Phone: 770-425-2724
Fax: 770-425-9319
Table of Contents • i
8.2. SERIOUS ALARM MODE .............................................................................................................................................. 14
8.3. PRESSURE SWITCH ...................................................................................................................................................... 14
8.4. DOOR SWITCH INPUT .................................................................................................................................................. 14
8.5. START DEFROST.......................................................................................................................................................... 14
8.6. SWITCH THE AUXILIARY RELAY ................................................................................................................................ 14
8.7. INVERSION OF THE KIND OF ACTION: HEATING - COOLING....................................................................................... 14
8.8. ENERGY SAVING ......................................................................................................................................................... 14
8.9. HOLIDAY DEFROST ..................................................................................................................................................... 14
8.10. ON - OFF FUNCTION ................................................................................................................................................ 14
8.11. DIGITAL INPUTS POLARITY ....................................................................................................................................... 15
9 RS485 SERIAL LINE (FOR MONITORING SYSTEMS)...................................................................................... 16
10 X-REP OUTPUT (OPTIONAL) ............................................................................................................................... 16
11 INSTALLATION AND MOUNTING...................................................................................................................... 17
12 ELECTRICAL CONNECTIONS............................................................................................................................. 17
12.1. PROBE CONNECTION ................................................................................................................................................. 17
13 HOW TO USE THE HOT KEY ............................................................................................................................... 18
13.1. HOW TO PROGRAM A HOT KEY FROM THE DEVICE (UPLOAD) ............................................................................... 18
13.2. HOW TO PROGRAM A HOT KEY FROM THE DEVICE (UPLOAD) ............................................................................... 18
14 ALARM SIGNALS .................................................................................................................................................... 19
14.1. SILENCING BUZZER/ALARM RELAY OUTPUT ........................................................................................................... 19
14.2. ALARM RECOVERY ................................................................................................................................................... 19
14.3. OTHER MESSAGES .................................................................................................................................................... 19
15 SPECIFICATIONS.................................................................................................................................................... 20
16 CONNECTIONS ........................................................................................................................................................ 21
17 E2 MODBUS NETWORK WIRING ....................................................................................................................... 22
18 ECT MODBUS NETWORKING TO E2S............................................................................................................... 23
18.1. E2 SETUP OF DEVICES .............................................................................................................................................. 23
18.1.1. Set Up Network Ports........................................................................................................................................ 23
18.1.2. Add and Connect the Device ............................................................................................................................. 24
18.2. WIRING TYPES .......................................................................................................................................................... 25
18.3. MODBUS TERMINATION BLOCKS ........................................................................................................................... 26
19 DEFAULT SETTING VALUES............................................................................................................................... 27
Press the UP arrow to see the MAX tempera- ON Continuous cycle is running
ture, to browse the parameter codes in pro-
gramming mode, or to increase the currently ON Energy saving enabled
displayed temperature value.
Press the DOWN arrow to see the MIN tem- ON Light ON
perature, to browse the parameter codes in
programming mode, or to decrease the cur- ON30 Auxiliary relay ON
rently displayed temperature value.
Table 4-1 - XR75CX Front Panel Keys and Functions ON Measurement unit
How to See the MIN Temperature Max and Min Temperature Memorization • 5
6 Main Functions 3. To change the setpoint value push the UP or
DOWN arrows within 10 seconds.
4. To memorize the new setpoint value, push the
SET key again or wait 10 seconds.
n.
The first digital input 18-20 is enabled with P3P = 8.5. Start Defrost
With P3P = n and i1F = i2F, the second digital in- A defrost will start if the right conditions exist. Af-
put is disabled. ter the defrost is finished, normal regulation will re-
The free voltage digital inputs are programmable start only if the digital input is disabled; otherwise, the
by the i1F and i2F parameters. controller will wait until the MdF safety time is ex-
pired.
Case:
Front: 32 mm x 74 mm
Dimensions Depth: 60 mm
Panel Mount: 71 mm x 29 mm panel cut-out
Housing Self extinguishing ABS
IP 20
Protection Frontal:
IP65
Connections Screw terminal block ≤ 2.5 mm2 wiring
24VAC ±10%
Power Supply
230VAC ±10%, 50/60Hz
(depending on the model)
110VAC ±10%, 50/60Hz
Power Absorption 3VA max
Display 3 digits, red LED, 14.2 mm high
Up to four (4) NTC or PT1000 probes
Inputs
Digital: free voltage contact
Compressor: SPST 8(3)A, 250VAC or SPST 16A 250VAC
AUX: SPDT 8(3)A, 250VAC or SPST 16(6)A 250VAC
Relay Outputs
Fan: SPST 5A, 250VAC
Defrost: SPDT 8(3)A, 250VAC
Data Storing On the non-volatile memory (EEPROM)
Internal Clock Back-up 24 hours
Kind of Action 1B
Pollution Grade 2
Software Class A
Rated Impulsive Voltage 2500V
Overvoltage Category II
Operating: 0 to 55°C
Temperatures
Storage: -30 to 85°C
Relative Humidity 20 to 85% (no condensing)
Measuring and Regulation NTC probe: -40 to 110°C (-40 to 230°F)
Range PT1000 probe: -100 to 150°C (-148 to 302°F)
Resolution 0.1°C or 1°C or 1°F (selectable)
Accuracy ±0.7°C ±1 digit
(ambient temperature 25°C)
Table 15-1 - XR75CX Specifications
COM4
100 Ohm
½ Watt
MODBUS TERMINATION
BLOCK 535-2711 150 ohm
Terminate last device only
Shield
Shield
E2 Modem/Expansion
COM Card Mounted COM6
Above PIB RS232
E2
XR75CX
XR75CX XR75CX XR75CX
#1
#1
#2 #3
SHIELD WIRE
(CONNECT TO PIN 18
OF LAST DEVICE)
FROM OTHER
TO LAST DEVICE
DEVICES
AT END OF DAISY
CHAIN
Table 19-1 - Default Setting Values ( *Only for models with real time clock (RTC), 2Only for XR75CX with X-REP output)
Table 19-1 - Default Setting Values ( *Only for models with real time clock (RTC), 2Only for XR75CX with X-REP output)
Table 19-1 - Default Setting Values ( *Only for models with real time clock (RTC), 2Only for XR75CX with X-REP output)