Laporan Instalasi Enggri Vristanto 181202019151424
Laporan Instalasi Enggri Vristanto 181202019151424
6 62 5 6 2 120 5
Stitik Pf Sdaya
(VA)
3 1 1025
1 1 25
1 1 25
1 0.8 50
2 0.8 550
3 1 1025 1025
1 1 25 1
1 1 25 1
1 1 40 0
2 1 80 0
2 0.8 250 0
5 1 2040 8
3 1 1040 0
4 1 1540 0
8 1 3080 3080
3 1 1040 0
4 1 1540
8 1 3080
6 1 2080
1 0.8 50
3 1 1040
7 1 3040
3 1 1040
4 1 1540
2 1 540
7 1 3040
1 0.8 50
5 1 1580
5 1 1580
7 1 3040
7 1 2120
2 1 540
6 1 2080
6 1 2080
2 1 540
2 1 540
4 1 1080
8 1 3120
9 1 3160
8 1 3120
8 1 3080
8 1 1700
2 1 540
3 1 120
3 1 1040
6 1 3080
1 0.8 50
7 1 3040
4 0.8 1150
4 0.8 1150
1 0.8 75
1 0.8 75
0
0
0
206 68580
Tabel 3.2. Pembagian Grup Beban
Lampu TL (W) Lampu Pijar (W) S.Kontak (VA)
Grup No. Nama Ruang Stitik
25 40 40 60 100 500 1000
Grup 1 1 Pos 1 Security 1 2 3
2 ruang tunggu 1 1
3 smoking area 1 1 1
4 wc 1 1 1
5 musholla 1 1 2
6 pos 2 security 1 2 3
7 smoking area 2 1 1
8 wc 2 1 1
9 parkir tamu 1 1
10 parkir staff 2 2
Grup 2 11 taman 2 2
12 lobby 1 4 5
Grup 3 13 ruang direktur 1 2 3
14 ruang meeting 1 1 3 4
Grup 4 15 kantor direksi 2 6 8
Grup 5 16 manager administrasi 1 2 3
17 ruang meeting 2 1 3 4
Grup 6 18 staff administrasi 2 6 8
Grup 7 19 kantin 2 4 6
20 wc 3 1 1
21 klinik 1 2 3
Grup 8 22 staff keuangan 1 6 7
Grup 9 23 manager keuangan 1 2 3
24 ruang meeting 3 1 3 4
25 manager teknik 1 1 2
Grup 10 26 staff teknik 1 6 7
27 wc 4 1 1
Grup 11 28 gudang spare part 1 2 3 5
29 gudang spare part 2 2 3 5
Grup 12 30 staff gudang 1 6 7
Grup 13 31 gudang barang mentah/baku 3 4 7
32 loading truk 1 1 1 2
Grup 14 33 ruang higenis barang baku 2 4 6
34 lorong 1 1 2
Grup 15 35 ruang bumbu 2 4 6
36 ruang sanitasi 1 1 2
Grup 16 37 ruang pembersihan 2 2 4
Grup 17 38 ruang pengolahan bahan baku 3 4 1 8
Grup 18 39 ruang proses bahan jadi 4 4 1 9
Grup 19 40 ruang pengemasan 3 4 1 8
Grup 20 41 quality control 2 6 8
Grup 21 42 gudang barang jadi 5 3 8
43 loading truk 2 1 1 2
44 parkir truk 2 3 3
45 genset 1 2 3
Grup 22 46 workshop teknik 2 2 2 6
Grup 23 47 wc 5 1 1
48 staff produksi 1 6 7
Grup 24 49 pengolahan air 2 2 4
50 pengolahan limbah 2 2
51 pengolahan sampah 1 2 3
52 pengolahan sampah/limbah b3 1 1
6 62 5 6 2 120 206
ban
Sdaya Stitik Sdaya (VA) R S T
(VA) Grup Grup (VA) (VA) (VA)
1025 16 2870 2870
25
25
50
550
1025
25
25
40
80
250 7 2290 2290
2040
1040 7 2580 2580
1540
3080 8 3080 3080
1040 7 2580 2580
1540
3080 8 3080 3080
2080 10 3170 3170
50
1040
3040 7 3040 3040
1040 9 3120 3120
1540
540
3040 8 3090 3090
50
1580 10 3160 3160
1580
3040 7 3040 3040
2120 9 2660 2660
540
2080 8 2620 2620
540
2080 8 2620 2620
540
1080 4 1080 1080
3120 6 3120 3120
3160 9 3160 3160
3120 10 3120 3120
3080 8 3080 3080
1700 16 3400 3400
540
120
1040
3080 6 3080 3080
50 8 3090 3090
3040 5540 1846.667
1150 10 2450 2450
1150 3
75
75
68580 68580 22150 22980 23450
19.4829545
0
Tabel 3.3. Perhitungan Penampang kawat dan Drop Tegangan
Daya E I r L1
Grup Jenis Kabel Vd max
(VA) (Volt) (A) (Ω/km) (m)
1 NYA 2X2 2870 220 13.045454545455 0.0000172 60 4.4
2 NYA 2X2 2290 220 10.409090909091 0.0000172 40 4.4
3 NYA 2X2 2580 220 11.727272727273 0.0000172 27 4.4
4 NYA 2X2 3080 220 14 0.0000172 20 4.4
5 NYA 2X2 2580 220 11.727272727273 0.0000172 18 4.4
6 NYA 2X2 3080 220 14 0.0000172 15 4.4
7 NYA 2X2 3170 220 14.409090909091 0.0000172 26 4.4
8 NYA 2X2 3040 220 13.818181818182 0.0000172 34 4.4
9 NYA 2X2 3120 220 14.181818181818 0.0000172 40 4.4
10 NYA 2X2 3090 220 14.045454545455 0.0000172 41 4.4
11 NYA 2X2 3160 220 14.363636363636 0.0000172 45 4.4
12 NYA 2X2 3040 220 13.818181818182 0.0000172 33 4.4
13 NYA 2X2 2660 220 12.090909090909 0.0000172 36 4.4
14 NYA 2X2 2620 220 11.909090909091 0.0000172 28 4.4
15 NYA 2X2 2620 220 11.909090909091 0.0000172 20 4.4
16 NYA 2X2 1080 220 4.9090909090909 0.0000172 26 4.4
17 NYA 2X2 3120 220 14.181818181818 0.0000172 10 4.4
18 NYA 2X2 3160 220 14.363636363636 0.0000172 15 4.4
19 NYA 2X2 3120 220 14.181818181818 0.0000172 22 4.4
20 NYA 2X2 3080 220 14 0.0000172 15 4.4
21 NYA 2X2 3400 220 15.454545454546 0.0000172 46 4.4
22 NYA 2X2 3080 220 14 0.0000172 44 4.4
23 NYA 2X2 3090 220 14.045454545455 0.0000172 40 4.4
24 NYA 2X2 2450 220 11.136363636364 0.0000172 55 4.4
756
v
220
Jumlah rms
L1 = Jarak PHB ke beban terjauh dalam 1 grup
rop Tegangan
R kabel
A (mm²) R (Ω) E% (Ω/km)
Vd E% R50° Vd50°
A1 A2 R1 R2 50°C
6.1195 4 0.33728 0.2682 3.4988 1.59036 0.300384 3.91864582 1.781203 4.47
3.25521 2.5 0.42271 0.2856 2.9728 1.351289 0.319872 3.32957673 1.513444 7.14
2.47552 2.5 0.37519 0.19278 2.2608 1.027629 0.215914 2.53207767 1.150944 7.14
2.18909 2.5 0.31429 0.1428 1.9992 0.908727 0.159936 2.239104 1.017775 7.14
1.65035 2.5 0.37519 0.12852 1.5072 0.685086 0.143942 1.68805178 0.767296 7.14
1.64182 2.5 0.31429 0.1071 1.4994 0.681545 0.119952 1.679328 0.763331 7.14
2.92898 2.5 0.30536 0.18564 2.6749 1.215865 0.207917 2.99589207 1.361769 7.14
3.67312 2.5 0.31842 0.24276 3.3545 1.524774 0.271891 3.75704204 1.707746 7.14
4.43504 4 0.31026 0.1788 2.5357 1.152595 0.200256 2.83999418 1.290906 4.47
4.50221 4 0.31327 0.18327 2.5741 1.17005 0.205262 2.88300371 1.310456 4.47
5.05339 4 0.30633 0.20115 2.8892 1.313293 0.225288 3.23595491 1.470889 4.47
3.56509 2.5 0.31842 0.23562 3.2558 1.479927 0.263894 3.6465408 1.657519 7.14
3.40304 2.5 0.36391 0.25704 3.1078 1.412658 0.287885 3.48078895 1.582177 7.14
2.60701 2.5 0.36947 0.19992 2.3809 1.082212 0.22391 2.66656931 1.212077 7.14
1.86215 2.5 0.36947 0.1428 1.7006 0.773008 0.159936 1.90469236 0.865769 7.14
0.99788 2.5 0.8963 0.18564 0.9113 0.414238 0.207917 1.02068247 0.463947 7.14
1.10876 2.5 0.31026 0.0714 1.0126 0.460264 0.079968 1.13409164 0.515496 7.14
1.68446 2.5 0.30633 0.1071 1.5383 0.699248 0.119952 1.72294691 0.783158 7.14
2.43927 2.5 0.31026 0.15708 2.2277 1.012582 0.17593 2.4950016 1.134092 7.14
1.64182 2.5 0.31429 0.1071 1.4994 0.681545 0.119952 1.679328 0.763331 7.14
5.55802 4 0.28471 0.20562 3.1778 1.444438 0.230294 3.55909527 1.617771 4.47
4.816 4 0.31429 0.19668 2.7535 1.2516 0.220282 3.0839424 1.401792 4.47
4.3924 4 0.31327 0.1788 2.5113 1.141512 0.200256 2.81268655 1.278494 4.47
4.78864 4 0.3951 0.24585 2.7379 1.244489 0.275352 3.06642 1.393827 4.47
Tabel 3.4. Perhitungan Arus Nominal dan Arus Asut
V motor Frek N
No Jenis Beban Kegunaan h
(Volt) (Hz) (rpm)
1 motor AC 1ɸ pompa air 220 50 0.8 1200
2 motor AC 3ɸ penggiling bumbu 220/380 50 0.75 1700
3 motor AC 3ɸ penggiling bahan baku 1 220/381 50 0.75 1700
4 motor AC 3ɸ penggiling bahan baku 2 220/382 50 0.75 1700
5 motor AC 3ɸ penggiling adonan 1 220/383 50 0.75 1700
6 motor AC 3ɸ penggiling adonan 2 220/384 50 0.75 1700
7 motor AC 1ɸ vacum kemasan 220 50 0.8 1300
8 pemanas mesin press kemasan 220 50
9 freezer 1 pendingin produk 220 50
10 freezer 2 pendingin produk 220 50
11 Air Conditioning lobby 220 50
12 Air Conditioning musholla 220 50
13 Air Conditioning ruang direktur 220 50
14 Air Conditioning ruang meeting 1 220 50
15 Air Conditioning kantor direksi 220 50
16 Air Conditioning manager administrasi 220 50
17 Air Conditioning klinik 220 50
18 Air Conditioning staff keuangan 220 50
19 Air Conditioning manager keuangan 220 50
20 Air Conditioning ruang meeting 3 220 50
21 Air Conditioning manager teknik 220 50
22 Air Conditioning staff teknik 220 50
23 Air Conditioning staff gudang 220 50
24 Air Conditioning ruang higenis barang baku 220 50
25 Air Conditioning ruang bumbu 220 50
26 Air Conditioning ruang sanitasi 220 50
27 Air Conditioning ruang pembersihan 220 50
28 Air Conditioning ruang pengolahan bahan baku 220 50
29 Air Conditioning ruang proses bahan jadi 220 50
30 Air Conditioning ruang pengemasan 220 50
31 Air Conditioning quality control 220 50
32 Air Conditioning staff produksi 220 50
Jumlah
ominal dan Arus Asut
Ia Pout In (A)
pf Pin (kVA) Asut
(A) (kW) Y Δ
0.75 6.6430034 1.5 3.69055742179299 1.40625 Langsung
0.65 24.56435 6 7.900814 13.64686122 5.2 Δ-Y
0.65 24.56435 6 7.900814 13.64686122 5.2 Δ-Y
0.65 24.56435 6 7.900814 13.64686122 5.2 Δ-Y
0.65 24.56435 6 7.900814 13.64686122 5.2 Δ-Y
0.65 24.56435 6 7.900814 13.64686122 5.2 Δ-Y
0.7 2.3930351 1 1.329464 2.29634684 0.875 Δ-Y
0.75 6.5454545 1 3.63636363636364 0.8 Langsung
0.7 7.3636364 2 4.09090909090909 0.9 Langsung
0.7 7.3636364 2 4.09090909090909 0.9 Langsung
0.75 4.6636364 0.6 2.59090909090909 0.57 Langsung
0.75 4.6636364 0.6 2.59090909090909 0.57 Langsung
0.75 4.6636364 0.84 2.59090909090909 0.57 Langsung
0.75 4.6636364 0.84 2.59090909090909 0.57 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 9.8181818 0.84 5.45454545454545 1.2 Langsung
0.75 9.8181818 0.84 5.45454545454545 1.2 Langsung
0.75 9.8181818 0.84 5.45454545454545 1.2 Langsung
0.75 7.0363636 0.84 3.90909090909091 0.86 Langsung
0.75 4.6636364 0.84 2.59090909090909 0.57 Langsung
304.41233 55.5 140.3877 70.53065295
Tabel 3.5. Perhitungan Penampang kawat dan Drop Tegangan Instalasi Day
P (Daya)
No Jenis Beban Kegunaan E (Volt) In
Watt
L1 A1 R1 A2 R2 Kabel
Vd yang R Kabel
KHA
diijinkan (ΔV) (Ω/Km)
(m) (mm²) (Ω) (mm²) (Ω)
11 12 0.230047 1.61333 2.5 85.68 7.14 26 NYM
19 20 0.514048 1.20333 6 59.4 2.97 60 NYFGBY
19 11 0.282727 1.20333 6 32.67 2.97 60 NYFGBY
19 11 0.282727 1.20333 6 32.67 2.97 60 NYFGBY
19 16 0.411239 1.20333 6 47.52 2.97 60 NYFGBY
19 16 0.411239 1.20333 6 47.52 2.97 60 NYFGBY
11 8 0.102243 2.42 4 35.76 4.47 26 NYM
11 7 0.07157 3.025 4 31.29 4.47 26 NYM
11 10 0.255608 1.21 4 44.7 4.47 26 NYM
11 11 0.281169 1.21 4 49.17 4.47 26 NYM
11 12 0.061346 6.05 2.5 85.68 7.14 26 NYM
11 15 0.076682 6.05 2.5 107.1 7.14 26 NYM
11 14 0.07157 6.05 2.5 99.96 7.14 26 NYM
11 9 0.046009 6.05 2.5 64.26 7.14 26 NYM
11 11 0.084351 4.03333 2.5 78.54 7.14 26 NYM
11 13 0.099687 4.03333 2.5 92.82 7.14 26 NYM
11 12 0.061346 6.05 2.5 85.68 7.14 26 NYM
11 12 0.092019 4.03333 2.5 85.68 7.14 26 NYM
11 11 0.084351 4.03333 2.5 78.54 7.14 26 NYM
11 11 0.084351 4.03333 2.5 78.54 7.14 26 NYM
11 16 0.122692 4.03333 2.5 114.24 7.14 26 NYM
11 16 0.122692 4.03333 2.5 114.24 7.14 26 NYM
11 20 0.153365 4.03333 2.5 142.8 7.14 26 NYM
11 19 0.203975 2.88095 2.5 135.66 7.14 26 NYM
11 19 0.203975 2.88095 2.5 135.66 7.14 26 NYM
11 21 0.225446 2.88095 2.5 149.94 7.14 26 NYM
11 22 0.236182 2.88095 2.5 157.08 7.14 26 NYM
11 18 0.19324 2.88095 2.5 128.52 7.14 26 NYM
11 18 0.19324 2.88095 2.5 128.52 7.14 26 NYM
11 20 0.214711 2.88095 2.5 142.8 7.14 26 NYM
11 21 0.225446 2.88095 2.5 149.94 7.14 26 NYM
11 25 0.191706 4.03333 2.5 178.5 7.14 26 NYM
403
Ukuran E (Volt) E%
NYFGbY 4 x 25 mm² 30 A
100 A
30 A
NYFGbY 4 x 25 mm² 30 A
100 A
30 A
PLN 10 A
NYFGbY 4 x 25 mm²
10 A
224 A 100 A 10 A
NYFGBY 4 x 50 mm² 10 A
GENSET 10 A
10 A
25 A
NYFGbY 4 x 25 mm²
100 A 10 A
35 A
10 A
63 A
NYFGbY 4 x 25 mm² 10 A
100 A 10 A
10 A
10 A
10 A
NYFGbY 4 x 25 mm² 10 A
100 A 10 A
10 A
10 A
10 A
10 A
NYFGbY 4 x 25 mm² 25 A
100 A
10 A
35 A
10 A
NYFGBY 3 x 2.5 mm²
M1
NYFGBY 4 x 6 mm²
M2
NYFGBY 4 x 6 mm²
M3
NYFGBY 4 x 6 mm²
M4
NYFGBY 4 x 6 mm²
M5
NYFGBY 4 x 6 mm²
M6
NYM 3 x 2,5 mm²
M7
NYM 3 x 2,5 mm²
HEAT
NYM 3 x 2,5 mm²
FREEZER
NYM 3 x 2,5 mm²
FREEZER
NYM 3 x 2,5 mm²
AC 1
NYM 3 x 2,5 mm²
AC 2
NYM 3 x 2,5 mm²
AC 3
NYM 3 x 2,5 mm²
AC 4
NYM 3 x 2,5 mm²
AC 5
NYM 3 x 2,5 mm²
AC 6