Professional Documents
Culture Documents
Cooling Load Calculation - Cold Room - The Engineering Mindset
Cooling Load Calculation - Cold Room - The Engineering Mindset
Cooling Load Calculation - Cold Room - The Engineering Mindset
Cooling Load Calculation for cold rooms. In this article we’ll be looking at how to calculate
the cooling load for a cold room. We’ll first look at the heat sources and then we’ll look at a
worked example of how to perform a cold room cooling load calculation in a simplified
example. Scroll to the bottom to watch the video tutorial.
With Danfoss, you can build sustainable and efficient cold rooms. Their wide range of
products and market-leading application expertise enable you to think ahead and meet
future refrigerant and energy regulations. Go green and get ahead of competition without
compromising on performance.
To remove the heat we use a refrigeration system as this allows accurate and automatic
control of the temperature to preserve the goods for as long as possible.
To remove the heat we need to know what the cooling load will be. The cooling load varies
throughout the day so in most cases the average cooling load is calculated and the
refrigeration capacity is calculated to suit this.
Transmission load
Typically 5-15% is through transmission loads. This is the thermal energy transferred
through the roof, walls and floor into the cold room. Heat always flows from hot to cold and
the interior of the cold room is obviously a lot colder than its surroundings, so heat is
always trying to enter the space because of that difference in temperature. If the cold store
is exposed to direct sunlight then the heat transfer will be higher so an additional correction
will need to be applied to allow for this.
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you
Product Load
Then we have Product loads which account for typically 55-75% of the cooling load. This
accounts for the heat that is introduced into the cold room when new products enter. Its
also the energy required to cool, freeze and further cool after freezing. If you’re just cooling
the products then you only need to consider the sensible heat load. If you’re freezing the
product then you need to account for the latent heat also as a phase change occurs. During
this time energy is used but you will not see a temperature change while the product
changes between a state of liquid and ice. There is additional energy required to further
chill this food down below the freezing point which is again sensible heat. You also need to
account for the packaging as this will inherently be cooled also. Lastly if you’re cooling fruit
and vegetables then these products are alive and they will generate some heat so you’ll
need to account for the removal of this too.
Internal load
The next thing to consider is the internal loads which account for around 10-20%. This is
the heat given off by people working in the cold room, the lighting and equipment such as
fork lifts trucks etc. So for this you’ll need to consider what equipment will be used by the
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you
staff members in order to move the products in and out of the store, how much heat will
wish. Accept Read More
they and the equipment give off and the daily duration.
https://theengineeringmindset.com/cooling-load-calculation-cold-room/ 3/11
12/19/21, 8:57 PM Cooling Load Calculation - Cold Room - The Engineering Mindset
Equipment Load
Then we need to consider the refrigeration equipment in the room which will account for
around 1-10% of the total cooling load. For this we want to know the rating of the fan
motors and estimate how long they will run for each day, then we want to also account for
any heat transferred into the space from defrosting the evaporator.
The last thing we need to consider is infiltration which again adds 1-10% to the cooling
load. This occurs when the door opens so there is a transfer of heat into the space through
the air. The other consideration is ventilation. Fruit and vegetables give off carbon dioxide
so some stores will require a ventilation fan, this air needs to be cooled down so you must
account for this if it’s used.
such as the Danfoss coolselector app for speed and accuracy. Download here –
> http://bit.ly/2Ars6yF
Transmission load
The dimensions of our cold store are 6m long, 5m wide and 4m high.
The ambient air is 30°c at 50% RH, The internal air is 1°C at 95% RH
The walls, roof and floor are all insulated with 80mm polyurethane with a U value of
0.28W/m2.K
Just to note the manufacturer should tell you what the u value is for the insulation panels, if
not, then you will need to calculate this.
A = surface area of walls roof and floor (we will calculate this) (m2)
24 = Hours in a day
To calculate “A” is fairly easy, its just the size of each internal walls, so drop the numbers in
to find the area of each wall, roof and floor.
Side 1 = 6m x 4m = 24m2
Side 2 = 6m x 4m = 24m2
Side 3 = 5m x 4m = 20m2
Side 4 = 5m x 4m = 20m2
Roof = 5m x 6m = 30m2
Floor = 5m x 6m = 30m2
Then we can run these numbers in the formula we saw earlier, you’ll need to calculate the
floor separately to the walls and roof as the temperature difference is different under the
floor so the heat transfer will therefore be different.
Q = 22 kWh/day
Floor
Q = 1.8 kWh/day
If the floor isn’t insulated then you will need to use a different formula based on empirical
data.
Remember if your cold room is in direct sunlight you’ll need to account for the suns energy
also.
For this example we’ll be storing apples, we can look up the specific heat capacity of the
apples but do remember if you’re freezing products then the products will have a different
specific heat when cooling, freezing and sub cooling so you’ll need to account for this and
calculate this separately, but in this example we’re just cooling.
There are 4,000kg of new apples arriving each day at a temperature of 5°C and a specific
heat capacity of 3.65kJ/kg.°C.
Q = kWh/day
https://theengineeringmindset.com/cooling-load-calculation-cold-room/ 6/11
12/19/21, 8:57 PM Cooling Load Calculation - Cold Room - The Engineering Mindset
Q = 16kWh/day
For this example I’ve used 1.9kJ/kg per day as an average but this rate changes over time
and with temperature. In this example we’re using a rules of thumb value just to simplify
the calculation since this cooling load is not considered critical. If you were to calculate for a
critical load you should use greater precision. In this example the store maintains a hold of
20,000kg of apples.
Q = m x resp / 3600
Q = kWh/day
Q = m x resp / 3600
Q = 10.5kWh/day
For the product section we’ll sum together the product exchange of 16kWh/day and
respiration load of 10.5kWh/day to get a total product load of 26.5 kWh/day.
We’ll estimate 2 people working in the store for 4 hours a day and we can look up and see
at this temperature they will give off around 270 Watts of heat per hour inside.
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you
Q = kWh/day
time = length of time they spend inside each day per person (Hours)
Calculation:
Q = 2.16 kWh/day
Q = kWh/day,
If we have 3 lamps at 100W each, running for 4 hours a day, the calculation would be:
Q= 1.2kWh/day
For the total internal load we then just sum the people load (2.16 kWh/day) and lighting
load (1.2kWh/day) to get a value of 3.36kWh/day.
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you
Q = kWh/day
In this cold room evaporator we’ll be using 3 fans rated at 200W each and estimate that
they will be running for 14 hours per day.
Calculation:
Q = 8.4kWh/day
Q = kWh/day,
cycles = how many times per day will the defrost cycle occur
In this example our cold room uses an electric heating element rated at 1.2kW, it runs for
30 minutes 3 times per day and the estimate that 30% of all the energy it consumes is just
transferred into the cold room.
Q = 0.54kWh/day
The total equipment load is then the fan heat load (8.4kWh/day) plus the defrost heat load
(0.54kWh/day) which therefore equals 8.94 kWh/day
Infiltration load
Now we need to calculate the heat load from air infiltration. I’m going to use a simplified
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you
equation but depending on how critical your calculation is then you may need to use other
wish. Accept Read More
more comprehensive formulas to achieve greater precision. We will use the formula:
https://theengineeringmindset.com/cooling-load-calculation-cold-room/ 9/11
12/19/21, 8:57 PM Cooling Load Calculation - Cold Room - The Engineering Mindset
Q = kWh/d
We’ll estimate that there will be 5 volume air changes per day due to the door being open,
the volume is calculated at 120m3, each cubic meter of new air provides 2kJ/°C, the air
outside is 30°C and the air inside is 1°C
Q = 9.67 kWh/day
Transmission load: 23.8kWh/day
Safety Factor
We should also then apply a safety factor to the calculation to account for errors and
variations from design. Its typical to add 10 to 30 percent onto the calculation to cover this,
I’ve gone with 20% in this example so well just multiply the cooling load by a safety factor
of 1.2 to give us our total cooling load of 86.7 kWh/day
Paul Evans
http://www.TheEngineeringMindset.com
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you