Dwelling Units More Than150m2
Dwelling Units More Than150m2
OTHER LOADS such as dryer, WM, WH, Pumps, etc not mentioned in the above demand factor is 40%
Lets compute the example in PEC, there are some typo errors in the example of PEC
(Note that convenience receptacle load refers to the outlets in toilets, outdoor, garage etc.)
Application of Demand Factor of cooking load : (See Table 2.20.3.16 Column B for 3 cooking appliances
referring to note 3 of table)
vii. One 1.5 kW microwave oven (See Table 2.20.3.16 Column A) = 1200 VA
viii. One 12-kW electric range (See Table 2.20.3.16 Column C) = 8000 VA
ix. One (ten) 20-ampere small appliance circuit@ 1 500 volt-amperes = 1500 VA (typo error)
Total Net Computed Load (AC, general lighting, cooking load subtotal, other load DL) =72840 VA