5 mm
As = 784.516 mm2
Number of Bars = 4.000 pcs 16 mm rebar
Actual As = 804.248

Solving for Actual a = 34.8192 < 100 - - - - - - - assumption is correct


Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Solving for Actual Mu = 76.1414 kN-m


Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Checking For Shear Capacity


Actual Ultimate Shear Vu = 63.9475 kN
Vud (Shear @ dist. d) = 63.9475 kN

If Vud > ØVc/2, stirrups is needed


ØVc = 1/6*(f'c)^0.5*b*d = 34.149 kN
ØVc/2 = 17.0745 kN < 63.9475 kN - - - - - Stirrups is Needed

Vud < Ø(Vc + Vs)


S = Avfyd/Vs = 243.66 mm

Check Limitations for Vs, it must be less than Ø(2/3) (f'c^0.5)bd


Ø(2/3) (f'c^0.5)bd = 136.596 kN
Vs = (Vud - ØVc)/Ø = 39.7314 kN < 136.596 kN - - - - - Vs Limits is Okay

Max Spacing of Shear Reinforcement


if Vs < 0.33(f'c)bd max spacing is 135.75 mm or 600mm =
if Vs > 0.33(f'c)bd max spacing is 67.875 mm or 300mm

0.33 (f'c)^0.5bd = 91.0639 kN


Vs = (Vud - ØVc)/Ø = 39.7314 kN < 91.0639 kN 135.8

There fore, use 2 legs of 10 mm rebar @ 135.75 mm O.C.

Checking For Ductility


Cb = 160.651 mm
ab = 136.553 mm
Acb = 64474 mm2
Ccb (Capacity of Conc.)= 822.05 kN (Capacity of Concrete at Balance Condition)
Actual Tension Force (Tf) = 332.959 kN
If Tf < Ccb , Pass Ductility 332.959 kN < 616.537 kN Beam Pass For Ductillity Requirem
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

Beam Type

T-Beams
L-Beams

11.425 kN/m

4.75 kN/m

2 layers brad

1 layer' 0.058
2 layer d' 0.0785

1.41860465116279
umption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING

- Stirrups is Needed

- Vs Limits is Okay

135.75
67.875

mm spacig O.C. 0.333333333333333 201.0619


4.47213595499958 fc'^0.5
200 b
326 d
97194.4214219909

157.07963267949 Av
227 fy
ance Condition) 271.5 d
39.7313658081605 Vs
ass For Ductillity Requirement 243.658784563225 spacing