Professional Documents
Culture Documents
Statcom
Statcom
net/publication/320747539
CITATIONS READS
5 108
3 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Abdul Hamid Bhat on 17 July 2018.
Abstract—One of the major issues in the present electrical called voltage swell. It is due to switching of heavy loads, LLG
power system is power quality. The power quality problems may fault, badly dimensioned power sources and badly regulated
be of many types whether at source side or load side. Distributed transformers.
Static Synchronous Compensator (D-STATCOM) is the most
convenient device among all FACTS devices for all these power V
=0 (3)
= 1 + ℎ (4)
= 1 + ℎ (5)
ℎ
Energy
Source ISTATCOM
Inverter
(VSC) = ℎ +( − ) ℎ (10)
filter
Controller Where =( ℎ − )/ ℎ
D-STATCOM
Iab
Vsbc_s GAIN PLL c
A. PI controller
The direct and quadrature axis component of current are:
∗
= + ∗( − ) (11)
∗
= + ∗ − (12) Fig. 6. Actual current follows the reference current path
B. d-q-0 to a-b-c transformation (Inverse Park’s VII. SIMULATION MODEL AND RESULTS AND DISCUSSION
Transformation) A. Simulation model for Voltage Swell and Sag at source side
= −1 0
The programmable voltage source as shown in Fig. 8 is
modelled to generate swell and sag for the system so voltage
1
⎡ cos( ) −sin(θ)
√2 ⎤
magnitude is control to analyse the performance of D-
2 ⎢ 2 2 1⎥
d STATCOM. In this model the equivalent Thevenin source and
= ∗ cos − 3 − sin − (13) transmission line impedance has been taken and then stepped
3 ⎢ √2 ⎥
q
3
⎢ 2 2 1⎥ 0 down for distribution load side as shown in Fig. 7. The D-
⎣ cos + 3
− sin +
3 √2 ⎦ STATCOM is connected at primary distribution level at 11 kV.
The large reactive load is connected at PCC.
Fig. 7. Simulation Model of Power system with voltage swell and sag at source side
Load rms voltage phase A
V
La
PU
Load rms voltage phase B
Vb
Time/ sec
TABLE.I SYSTEM PARAMETER (SWELL AND SAG) Fig. 10. rms value of load voltage for Voltage Swell - (1) ( ), (2)
( ) , (3) ( )
S. No. System parameter Values
1 Grid rating 250 MVA 2) For Voltage Sag
2 Source voltage Vs= 230 kV L-L Voltage sag is at the side of grid. This voltage sag is
3 Distribution side voltage Vr= 11 kV L-L transferred to the load side and affects the load connected at
4 System frequency f=50 Hz pcc. Voltage drops from 1.0 p.u to 0.8 p.u. is shown in Fig. 11
5 Line Thevenin equivalent Rth= 21.16 ohm and maintains again at 1.0 with the connection of D-
resistance
6 Line Thevenin equivalent Xth= 0.6735 H
STATCOM. load voltage
reactance V
La
V
Lb VLa
time/ sec
TABLE.II D-STATCOM PARAMETER (SWELL AND SAG) Fig. 11. Load voltage in per unit for Voltage Sag
S. No. Parameters Value load rms voltage phase A
VLb
voltage is increased from 1 p.u to 1.2 p.u for this duration at time/ sec
VDC
DC link voltage/ volts
time/ sec
Fig. 9. Load voltage in per unit for Voltage Swells time/ sec
TABLE.III SYSTEM PARAMETERS (WITH FAULTS) When LLLG fault occurs at load side (at 0.2 to 0.5
S. No. System parameter Values seconds), all the three phases experience voltage drop and is
1 Feeder reactance F1= 1.0 mH reached from 1.0 p.u. to 0.7 p.u. After the connection of D-
2 Load parameter Load 1 P1=100kW,Q1=10kVARs STATCOM at 0.4 seconds the voltage maintains at 1.0 p.u as
3 Load parameter Load 2 P1= 10kW, Q1= 1 kVARs shown in Fig. 15. The fault resistance is 0.66 ohm and ground
4 Fault resistance Rfault= 0.66 ohm
5 Fault ground resistance Rg= 0.66 ohm
resistance is 0.66 ohm. Rms value of different phases of
voltage is shown in Fig. 16. The fault level can be increased to
TABLE.IV D-STATCOM PARAMETER (FOR FAULTS) show the performance of D-STATCOM but in this paper, the
fault resistance has been taken 0.66 ohm.
S. No. Parameters Value
1 DC link voltage Vdc= 18 kV 2) Single line to ground fault
2 Capacitance Cdc= 2200e-6 F
Fault occurs from 0.2 seconds to 0.5 seconds and
3 Filter reactance Lf= 1.0 mH
4 PI parameter for DC voltage Kp= 0.5, Ki= 1 STATCOM is connected at 0.4 seconds. At one phase the
5 PI parameter for reactive power Kp= 2, Ki= 10 voltage is dropped from 1.0 p.u to 0.7 p.u. So sag occurs at one
phase. By connecting D-STATCOM this voltage is maintained
and now all phases are equal and balanced shown in Fig. 17.
load voltage
V V VLa
La La
Load voltage/ pu
Load voltage/ pu
Fig. 15. Load Voltage at three-phase to ground fault load rms voltage phase A
load rms voltage/ pu
VLa
load rms voltage/ pu
VLa
STATCOM connected at 0.4 sec
VLb
V
Lb
VLc
load rms voltage/ pu
VLc
time/ sec
time/ sec
Fig. 18. rms value of load voltage at single line to ground fault (1) ( ),
Fig. 16. rms value of load voltage at 3-phase to ground fault (1) ( ), (2) (2) ( ) , (3) ( )
( ) , (3) ( )
3) Double line to ground fault The IGBT based voltage source converter (VSC) is used
This fault occurs on the load side and in two phases, which is self commutated so the switching is at proper interval
voltages is dropped and third phase voltage is increased. In of time based on the HCC technique. STATCOM maintains the
phase ‘B’ drop is little bit more than phase ‘A’ and in phase DC link voltage constant and compensates for voltage variation
‘C’ voltage is reached to 1.1 p.u during fault. After the at PCC.
connection of D-STATCOM voltages of all the three phases
maintain at rated value at 1 p.u. It is clearly shown in Fig. 19. REFERENCES
[1] Saurabh S. Kulkarni, and Naveen Kumar Mucha, “A
V
La V
Lb
V
Lc
Matlab/Simulink Model for the control scheme utilized to
improve power quality of Wind Generation System connected
to grid,” International Journal of Innovative Research in
Advanced Engineering (IJIRAE) pp: 2349-2163 Volume 1
load voltage/ pu
Issue 6, 2014.
[2] Shaik Khaja Gareeb Nawaz, and Shaik Hameed, “ Mitigation
Of Power Quality Problems By Using D-Statcom,”
International Journal Of Recent Advances In Engineering &
Technology (Ijraet), Volume-1, Issue -3, 2013
time/ sec
[3] Dhanorkar Sujata, E. Himabindu: “Voltage Sag Mitigation
Fig. 19. Load Voltage at Double Line to Ground fault (LLG) Analysis Using DSTATCOM Under Different Faults in
load voltage phase A
Distribution System” International Journal of Emerging Trends
load rms voltage /pu
VLa
in Electrical and Electronics (IJETEE – ISSN: 2320-9569)
Volume. 9, Issue. 1, 2013.
[4] Kolli Nageswar Rao, C. Hari Krishna, and Kiran Kumar
VLa
load voltage phase B
Kuthadi: “Implementation of D-STATCOM for Improvement
load rms voltage /pu
VDC
[7] Eun-Chul Shin, Sung-Min Park, Won-Hyun Oh, and Ji-Yoon
Yoo, “A novel hysteresis current controller to reduce the
switching frequency and current error in D-STATCOM,” 30th
Annual Conference of IEEE, Volume 2, Industrial Electronics
Society, 2004.
time/ sec [8] K. R. Padiyar. “FACTS Controllers in Power Transmission and
Fig. 21. DC link voltage at fault Distribution”.
[9] Narain G. Hingorani, and Laszlo Gyugyi. “Understanding
VIII. CONCLUSION FACTS Concept and technology of flexible AC transmission
systems”.
MATLAB/Simulink model with voltage sag and swell [10] Vandana S Pai, and Jo Joy, “Reactive Power Compensation
is presented in which at grid side voltage hike/drop occurs and and Harmonic Mitigation in a Grid connected system using
this swell/sag is transferred at load side and affects the STATCOM,” IJAREEIE, Volume 3, Special Issue 5, 2014.
[11] R. Mohan Mathur, and Rajiv K. Varma, “Thyristor-Based
customers, connected at PCC. The programmable voltage Facts Controllers For Electrical Transmission Systems,” A
source is used to create voltage swell and sag. All the analysis John Wiley & Sons, Inc. Publication.
is done at load side and results are presented. D-STATCOM is
connected to load side and it maintains the voltage level at 1.0
p.u. This also improves the power quality of the load side so
customers, which are connected to PCC, do not influenced by
voltage variation.
Another model is presented with different type of faults.
This model is worked on all type of fault LG, LLG and LLLG
and gave the satisfactory results. In the fault conditions, some
phase experiences voltage sags and some voltage swell. So it
compensates at all fault conditions and maintains the PCC
voltage magnitude at rated value. All simulation work has been
done on practical voltage level (Grid voltage 230kV and
primary distribution voltage 11kV).