4.beam Design Singly and Doubly
4.beam Design Singly and Doubly
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
Beam Design
Beam Mark Label B -1
Design Parameters
F'c = 21 MPa
Fy = 235 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 24.9752 kN/m
Max. Moment 103.218 kN-m
Beam Type
T-Beams
L-Beams
6.728 kN/m
1.9 kN/m
2 layers brad
1 layer' 0.058
2 layer d' 0.0785
umption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
- Stirrups is Needed
- Vs Limits is Okay
160.75
80.375
157.07963267949 Av
227 fy
ance Condition) 321.5 d
34.3508464196541 Vs
ass For Ductillity Requirement 333.725404978855 spacing
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
Beam Design
Beam Mark Label B -2
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 31.579 kN/m
Max. Moment 64.7468 kN-m
Beam Type
T-Beams
L-Beams
11.425 kN/m
4.75 kN/m
2 layers brad
1 layer' 0.058
2 layer d' 0.0785
1.41860465116279
umption is correct
Engineering Report Structural
PROPOSED
Calculation
FOUR STOREY W/ ROOFDECK RESIDENTIAL BUILDING
- Stirrups is Needed
- Vs Limits is Okay
135.75
67.875
157.07963267949 Av
227 fy
ance Condition) 271.5 d
39.7313658081605 Vs
ass For Ductillity Requirement 243.658784563225 spacing