Professional Documents
Culture Documents
Method Statement For Duct Leakage Test
Method Statement For Duct Leakage Test
The engineering community has traditionally specified SMACNA’s three distinct duct sealing
classes (A, B, or C), which differ in their requirements for sealing the transverse joint,
longitudinal seams, and duct penetrations. Typically the designer will specify a Seal Class and a
percentage of the design airflow as an acceptable air leakage rate.
As reported in the SMACNA 1990 HVAC Systems Duct Design Manual, duct leakage
previously specified as an arbitrarily established percentage of the airflow was impossible to
attain by the installing contractor. Joint research conducted by SMACNA and the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) has since
developed a methodology used to relate the amount of ductwork leakage to the ductwork surface
area and the design static pressure independent of the actual airflow in the ductwork.
SMACNA publishes a table (Table 1) that correlates the Seal Class (A, B, or C) and the Leakage
Class (typically 3, 6, 12, or 48). Obviously, this assumes a superior application of sealants to the
ductwork system.
Seal Class A B C
Leakage Class – Rectangular 24 12 6
Leakage Class – Round 12 6 3
Table 1
ASHRAE’s Energy Standard 90.1 recognizes the Leakage Class method for
Lmax = CLP0.65
where:
Lmax = maximum permitted leakage in cfm/100 ft2 ductwork surface area
CL = duct leakage class, cfm/100ft2 at 1 inch water gauge
P = test pressure, which shall be equal to the design duct pressure class rating in inches water
column
In addition, the leakage class recognizes that under the best conditions, rectangular ductwork will
leak air at a rate twice greater than round.
For Bio-Containment and Hazardous discharge exhaust ducting system, SMACNA Class A
Sealing Rating is assigned.
To perform a proper duct leakage test using an orifice duct leakage tester, perform the following
steps:
1. Use the orifice plate with the recommended leakage range for your job. Refer to the test
equipment manual for selection procedure to help determine which plate(s) you can use
with your testers.
2. Make sure you have adequate electrical power for the fan. DO NOT OVERLOAD
extension cords. Make sure you use one with the proper gauge.
3. Cover all open end of the duct with isolation valve, plate clamp or other adequate method..
4. Allow all joints and seams that were sealed with duct sealer to cure for at least 24 hours or
the required cure time by the manufacturer, whichever is greater.
5. If possible, position the orifice duct leakage tester in a location where there will be a
straight path from the orifice tube outlet to the location where you will feed air into the
system.
6. Select a test pressure not in excess of the pressure class rating of the duct. The test pressure
should be the working static pressure of the exhaust duct system.
7. Calculate the allowable or allocated leakage (in cfm) using the ASHRAE’s Energy
Standard 90.1 recognizes the Leakage Class method.
8. Connect the blower and flow meter to the duct section and provide temporary seals at all
open ends of the ductwork.
9. Close the fan's inlet damper so the duct system does not get over pressurized by the tester.
10. Turn on the tester blower.
11. Adjust inlet damper until the reading on the gauge marked "Duct System" is at the system
pressure required for performing the leakage test.
12. Once the duct system pressure has been reached and stabilized, note the reading on the
gauge marked "Orifice Tube". This pressure drop reading will correspond to the amount of
air you're feeding into the duct system, which is the amount of air that is leaking out.
13. Refer to the calibration table that came with your test rig. Find the pressure reading and
note the corresponding leakage rate.
Troubleshooting:
If the "Orifice Tube" gauge exceeds the maximum range, the system is probably leaking too
much air.
Investigate system for missed outlets or unsealed joints. You can also use a larger orifice or a
gauge
with a larger range.
If you cannot obtain any pressure (or very little pressure) with the blower on and the inlet
damper wide
open, it could be due to one of the following problems:
Date :
____________________________________________
Time :
____________________________________________
Test Location :
____________________________________________
Test Conducted By :
____________________________________________
(Name) (Organization) (Signature)
Test Witnessed By :
____________________________________________
(Name) (Organization) (Signature)
Test Verified By :
____________________________________________
(Name) (Organization) (Signature)
Laboratory Type / Class
____________________________________________
Owner Details :
____________________________________________
Test Pressure :
____________________________________________
Leakage Classification
____________________________________________
Test Summary :
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________