HALAT AMMAR LAND PORT ELE

AZM ALHADETHAH AND LIGHTING IMPROV

INSPECTION AND TEST PLAN FO


INSPECTION AND TEST PLAN
OF LIGHTING SYST

Inspection codes: E.CONTRACTOR C.COMPANY


R:DOCUMENT REVIEW S:SURVEILLANCE H:HOLD POING(re
W:WTTNESS(Notification required pr
item Description of Activity Control procedure Reference
Owner's specification
Name plate, equipment classification and IP Project procedure for field material control
1
rating checked QCP for installation of Diesel driven generator
Data sheet from vendor (fromP.O)t

Owner's specification
2 Equipment checked for any damages
QCP for installation of Diesel driven generator

AFC drawing
3 Equipment fixing and mounting are secure Owner's specification
QCP for installation of Diesel driven generator
Owner's specification
Earthing completed and checked against design QCP for installation of earthing & lightning
4
requirements protection systems
AFC drawing

AFC drawing
Neutral earthing resistor to be checked against Owner's specification
5
data sheet and drawing QCP for installation of Diesel driven generator
data sheets

Owner's specification
Auxiliary power panel circuit breaker and
6 QCP for installation of switchgear and MCC'S
auxiliary circuit tested
MAR LAND PORT ELECTRICAL POWER
Date : 31.10.2022
ND LIGHTING IMPROVEMENT

N AND TEST PLAN FOR INSTALLATION


REV : 00
OF LIGHTING SYSTEMS

C.COMPANY A.THIRD PARTY(TPI) I:INSPECTION/TEST


:HOLD POING(required presence notification mandatory)
on required presence not mandatory)
Responsible party Acceptance criteria Verifying document E C
Site Electrical
Engineer & QA/QC correct as per data sheets I/W W/R
Engineer/Officer

Site Electrical
Engineer & QA/QC no damage I/W W/R
Engineer/Officer

Site Electrical
Engineer & QA/QC As per AFC drawing I/W W/R
Engineer/Officer

Site Electrical SHOP DRAWINGS &


≤1Ω TECHNICAL DATA
Engineer & QA/QC I/W S/R
As per AFC drawing SHEET
Engineer/Officer

Site Electrical
As per AFC drawing
Engineer & QA/QC I/W W/R
As per data sheet
Engineer/Officer

Site Electrical
test results as per vendor
Engineer & QA/QC I/W W/R
specification
Engineer/Officer


A

≤1Ω Ω