HYDRO - OUTGOING 20KV May 29 2019
HYDRO - OUTGOING 20KV May 29 2019
S42
Properties
Customer : VUI
Project : HYDRO
Switchboard : 20kV Feeder
Cubicle : 20kV OUTGOING FEEDER
Print date : 29/05/19
Sepam xxxx (2019/5/29 9:43) page 2/24 HYDRO - OUTGOING 20KV.S42
Hardware configuration
Application type : Substation S42
Sepam label : Sepam xxxx
Sepam model : MD model (with fixed advanced UMI)
Optional modules
MES (Input / output module) : MES114 (10I + 4O module)
MET148 (8 temperature sensors module) number 1 : absent
MET148 (8 temperature sensors module) number 2 : absent
MSA141 (1 analog output module) : absent
DSM303 (Front panel UMI module) : absent
Communication interface : ACE 937/949/959
Synchronization mode : Network
Communication configuration
Communication protocol : Modbus
Sepam address : 1
Speed : 9600 Bauds
Parity : Even
Mode Telecommande : Direct
Sepam xxxx (2019/5/29 9:43) page 3/24 HYDRO - OUTGOING 20KV.S42
General characteristics
Network frequency : 50 Hz
Selection of active setting group : Setting group A
Remote setting enabled : No
Sepam working language : UK English (IEC)
Main/feeder : ANSI Main/Feeder - IEC Feeder
Rated secondary current : 5A CT
Number of CTs : Ia,Ib,Ic
Rated primary current (IN) : 100A
Base current (IB) : 100A
Demand Interval : 5min
Residual current : 2 A rated CSH120/200
Rated residual current (INr) : 2A
Rated primary voltage (VLLp) : 20kV
Rated secondary voltage (VLLs) : 100V
VT connection type : Van,Vbn,Vcn
Residual voltage measurement : sum of 3V
Meter increment Active energy : 0.1kW.h
Meter increment Reactive energy : 0.1kVar.h
Sepam xxxx (2019/5/29 9:43) page 4/24 HYDRO - OUTGOING 20KV.S42
Program logic
Circuit breaker control : Yes
Zone selective interlocking : Yes
H2 threshold : 17 %
Group B
1/2 : ZSI
3/4 : Time-based disc.
Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 Icc min.
1 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
2 Definite time 30A 200ms Definite time 0ms 6.3 kA
3 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
4 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X X
Element 2 X X
Element 3 X
Element 4 X
Sepam xxxx (2019/5/29 9:43) page 7/24 HYDRO - OUTGOING 20KV.S42
Group B
1/2 : ZSI
3/4 : Time-based disc.
Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 restraint
1 Definite time 10A 100ms Definite time 0ms
2 Definite time 10A 100ms Definite time 0ms
3 Definite time 10A 100ms Definite time 0ms
4 Definite time 10A 100ms Definite time 0ms
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X X
Element 2 X X
Element 3 X
Element 4 X
Sepam xxxx (2019/5/29 9:43) page 8/24 HYDRO - OUTGOING 20KV.S42
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1
Sepam xxxx (2019/5/29 9:43) page 9/24 HYDRO - OUTGOING 20KV.S42
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 10/24 HYDRO - OUTGOING 20KV.S42
67 : Directional overcurrent
On Latching Trip C.B.
Element 1 X X
Element 2 X X
Group B
Tripping curve Is threshold Delay Angle Direction
1 Definite time 1.26kA 100ms 45° FWD
2 Definite time 1.26kA 100ms 45° FWD
Group A advanced
Curve Timer hold Delay Timer hold Tripping logic
1 Definite time 0ms One out of three
2 Definite time 0ms One out of three
Group B advanced
Curve Timer hold Delay Timer hold Tripping logic
1 Definite time 0ms One out of three
2 Definite time 0ms One out of three
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 11/24 HYDRO - OUTGOING 20KV.S42
Group B
1 : Zone selective interlocking
2 : Zone selective interlocking
Tripping curve Isr threshold Delay Angle Vsr Threshold Direction
1 Definite time 30A 100ms 0° 2%VLLp FWD
2 Definite time 30A 100ms 0° 2%VLLp FWD
Advanced group A
Delay Memory Voltage Memory Sector
1 0ms 0%VLLp 86°
2 0ms 0%VLLp 86°
Advanced group B
Delay Memory Voltage Memory Sector
1 0ms 0%VLLp 86°
2 0ms 0%VLLp 86°
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 12/24 HYDRO - OUTGOING 20KV.S42
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Sepam xxxx (2019/5/29 9:43) page 13/24 HYDRO - OUTGOING 20KV.S42
27/27S : Undervoltage
On Latching Trip C.B. Voltage mode Voltage threshold Delay
Element 1 X Phase-to-phase 85%VLLp 500ms
Element 2 Phase-to-phase 10%VLLp 100ms
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 14/24 HYDRO - OUTGOING 20KV.S42
59 : Overvoltage
On Latching Trip C.B. Voltage mode Voltage threshold Delay
Element 1 X X Phase-to-phase 115%VLLp 200ms
Element 2 X Phase-to-phase 110%VLLp 200ms
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 15/24 HYDRO - OUTGOING 20KV.S42
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Sepam xxxx (2019/5/29 9:43) page 16/24 HYDRO - OUTGOING 20KV.S42
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Sepam xxxx (2019/5/29 9:43) page 17/24 HYDRO - OUTGOING 20KV.S42
81H : Overfrequency
On Latching Trip C.B. Frequency threshold Delay Min. voltage
Element 1 X X 55Hz 15s 20%V
Element 2 53Hz 100ms 20%V
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
81L : Underfrequency
On Latching Trip C.B. Frequency threshold Delay Min. voltage df/dt_restraint Threshold
Element 1 X X 45Hz 15s 20%V No 5Hz/s
Element 2 45Hz 100ms 20%V No 5Hz/s
Element 3 45Hz 100ms 20%V No 5Hz/s
Element 4 45Hz 100ms 20%V No 5Hz/s
Tripping behavior
O1 O2 O3 O4 O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Element 3 X
Element 4 X
Sepam xxxx (2019/5/29 9:43) page 18/24 HYDRO - OUTGOING 20KV.S42
79 : Recloser
Activity : Off
Number of reclosing shots : 1 hot
Additional dead time if CB not ready : No
Delays
Reclaim time : 10s
Blocking time until 79 ready : 10s
Dead time shot 1 : 10s
Dead time shot 2 : 10s
Dead time shot 3 : 10s
Dead time shot 4 : 10s
Sepam xxxx (2019/5/29 9:43) page 19/24 HYDRO - OUTGOING 20KV.S42
Logical equations
On Latching Trip C.B. O1 O2 O3 O4 O11 O12 O13 O14 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
50/51 - 1 X X X X X
50/51 - 2 X X X X X
50/51 - 3 X X X
50/51 - 4 X X X
50N/51N - 1 X X X X X
50N/51N - 2 X X X X X
50N/51N - 3 X X X
50N/51N - 4 X X X
50BF - 1
46 - 1 X X X
46 - 2 X X X
67 - 1 X X X
67 - 2 X X X
67N - 1 X X X
67N - 2 X X X
32P - 1 X X X
27/27S - 1 X X
27/27S - 2 X
59 - 1 X X X
59 - 2 X X
59N - 1 X
59N - 2 X
47 - 1 X
81H - 1 X X X
81H - 2 X
81L - 1 X X X
81L - 2 X
81L - 3 X
81L - 4 X
Sepam xxxx (2019/5/29 9:43) page 21/24 HYDRO - OUTGOING 20KV.S42
O1 O2 O3 O4 O11 O12 O13 O14 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
Close command by CB control X
Tripping by CB control X X
Block closing by CB control X
Pick-up X
Drop-Out
Trip circuit fault
Blocking signal 1 X
Blocking signal 2 X
RemCtrl/CB pos. discrepancy
Control circuit fault
Phase reversal
Fault recording blocked
Recloser on
Watchdog X
Sepam xxxx (2019/5/29 9:43) page 22/24 HYDRO - OUTGOING 20KV.S42
O1 O2 O3 O4 O11 O12 O13 O14 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
I11 (Open position) X
I12 (Closed position) X
I13 (Customized use) X X
I14 (Customized use)
I21 (Customized use)
I22 (Customized use)
I23 (Customized use)
I24 (Customized use)
I25 (Customized use)
I26 (Close block)
Sepam xxxx (2019/5/29 9:43) page 23/24 HYDRO - OUTGOING 20KV.S42
O1 O2 O3 O4 O11 O12 O13 O14 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
Sepam xxxx (2019/5/29 9:43) page 24/24 HYDRO - OUTGOING 20KV.S42
Function setting
Fault recording
Activity : On
Settings
Memory use : 100%
Number of records : 9
Record length : 2s
Number of cycles before trigger : 36